Ecosaire representative. Your ® customer’s satisfaction is at stake and the Ecosaire ® warranty may be void if conditions explained in this manual are not met. Data subject to change without notice.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Contents Ecosaire EN Series ® Page Product Description Precision Environmental Unit Nameplate Building Control for Industrial and Moisture Migration Commercial Applications Installation Unpacking & Locating Locate Remote Condenser Unit-Duct Connections Standard Practice for Ducts ®...
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description All sensitive electronic equipment The Supervisaire ® Microprocessor The computer-site conditions and requires a stable environment for Controls provide extremely user- utilities will determine the type of optimum performance. The friendly, programmable monitoring environmental control units selected.
Page 5
® Owners Manual Ecosaire EN Series Precision Air Conditioner Product Description EN Series Standard Features Deep-pleated filters rated at 30% adjustment of the air flow, resulting efficiency by the ASHRAE 52-76 from changes in external static pres- The cabinet and frame are construct- method are standard on all Ecosaire®...
Page 6
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description Major Cooling Options Air-Cooled Direct Expansion Ecosaire ® unit operates its refrigeration system as needed to control room conditions. Remote Condenser Heat is transported via refrigerant-vapor flow to an outdoor air-cooled condenser.
Page 7
® Owners Manual Ecosaire EN Series Precision Air Conditioner Major Cooling Options Product Description Glycol-Cooled Direct Expansion ® The Ecosaire unit operates its refrigeration sys- tem as needed to control room conditions. Heat is transferred via pumped glycol-fluid flow to an outdoor heat exchanger.
Page 8
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description Major Cooling Options FreeCool When the outdoor temperature is above ® 60°F (16°C), the Ecosaire unit operates its refrigeration system to move heat into a Ecosaire flow of glycol solution. Refrigeration con- densing pressure is controlled by pressure- controlled throttling valves.
Page 9
® Owners Manual Ecosaire EN Series Precision Air Conditioner Major Cooling Options Product Description Air-Cooled DualCool Normally, heat is transferred to a flow Ecosaire of chilled water (by others). DualCool units include a three-way proportional chilled-water valve, balanced bypass line, flow switch and water-temperature sensor.
Page 10
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description Major Cooling Options Glycol-Cooled DualCool Normally, heat is transferred to a flow of chilled water (by others). DualCool units include a Ecosaire three-way proportional chilled- water valve, balanced bypass line, flow switch and water-tem- perature sensor.
Page 11
(by others) Chilled Water The Ecosaire unit increases or decreases the flow of chilled water (by others) through an inter- nal heat exchanger to control room conditions. The unit is rated for use with 45°F chilled water.
Page 12
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description Air-Flow Options Airflow Pattern U Airflow Pattern W Airflow Pattern R Airflow Pattern S Airflow Pattern N Airflow Pattern M Data subject to change without notice. Ecosaire ® July 2009...
Page 13
® Owners Manual Ecosaire EN Series Precision Air Conditioner Model Designation Chart Product Description EN U G 068 F Z 6 9 E H F S C G K L T Y Miscellaneous: SERIES: Condensate Pump Hot Gas Bypass EN: Ecosaire EN series...
® Ecosaire EN Series Precision Air Conditioner Owners Manual Product Description Unit Nameplate PRECISION CONTROL AIR CONDITIONER Before calling for assistance, be sure to have the UNIT MODEL model, serial, and tag numbers available for the SERIAL # service department.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Moisture Migration Building Construction In order to prevent moisture migra- tion, the room (including the ceiling plenum, if any) must have a sealed vapor retarder. Rooms with concrete walls or floor should be painted with a rubber- or plastic-based paint.
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Unpacking and Locating Ecosaire® Unit Important! Do not allow water, plaster, con- Inspect your unit immediately crete, dusts, or other foreign materi- for shipping damage. Claims for als to enter any open pipes or tubes.
Page 17
Outdoor condensers (with Ecosaire unit of Cooling Type = A) must have no more than 100 ft. (30 m) of tube (one way) connecting to the Ecosaire unit. Areas subject to heavy snow and ice accumulation should be avoided.
