200 Amp Charge Controller with Digital LED Volt Meter for Wind & Solar
12 or 24 volt. See more about this product on YouTube at:
Disconnect Mode (Solar)
Disconnects solar when batteries are full. Wind should have
a diversion load. You can run multiple wind and solar in both
diversion and disconnect modes simultaneously.
Solar Panels:
– This controller DOES NOT
reduce solar voltage so you
will need to wire your panels in
parallel!!!
Max Solar
Solar Panel Voltage
Watts
12v
840
12v (with cooling fan)
1,200
24v
1,680
24v (with cooling fan)
2,400
Solar Panel
(not included)
– Orient controller as drawn. Leave about 6-8 inches
(20 cm) of clear space around it to keep cool.
– Solar + input on left side relay must enter as
shown, if reversed no current will flow and your
batteries won't charge from solar.
– Battery + input on right side relay MUST enter top
right side of relay as shown, if reversed no current
will flow and your batteries over charge.
See arrows!!!
https://youtu.be/fC_vK_eKxPA
DC Water Heating Element
Diversion Load "Dump Load"
(Optional, may not be included.
Dump load needed only for wind, not solar. )
Battery Bank
(not included)
These cables
come pre-wired.
Charge
Controller
2 4 . 0
Blow Hard + Shine Bright
Divert Mode (Wind and/or Solar)
Diverts ("dumps") wind and/or solar when batteries are full. You
can divert multiple wind and solar simultaneously. You can divert
to your dump load resistors and/or DC water heating elements
and more, simultaneously.
(not included)
These cables
come pre-wired.
Cooling Fan Location:
– Mount fan with two bolts that extend the length of the
heat-sink fins. Use washer to hold fan against heat-sink.
– Locate cooling fan under each relay pulling over
70 amps or relay failure will occur!!
332 Cobble Stone Drive, Seymour, MO 65746
www.mwands.com
Model:
Date: 07/2018
Page: 1 of 2
Diversion Loads:
– You must use a diversion load when
using wind or hydro. Very large wind
turbines and hydro can sustain high amp
outputs. Make sure your dump load is
rated above the amp draw of them.
– You must install a cooling fan under
the relay heat-sink if drawing more than
70 amps.
Wind Turbine
Diversion
12v
12v (with cooling fan)
24v
24v (with cooling fan)
End View
Air Flow
• (417) 708–5359
200ECCDIGSSR