POSITION
1
Insulating body
2
Upper conducting body
3
Lower conducting body
4
Tightening screw
5
Wire clamping collar
Cabur terminal block type DBC.2 allows the direct and anti-loosening connection of solid, stranded and flexible conductors, by
means of wire clamping collars, captive screws and conducting body.
Each clamping unit shall house only one conductor
The insertion of the cable is eased by:
Sloping entrance planes provided on the insulating body
A tab provided in the collar that avoids faulty introduction of the conductors
Adequate dimensioning of the conductors insertion hole, with respect to the diameter of the maximum connectable conductor
(according to the different Gauges prescribed by IEC 60947-1Std.)
Appropriate grooving, provided in the wire clamping collar and on the conducting body guarantee a perfect electrical contact and an
efficient blocking of the conductor. Both the wire clamping collar and the tightening screw are manufactured in tempered steel with
galvanic RoHS conforming zinc plating; thanks to their coupling it is possible to apply the correct contact pressure
By acting on the tightening screw, the collar tightens the conductor against the conducting body, which is manufactured in tin-plated
copper. With the clamping yoke tightening system a gas proof, particularly safe connection is guaranteed
limiting wall is reached. By holding firmly the conductor in one hand, tightening operation must be performed (applying the
prescribed torque values given in the table). Once this operation is performed the conductor is firmly secured.
Thanks to the force applied during the tightening process, the overlapped threaded parts system acts, by means of elastic
deformation on the head of the screw, blocking it and avoiding subsequent loosening
Fig. A
COMPONENT
Thanks to the force applied during the tightening process, the overlapped threaded parts system act,
by means of elastic deformation on the head of the screw, blocking it and avoiding subsequent
loosening
For the connection of the conductor it is necessary to:
1)
Loosen the tightening screw (Pos.4 - Fig. A) until it frictions, making the collar (Pos.5 - Fig. A)
reach its lower position; once this operation is performed, the conductor's insertion hole results
to be completely open and is ready to house the conductor.
2)
Prepare the conductor by stripping one end from its insulation (Fig. B) and according to the
correct insulation stripping length given in the table. introduce it in the terminal block until the
TECHNICAL NOTE
TERMINAL BLOCK
STRIPPING LENGTH
DBC.2
Note(*): values taken from Table 4 of IEC 60947-1 Std.
Page Rev.
31
3
4
Fig. B
INSULATION
TIGHTENING
[ mm ]
9
Date
Issued
18/07/14
TORQUE
[ Nm ] (*)
0,4
Approved