Page 18
Outdoor condensers (with Ecosaire unit of Cooling Type = A) must have no more than 100 ft. (30 m) of tube (one way) connecting to the Ecosaire unit. Areas subject to heavy snow and ice accumulation should be avoided. Areas subject to public access should be avoid- ed.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Unit-Duct Connection Ductwork Installation Important! specified for each unit. Static aerofoil turning vanes and acoustic pressures higher than specified insulation. Poor duct design can Where located in areas below may reduce air flow below the mini- reduce the amount of air mum acceptable value.
Page 20
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Ductwork Unit-duct Connection Supply Duct Refer to AMCA 1 guidelines for system effect considerations. Some installations may use supply duct. To prevent unexpected external energy loss, allow a section of straight duct with a length...
Page 21
® Owners Manual Ecosaire EN Series Precision Air Conditioner Standard Practice Ductwork Installation 2.5 W or more RETURN DUCT RIGHT WRONG Turning Vanes Vanes and straight length The air will not be evenly dis- Always install allow air to flow evenly.
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Humidifier For installation connections for the humidifier, please refer to the Carel humidifier manual included with this manual. Data subject to change without notice. Ecosaire ® July 2009...
® Owners Manual Ecosaire EN Series Precision Air Conditioner Condensate Piping Installation IMPORTANT! Select materials Fill P-trap The condensate drain must be Ordinary schedule 40 PVC or ABS To prevent air from being drawn installed and the P-trap must be...
Page 24
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Refrigerant Note below the operation of rotalock service valves, as found on Ecosaire® compressors and receivers. To System To System If pressure testing, be sure to isolate the compressor from high pressure.
Page 25
® Owners Manual Ecosaire EN Series Precision Air Conditioner Refrigerant Piping Installation Air-Cooled Direct Expansion and DualCool Units Only When shipped, remote air-cooled units contain a refrigerant holding charge. The holding charge must be reclaimed before removing the caps on the remote-condenser tube stubs. Failure to reclaim the holding charge can lead to property damage and/or personal injury.
Page 26
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Refrigerant Air-Cooled and DualCool units Only NOTE: After the following step, installation must proceed immediately and rapidly to the evacuation stage, since the filter-drier will be exposed to atmosphere.
Page 27
® Owners Manual Ecosaire EN Series Precision Air Conditioner Refrigerant Piping Installation Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only Equivalent R-410a condenser-connecting tube sizes, inches O.D. length of tube, ft., EN-027A EN-035A EN-042A EN-051A EN-068A EN-079A EN-087A EN-102A one way Gas Liq.
Page 28
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Refrigerant Tube Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only IMPORTANT: Cut tubes as necessary using a tube- cutter only. DO NOT use a saw. Total length of tube not to exceed 100 ft one Never apply heat to a refrigerant line way.
Page 29
® Owners Manual Ecosaire EN Series Precision Air Conditioner Calculate Refrigerant Charge Piping Installation Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only For options, see Product Description - Model Designation Chart. Note: Water- and Glycol-cooled units are shipped with a full refrigerant charge.
Page 30
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Calculate Oil Charge Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only BOX A pounds of refrigerant Some installations may require the addition of extra refrigeration oil. 1. Note the compressor model from the compressor nameplate.
Page 31
® Owners Manual Ecosaire EN Series Precision Air Conditioner Installation This page intentionally left blank. Data subject to change without notice. ® Ecosaire July 2009...
Page 32
Open the receiver isolation valves (if any). Open the compressor(s) rotalock valves to the access (middle) position. The Ecosaire® unit, condenser, and tubes must be evacuated to a pressure below 500 microns of mercury as measured by an electronic vacuum gauge. Compound gauges as found on refrigeration manifolds are not adequate.
Page 33
Piping Installation Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only Each circuit of an Ecosaire unit may have two liquid-line solenoid valves. Release the liquid-line solenoid valve from the locked-open position by turning the manual stem counter- clockwise all the way.
