Download Print this page

EpiSensor ZDR-16 Install Sheet

Wireless demand response controller
Hide thumbs Also See for ZDR-16:

Advertisement

Quick Links

Voltage References & Current Transformer Wiring Diagram
Note: By default, a
single phase supply is
taken from L1 and N to
power ZDR (not shown
on this diagram). This
can be replaced with a
separate auxiliary
supply if required.
N
L1
CT3
CT2
CT1
-
-
-
+
+
Important: Fused disconnect
or circuit breakers (not
2
supplied) to protect 0.75mm
conductor according to local
electrical regulations (min.
500mA)
3-Phase
Supply
L1
N
L2
L3
L2
Note: Insulation
colours for CT /
Rogowski coil cables
can vary
+
Configuration: 4 WIRE WYE
ANSI Meter Form: 9S/16S
Inputs: 3 x Vref, 3 x CT
Note: configure ZDR on Gateway for 9S/16S
L3
CT3
Phase C
CT1
Phase A
Neutral
CT2
Phase B
Install Sheet
ZDR-16
//
Wireless Demand Response Controller
Document Ref. EPI-065-02
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
NEVER work alone.
Use appropriate personal protective equipment (PPE) and follow safe electrical work practices.
Only qualified electrical workers should install this equipment. Such work should be performed only after
reading the entire set of installation instructions.
If the equipment is not used in a manner specified by EpiSensor, the protection provided by the equipment
may be impaired.
Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of
electric power. Assume that all circuits are live until they have been completely de-energized, tested, and
tagged. Pay particular attention to the design of the power system. Consider all sources of power, including
the possibility of backfeeding.
Turn off all power supplying the meter and the equipment in which it is installed before working on it.
Always use a properly rated voltage sensing device to confirm that all power is off.
Before closing all covers and doors, inspect the work area for tools and objects that may have been left
inside the equipment or panel.
When removing or installing metering or other equipment, do not allow it to extend into the energised bus.
The successful operation of this equipment depends upon proper handling,
Neglecting fundamental installation requirements may lead to personal injury as well as damage to
electrical equipment or other property.
Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the energy meter is
installed, disconnect all input and output wires to the energy meter.
High voltage testing may damage electronic components contained in the meter.
Failure to follow these instructions will result in death or serious injury.
Installation & Safety Notes
EpiSensor equipment should be installed, operated, serviced and maintained only by qualified personnel.
EpiSensor does not assume any responsibility for any consequences arising out of the use of this
equipment.
The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage
exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more
information on available product variants. For voltages exceeding 480 V L-L, a voltage transformer must
be used.
Fuse for neutral terminal is required if the source neutral connection is not grounded.
Clearly label the device's disconnect circuit mechanism and install it within easy reach of the operator.
The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault
current.
Depending on the type of current transformers used with the EpiSensor ZDR, shorting links may be
required. Please consult the user guide for more information.
If Voltage Transformers are used, the VT ratio setting should be adjusted on the ZDR settings page on the
Gateway.
By default, there will not be a cable included for mains reference voltages
ZDR's using Rogowski coil or milliamp Current Transformers are individually calibrated and the current
transformer cables should not be extended or interchanged.

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZDR-16 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EpiSensor ZDR-16

  • Page 1 ➔ supplied) to protect 0.75mm The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage conductor according to local exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more ANSI Meter Form: 9S/16S electrical regulations (min.
  • Page 2 ➔ supplied) to protect 0.75mm The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage conductor according to local exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more ANSI Meter Form: 5S/13S electrical regulations (min.
  • Page 3 ➔ supplied) to protect 0.75mm The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage conductor according to local exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more electrical regulations (min.
  • Page 4 ➔ The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more information on available product variants. For voltages exceeding 480 V L-L, a voltage transformer must be used.
  • Page 5: Input Voltage

    Install Sheet Installation Checklist ZDR-16 Wireless Demand Response Controller Document Ref. EPI-065-02 Input Voltage If the mains power supply of the ZDR is powered directly from the 3-phase voltage reference, ensure that the voltage does not exceed 480V AV L-L...