Table 15 — Enthalpy Operation, with Demand Controlled Ventilation (DCV) (CO
OUTSIDE AIR
DCV
GOOD TO
ECONOMIZE?
No
Below Set
Yes
No
Above Set
Yes
*With 2SP FAN DELAY (Advanced Setup Menu) when in the
economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high
and opening the OA damper 100% before the first stage mechanical
cooling is enabled.
Table 16 — Dry Bulb Operation, No Demand Controlled Ventilation (DCV) (CO
OUTSIDE AIR
DCV
GOOD TO
ECONOMIZE?
No
None
Yes
*With 2SP FAN DELAY (Advanced Setup Menu) when in the
economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high
and opening the OA damper 100% before the first stage mechanical
cooling is enabled.
Table 17 — Dry Bulb Operation, with Demand Controlled Ventilation (DCV) (CO
OUTSIDE AIR
DCV
GOOD TO
ECONOMIZE?
No
Below Set
Yes
No
Above Set
Yes
*With 2SP FAN DELAY (Advanced Setup Menu) when in the
economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high
and opening the OA damper 100% before the first stage mechanical
cooling is enabled.
Y1-I
Y2-I
FAN SPEED
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Y1-I
Y2-I
FAN SPEED
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Y1-I
Y2-I
FAN SPEED
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Y1-O
Y2-O
OCCUPIED
0-v/Off
0-v/Off
VENTMIN
24-v/On
0-v/Off
VENTMIN
24-v/On
24-v/On
VENTMIN
0-v/Off
0-v/Off
VENTMIN
0-v/Off
0-v/Off
VENTMIN to Full-Open
24-v/On
0-v/Off
VENTMIN to Full-Open
0-v/Off
0-v/Off
VENTMIN to VENTMAX
24-v/On
0-v/Off
VENTMIN L to VENTMAX Closed
VENTMIN H to
24-v/On
24-v/On
VENTMAX
0-v/Off
0-v/Off
VENTMIN L to VENTMAX Closed
0-v/Off
0-v/Off
VENTMIN to Full-Open
DELAY*
0-v/Off
VENTMIN to Full-Open
24-v/On
With stage 3 delay (STG3 DLY) in Advanced setup menu, second
stage of mechanical cooling Y2-O can be turned on after the delay if the
calls for Y1-I and Y2-I have not been satisfied.
Y1-O
Y2-O
OCCUPIED
0-v/Off
0-v/Off
MIN POS L
24-v/On
0-v/Off
MIN POS L
24-v/On
24-v/On
MIN POS H
0-v/Off
0-v/Off
MIN POS L
0-v/Off
0-v/Off
MIN POS L to Full-Open
DELAY*
0-v/Off
MIN POS H to Full-Open
24-v/On
With stage 3 delay (STG3 DLY) in Advanced setup menu, second
stage of mechanical cooling Y2-O can be turned on after the delay if the
calls for Y1-I and Y2-I have not been satisfied.
Y1-O
Y2-O
OCCUPIED
0-v/Off
0-v/Off
VENTMIN L
24-v/On
0-v/Off
VENTMIN L
24-v/On
24-v/On
VENTMIN H
0-v/Off
0-v/Off
VENTMIN L
0-v/Off
0-v/Off
VENTMIN L to Full-Open
24-v/On
0-v/Off
VENTMIN H to Full-Open
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
24-v/On
0-v/Off
VENTMIN L to VENTMAX
24-v/On
24-v/On
VENTMIN H to VENTMAX
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
0-v/Off
0-v/Off
VENTMIN L to Full-Open
DELAY*
0-v/Off
VENTMIN H to Full-Open
24-v/On
With stage 3 delay (STG3 DLY) in Advanced setup menu, second
stage of mechanical cooling Y2-O can be turned on after the delay if the
calls for Y1-I and Y2-I have not been satisfied.
42
Sensor) — 1 Speed Fan
2
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Sensor) — 2 Speed Fan
2
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Sensor) — 2 Speed Fan
2
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed to Full-Open
Closed to Full-Open