Page 34
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Water Water-Cooled Direct-Expansion and Water-Cooled DualCool Units Only can contaminate the system and Condenser water pipes must be IMPORTANT: damage components. sized to deliver the required con- Contact the factory before using If flux must be used, use only denser water flow.
Page 35
® Owners Manual Ecosaire EN Series Precision Air Conditioner Glycol Piping Installation Glycol-Cooled Direct-Expansion, Glycol-Cooled DualCool, & FreeCool Units Only Fill port at highest point. On the remote DryCooler, installed anywhere air can Ecosaire mount the pump to its be trapped in the system.
Page 36
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Piping Glycol Filling Glycol-Cooled Direct-Expansion, Glycol-Cooled DualCool, & FreeCool Units Only After all piping connections have damage components. The pipe plugs on the pump impeller been completed, the system should...
Page 37
® Owners Manual Ecosaire EN Series Precision Air Conditioner This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Wiring Power units with factory-supplied dis- IMPORTANT! Insure phase rotation connects, follow instructions Before working on this or any All the motors in the unit are con- inside the disconnect.
Page 39
® Owners Manual Ecosaire EN Series Precision Air Conditioner Power Wiring Installation Remote Condensers and Heat Exchangers Select branch-circuit voltage from the condenser nameplate data. Select branch-circuit conductors from the condenser nameplate data. Connect the conductors as shown. Note that L3 will not be pres- ent on single-phase condensers.
Page 40
Some installations may use the optional emergency power input. In this case, an open circuit on the input will register terminal 300 an alarm and will cause the number of operating Ecosaire® units in a group to be reduced to a predefined number to Switch opens to reduce the load on the emergency generator.
Page 41
Control Wiring Wiring Installation GENERAL ALARM Ecosaire® Ecosaire® units may be provided with an output for a terminal 1 general alarm. Two dry-contact switch-closures are provided to enable an alarm (by others) in the event of a contacts close to to alarm condition that prevents the normal operation of the unit.
Page 42
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Wiring Control Wiring This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
Page 43
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Wiring Control Wiring Optional Remote Display Note: Cables may be supplied , depending on options. The communication system between the controller and the remote display (if any) is based on ANSI/IEEE RS- 485.
Page 44
® Owners Manual Ecosaire EN Series Precision Air Conditioner Control Wiring Wiring Installation Optional Remote Display Assembling data (reversed) modular telephone cable Note that the lock tabs of the plugs are on opposite sides of the cable. (Colors are for example only, colors may vary by cable vendor.)
Page 45
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Wiring Control Wiring Optional Remote Display Unit Controller Insert 6P6C modular tele- phone plug (by others) into the For cable lengths not modular port. exceeding 650 ft (200m) - Note: Cables may be supplied by Dectron, depending on options.
Page 46
® Owners Manual Ecosaire EN Series Precision Air Conditioner Control Wiring Wiring Installation Optional Remote Display For cable lengths not exceeding 1640 ft (500m) - Note: Cables may be supplied by Dectron, depending on options. Keep pair together. Consult factory for longer cable DO NOT SPLIT requirements.
Page 47
® Ecosaire EN Series Precision Air Conditioner Owners Manual Installation Wiring Control Wiring Remove the display from its box. Refer to the instruc- tions included. Separate the display into its three pieces. Thread the end of the cable thorugh the hole in the sub- base as shown.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Contents Startup Page ® Supervisaire Controller Interface Pre-Startup Adjustments Airflow Remote Heat Exchanger Pre-Startup Checklist Enable Operation Expansion Valve Adjustment Startup Report & Warranty Registration Warranty Data subject to change without notice.
Page 49
IMPORTANT! Never run the blower without the filters in place. Regardless of filters, never run the blower when con- struction dust is present. The resulting heat exchanger damage is not covered by the Ecosaire® warranty. IMPORTANT! Airflow must be set and confirmed before the refrigeration system is adjusted.
Page 50
HEAT EXCHANGER FAN THERMOSTATS Remote heat exchangers have a minimum number of fans that run whenever the Ecosaire® unit is in cooling mode. Other fans may be controlled by thermostats sensing outdoor air temperature. Where this is the case, the thermostats must be adjusted at installation, using the diagrams below.
