Par t 16: Electrical installations inspection and maintenance GB50257-2014 Code for construction and acceptance of electric device for explosive atmospheres and fire hazard electrical equipment installation engineering GB15577-2018 Safety regulations for dust explosion prevention and protection. IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Allow time for temperature to normalise after isolation to avoid the danger of burns. 1.10 Tools and consumables Before starting work ensure that you have suitable tools and/ o r consumables available. Use only genuine Spirax Sarco replacement parts. IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk.
2.1 Introduction The IPC6 is a Electro-pneumatic convertor requiring an air supply between 1.5 and 8 bar g. It will convert a 4 -20mA signal into an air pressure signal. The IPC6 can be mounted directly onto a flat surface, or using mounting kits for panel, wall or pipe mounting.
Fig. 1c Nameplate - CCC / NEPSI / ATEX / IECEx 2.3 Operating principle The IPC6 is an electro-pneumatic device that converts a DC input signal to a pneumatic output. This device is made up of two sections, the Primary Converting Section and the Pneumatic Relay Section. The Coil Fig.
3. Installation The IPC6 is supplied with a wall mounting kit and a DIN Rail Mounting Kit. Mounting Kit PMK is available when installing the unit on a 2" pipe, see Figure 5. 1 1/2 38.1 1 1/2 38.1 19.1...
Use a filter to remove dirt and liquid in the air line ahead of the convertor. The user is responsible for insuring that the environment in which the unit will be installed and the operating gas are compatible with the materials in the convertor. IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
All units have the capability to be split ranged or set for any output in the range as long as the Output Span is equal to or greater than the minimum Span. IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Page 11
Terminal #3 (NA) not used Terminal #2 (-) negative ground (NA) Terminal #1 Not used (+) positive Note: Not used on ATEX intrinsically safe units Fig. 6 Fig. 6 Fig. 6 IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Date of purchase Original order number iii. Serial number Please return all items to your local Spirax Sarco branch. Please ensure all items are suitably packed for transit (preferably in the original cartons). IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Zero and span adjust Low or improper Supply pressure low Span adjust Output leakage DC signal Loose wires or connections Erratic operation Liquid in air supply Dirt in magnet gap IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Page 14
Rating : Ex ia IIC T4 Ga/Ex iaD 20 T135°C Certification No. : GYJ21.1274X CCC / NEPSI Ambient temperature : -40 ~ +70 °C (-40~+158 °F) Safety parameters: Ui=28V, Ii=93mA, Pi=0.65W, Ci=0, Li=0 IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...
Page 15
On behalf of: Spirax Sarco Ltd, (name, function): M Sadler Steam Business Development Engineering Product Integrity & Compliance Manager (place and date of issue): Cheltenham 2021-06-24 GNP234-EU-C/02 issue 1 (EN) Page 1/1 IPC6 and IPC6 ATEX Electro-pneumatic Convertor IM-P705-02 CTLS Issue 3...