Page 51
® Ecosaire EN Series Precision Air Conditioner Owners Manual This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
Page 52
® Owners Manual Ecosaire EN Series Precision Air Conditioner Adjust Remote Heat Exchanger Controls Startup Air-Cooled Direct Expansion, Glycol-Cooled Direct Expansion, Air-Cooled DualCool, & Glycol-Cooled DualCool Units Only For glycol coolers, be sure that the system is full of glycol solution.
Page 53
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Check Remote Heat Exchanger Operation Glycol-Cooled Direct Expansion, Glycol-Cooled DualCool, & FreeCool Units Only (continued from previous page) Check that the glycol solution is flowing at the proper flow rate. See table below.
Page 54
® Owners Manual Ecosaire EN Series Precision Air Conditioner Open Refrigerant Valves Startup Ecosaire For all circuits, be sure the compressor rotalock valves are open. Air-Cooled Direct Expansion and Air-Cooled DualCool Units Only Locate the refrigerant receiver in the remote condenser.
Page 55
® Ecosaire EN Series Precision Air Conditioner Owners Manual This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
Page 56
® Owners Manual Ecosaire EN Series Precision Air Conditioner Check Valve Positions Pre-Startup Adjustments Startup Ecosaire For Water-Cooled Direct-Expansion units, be sure any water valves (by others) are open. For Glycol-Cooled Direct-Expansion units, be sure any glycol valves (by others) Ecosaire are open.
Page 57
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Humidifier Humidifier (if any) Some units may be equipped with electrode-type humidifiers. Refer to the humidifier manual supplied with this manual. Data subject to change without notice. Ecosaire ® July 2009...
Page 58
® Owners Manual Ecosaire EN Series Precision Air Conditioner Prepare to Add Refrigerant Startup Air-Cooled Direct Expansion & Air-Cooled DualCool Units Only For Air-Cooled Direct Expansion or Air-Cooled DualCool units, the required weight of refrigerant should have been added when the remote condenser was installed in Installation - Piping - Refrigerant. If all the necessary refrigerant was not added during installation, it must be added at startup.
Page 59
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Prepare to Adjust Expansion Valves Air-Cooled Direct Expansion, Water-Cooled Direct Expansion, Glycol-Cooled Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool, & FreeCool Units Only The refrigerant expansion valves must be adjusted at startup.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Pre-Startup Checklist Startup ________ Model _____________ Serial Number Print your initials in the Piping Wiring boxes to indicate comple- For Air-Cooled Direct Confirm that the voltage to be tion. Print “N/A” for items Expansion &...
Page 61
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Pre-Startup Checklist Model ________ Serial No. ____________ Unit preparation Confirm that all ducts and Exchanger (if any) plenums have been sized and Confirm that the Ecosaire ® Confirm that the heat...
Page 62
® Owners Manual Ecosaire EN Series Precision Air Conditioner Pre-Startup Adjustments Startup Set Clock Note: This adjustment requires the user password, see Startup - Pre-start- up Adjustments - Controller Password. The clock is set at the factory for date and Eastern Time. These settings can be changed as below.
Page 63
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Pre-Startup Adjustments Humidity Set Points Note: This adjustment requires the user password, see Startup - Pre-startup Adjustments - Controller Password. ↵ ↵ Press Prg, enter the password, and press , as discussed in Startup - Pre- startup Adjustments - Controller Password.
Page 64
® Owners Manual Ecosaire EN Series Precision Air Conditioner Temperature Set Points Pre-Startup Adjustments Startup Note: This adjustment requires the user password, see Startup - Pre-startup Adjustments - Controller Password. To adjust the temperature set point screen, first press Prg, enter the password, ↵...
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Enable Operation IMPORTANT! Start-up must be performed by a qualified factory-trained service and installation technician. Once startup is completed, all portions of the “Startup Report and Warranty Registration” form must be completely filled in and a copy must be sent to the factory in order to register and validate the warranty.
Page 66
® Owners Manual Ecosaire EN Series Precision Air Conditioner Adjustments Startup Adjust Head Pressure Air-Cooled Direct Expansion Units Only For each refrigeration circuit: With the compressor running, check that the refrigerant sight glass is full. Check the suction pressure and the discharge pressure at the compressor.
Page 67
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Adjustments Water-Cooled Direct Expansion, Glycol-Cooled Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool, & FreeCool Units Only With the compressor running, check that refrigerant sight glass is full. Check the suction pressure and the discharge pressure at the compressor.
Page 68
® Owners Manual Ecosaire EN Series Precision Air Conditioner Add Refrigerant and Adjust TXV Startup The evaporator superheat must be adjusted at startup. It should be 12°F ± 2°F (6°C ±1°C) for room temperatures between 68°F (20°C) and 73°F (23°C).
Page 69
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup View Status FOR GLYCOL-COOLED AND FREE-COOL UNITS ONLY This page is left blank intentionally Data subject to change without notice. Ecosaire ® July 2009...
® Owners Manual Ecosaire EN Series Precision Air Conditioner Startup ECOSaire® Startup Report & Warranty Registration Warranty void unless this form is completed and a copy returned to factory within 2 weeks after start-up! Installation Name....................................Installation Address ....................................®...
Page 71
® Ecosaire EN Series Precision Air Conditioner Owners Manual Startup Ecosaire® EC Series Start-up Report & Warranty Registration Warranty void unless this form is completed and a copy returned to factory within 2 weeks after start-up! Operational Data NOTE: To obtain adequate readings, a delay of ten (10) minutes is required after every operation or adjustment.
Page 72
® Owners Manual Ecosaire EN Series Precision Air Conditioner Dectron Internationale Terms and Conditions of Sale for Products Installed in the United States of America and Canada Ecosaire® Units and Factory-Supplied Accessories 1. This Contract constitutes the entire deliver in accordance, with the provi-...
Page 73
® Ecosaire EN Series Precision Air Conditioner Owners Manual Dectron Internationale Terms and Conditions of Sale for Products Installed in the United States of America and Canada Ecosaire® Units and Factory-Supplied Accessories 14. The conditions below apply to all war- dures.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Contents Operation Page Maintenance Schedule Maintenance Record Maintenance Tasks Logical Flow Charts Supervisaire ® Controller Interface Password Enable / Disable Clock Set Point Change Alarms Alarm History Component Run Times Supervisaire ®...
Page 75
In the event of a future shutdown, leave power on the unit for the crankcase heaters if safe to do so. To start the Ecosaire® unit again, follow the steps in the STARTUP section of this manual. Data subject to change without notice.
® Owners Manual Ecosaire EN Series Precision Air Conditioner Maintenance Record Maintenance Operation Photostat the next two pages as needed. Tape the spine edges of the copies together. Post the copies as appropriate to be filled out by maintenance personnel.
Page 77
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Maintenance Maintenance Record DATES No alarms? Room temperature Room humidity Air filters clean? Humidifier strainer clean? Humidifier high-water sensor not lit? Condensate drain- pan clean? Remote heat- exchanger clean? Remote heat-...
Page 78
® Owners Manual Ecosaire EN Series Precision Air Conditioner Maintenance Record Maintenance Operation DATES Data subject to change without notice. Ecosaire ® July 2009...
Page 79
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Maintenance This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
Page 80
® Owners Manual Ecosaire EN Series Precision Air Conditioner Air Filters Maintenance Operation Air filters should be checked at least every month. Dirty filters can prevent proper operation and can lead to expensive repairs. If filters are dirty, replace them with filters of equal per- formance.
Page 81
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Maintenance Remote Heat Exchanger Air-Cooled Direct Expansion, Glycol-Cooled Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool, & FreeCool Units Only NOTE: Units must be completely disconnected before servicing. 1. Be sure the remote condenser has not been damaged.
Page 82
® Owners Manual Ecosaire EN Series Precision Air Conditioner Refrigerant Sight Glasses Maintenance Operation Be sure there are no bubbles or droplets in the refrigerant sight glasses after five minutes of compressor operation. If bubbles or droplets are noted, contact a service technician or the factory.
Page 83
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Maintenance Humidifier Humidifier (if any) Some units may be equipped with electrode-type humidifiers. Refer to the humidifier manual supplied with this manual. Data subject to change without notice. Ecosaire ®...
Page 84
® Owners Manual Ecosaire EN Series Precision Air Conditioner This page intentionally left blank. Data subject to change without notice. Ecosaire ® July 2009...
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Logical Flowchart General Flowchart Specific units may vary. Enabled? Run blower Temperature Humidity set point set point Room air Room air temp. humidity Temperature Humidity Enable < set point? < set point?
Controller Interface Operation The Supervisaire controller handles all the functions of the Ecosaire® unit. The initial startup at installation requires the manual input of the set points and permission to run. After this all functions are fully automatic.
Page 87
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Controller Password NOTE: The password will be cleared automatically if no button activity for the duration of the password timer Some settings require the User Password. To enter the password when ↵...
Page 88
® Owners Manual Ecosaire EN Series Precision Air Conditioner Enable and Disable Unit Operation Note: This adjustment requires the user password, see Startup - Pre-Startup Adjustments - Controller Password. To access the System ON/OFF menu, press Prg and enter the password as discussed in Startup - Pre-startup Adjustments - Controller Password .
Page 89
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Clock Change Date and/or Time Note: This adjustment requires the user password, see Startup - Pre-startup Adjustments - Controller Password. The clock is set at the factory for date and Eastern Time. These settings can be changed as below.
Page 90
® Owners Manual Ecosaire EN Series Precision Air Conditioner Change Room Humidity Set Points Operation Note: This adjustment requires the user password, see Startup - Pre-startup Adjustments - Controller Password. ↵ ↵ Press Prg, enter the password, and press , as discussed in Startup - Pre- startup Adjustments - Controller Password.
Page 91
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Change Room Temperature Set Points Note: This adjustment requires the user password, see Startup - Pre-startup Adjustments - Controller Password. To adjust the temperature set point screen, first press Prg, enter the password, ↵...
® Owners Manual Ecosaire CN Series Precision Air Conditioner Alarms Operation If an alarm other than Power Restart is registered, the ALARM button will light. To view the alarm information, press . In the example, the hour of occur- rence is “hh”, the minute of occurrence is “tt”, the month of occurrence is “mm”, the day of occurrence is “dd”, and the name of the alarm is “xxxxxxxxx”.
® Ecosaire CN Series Precision Air Conditioner Owners Manual Operation Alarm History Select Programming Menu by pressing Prg and Esc To select Alarm History, pressing ↓ ↵ to bring up the Alarm History Press ↓ ↓ To view the alarm list, press...
Page 94
® Owners Manual Ecosaire CN Series Precision Air Conditioner View Component Run Times Chilled Water Units Operation ↵ Select User Setup from the Programming Menu by pressing Prg and ↵ ↵ Select Run Hours by pressing The display will return to ROOM STATUS after a short delay.
Page 95
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Controller Diagnostics CHECKS CORRECTIONS • Consult air balancing records. Correct as *** ALARM *** 1. Be sure that the airflow was cor- 00:00 00/00 rectly adjusted at installation. necessary. Change Air Filters •...
Page 96
® Owners Manual Ecosaire EN Series Precision Air Conditioner Controller Diagnostics Operation CHECKS CORRECTIONS *** ALARM *** • If fire or smoke is found, follow proper emergency 00:00 00/00 1. Check for fire or smoke Fire detected procedures. • If necessary, correct operation of fire detector 2.
Page 97
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Controller Diagnostics CORRECTIONS CHECKS *** ALARM *** 00:00 00/00 • Correct as in previous alarm “Change air filters”. 1. Check that there is adequate air Compressor 1 flow. See previous alarm Low pressure “Change air filters”.
Page 98
® Owners Manual Ecosaire EN Series Precision Air Conditioner Controller Diagnostics Operation CHECKS CORRECTIONS • If controller does not agree with known good 1. Check temperature of return air *** ALARM *** with a known good thermometer. thermometer, contact factory for corrective...
Page 99
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Controller Diagnostics CORRECTIONS CHECKS • If controller does not agree with known good 1. Check the temperature of the *** ALARM *** thermometer, contact factory for corrective supply air at the unit.
Page 100
® Owners Manual Ecosaire EN Series Precision Air Conditioner Diagnostics Operation CORRECTIONS CHECKS SYMPTOM • Correct as necessary. 1. Check heaters for operation. In heating mode the room air temperature does • If the heating capacity is not sufficient, contact 2.
Page 101
® Ecosaire EN Series Precision Air Conditioner Owners Manual Operation Diagnostics CORRECTIONS CHECKS SYMPTOM In humidification mode, • If the humidifier capacity is not sufficient, 1. Have a qualified HVAC engineer the room relative humidity contact the factory for solutions.
Page 102
® Owners Manual Ecosaire EN Series Precision Air Conditioner Sensors Diagnostics Operation Humidity is represented by a 0 - 1 VDC signal which is linear with relative humidity. This signal cannot be calibrated in the field. Contact the factory for software solutions.
Page 105
We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the product described.
Page 107
IMPORTANT WARNINGS BEFORE INSTALLING OR HANDLING THE APPLIANCE, PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFETY REGULATIONS CONTAINED IN THIS MANUAL AND INDICATED ON THE LABELS ATTACHED TO THE UNIT. INSTRUCTION SHEET +050003755 OF THE CP* CONTROL BOARD IS AN INTEGRAL PART OF THIS MANUAL! CAREFULLY KEEP INSTRUCTION SHEET +050003755 TOGETHER WITH THIS MANUAL! This humidifier produces non-pressurised steam by means of electrodes immersed in the water contained in the cylinder-boiler...
Page 109
INDEX 1. MODELS AND DESCRIPTION OF THE COMPONENTS ........................3 Description of the components ................................3 2. INSTALLATION: dimensions, weights, hose connections........................... 6 Positioning......................................6 Connecting the hoses.................................... 8 Drain........................................9 Supply ........................................9 Checks........................................9 Installation of the steam hose and condensate return hose ......................... 10 Characteristics of the water ................................
Page 111
1. MODELS AND DESCRIPTION OF THE COMPONENTS The code that identifies the model of humidifier is made up of 10 characters, with the following meaning: Revision level Family prefix Type of power supply Size and steam production Cylinder field Type of cylinder Custom features of conductivity 0=no cylinder...
Page 112
KUE***CC** description For the details of the components see Chap.3 Table 1.1.1 Fig. 1.1.1 A KUE*4 description Load-bearing frame Cylinder Drain pump Supply/drain manifold Supply tank + conductivity meter Fill solenoid valve Table 1.1.1 Fig. 1.1.1 B CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 113
CP1* CP2* CP3* CP4* CP* control boards (also see instruction sheet +050003755 for the boards) Fig. 1.1.1a. External TAM (current transformer) (required only for boards CP1* and CP3*) Fig. 1.2.2 refers to the following table for the description. description fill solenoid valve flow limiter supply hose fill hose...
Page 114
2. INSTALLATION: dimensions, weights, hose connections Positioning • To favour steam distribution, position the appliance so as to minimise the length of the steam outlet pipe (max 4 m). The unit has been designed for wall mounting; the wall must be able to support the weight of the unit during operation. •...
Page 117
Drain models KUE*R* KUE*1* KUE*2* KUE*3* KUE*4* Max. instant drain flow l/min ~ 22.5 Darin water attachment (mm) Min. ID of the drain hose Supply models KUE*R* KUE*1* KUE*2* KUE*3* KUE*4* Max. instant supply flow l/min ¾ ”G ¾ ”G ¾...
Page 118
Installation of the steam hose and condensate return hose The connection between humidifier and distributor must be made using a pipe suitable for this purpose, such as the CAREL hose. Avoid the formation of pockets or traps where the condensate may accumulate.
Page 119
LIMIT VALUES FOR THE SUPPLY WATER WITH MEDIUM-HIGH CONDUCTIVITY IN LIMITS AN IMMERSED ELECTRODE HUMIDIFIER Hydrogen ions Specific conductivity at 20°C σ µS/cm 1250 R, 20°C Total dissolved solids mg/l Dry residue at 180°C mg/l Total hardness mg/l CaCO 100( Temporary hardness mg/l CaCO Iron + Manganese...
Page 120
3. OEM WITH FRAME Introduction This is a special OEM version fitted on a frame, with a pre-wired control board, switch and drain button. Fig. 3.1.1 Italian English Cilindro Cylinder Struttura idraulica Water circuit support structure Conn. elett. carico Fill elect. conn. Scheda Board Carpenteria...
Page 121
Drain Drain assembly made up of a manifold and drain solenoid valve with 90° connector and 32 mm diameter fitting, with the possibility to replace the drain with a straight pipe, supplied. Water circuit Water circuit with supply tank plus conductivity meter and cylinder fill, drain and overflow hoses. Structure Back made from polypropylene reinforced with fibreglass, cylinder secured by convenient strap closing system.
Page 122
4. ELECTRICAL CONNECTIONS (with CAREL controller, model CP) Before making the connections, make sure that the unit is disconnected from the mains power supply. For further information on the controller, refer to the corresponding instruction sheet. Single-phase wiring diagram, EXTERNAL TAM (CP1 *) CAREL code +030221791 - rel.
Page 124
Single-phase wiring diagram, INTERNAL TAM with contactor (CP4 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 125
Single-phase wiring diagram, EXTERNAL TAM with contactor (CP3 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 126
Three-phase wiring diagram, EXTERNAL TAM with contactor (CP3 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 127
Three-phase wiring diagram, INTERNAL TAM with contactor (CP4 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 128
Three-phase wiring diagram, KUE with frame, INTERNAL TAM with contactor (CP4 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 129
Single-phase wiring diagram, KUE with frame, INTERNAL TAM with contactor (CP4 *) CAREL code +030221791 - rel. 2.1 – 21/09/07...
Page 130
Three-phase wiring diagram, EXTERNAL TAM with contactor (CP3 *) Elettrodi immersi Immersed electrodes TAM esterna MAX. 5A External TAM Alimentazione 24 Vac Power Supply 24Vac Drenaggio manuale Relè di allarme Manual drainage Alarm relay Elettrovalvola di scarico RS485 Drain solenoid valve Elettrovalvola di carico Fill solenoid valve Umidostato...
Page 131
5. STARTING, CONTROL AND SHUTDOWN IMPORTANT WARNINGS: 1. Before starting the unit, check that the humidifier is in good condition, that there are no water leaks and that the electrical parts are dry. 2. Do not power the appliance if it is damaged or even partially wet! When installation is completed, flush the supply hose for around 30 minutes by piping the water directly into the drain without sending it into the humidifier.
Page 132
6. MAINTENANCE AND SPARE PARTS Replacing the cylinder IMPORTANT WARNING: the cylinder may be hot. Allow it to cool before touching it or use protective gloves. To access the cylinder: • completely drain the water contained in the cylinder; • turn the appliance off and open the mains power disconnecting switch (safety procedure); •...
Page 133
Maintenance of the other components in the water circuit IMPORTANT WARNINGS: • when cleaning the plastic components do not use detergents or solvents; • scale can removed using a solution of 20% acetic acid and then rinsing with water. The steam humidifier has just one part that requires periodical replacement: the steam production cylinder. This operation is necessary when the lime scale deposits that form inside the cylinder prevent the sufficient passage of current.
Page 134
no description Order code Load-bearing frame Supply/drain manifold 18C499A001 Drain circuit 13C499A034 Drain pump KITPS00000 Fill solenoid valve KITVC00040 Supply tank UEKVASC000 Supply tank cover Tank fill hose Cylinder fill hose UEKT0000XL Overflow pipe Corrugated drain pipe 13C479A001 Table 5.2.1 IMPORTANT WARNING: after having replaced or checked the parts in the water circuit, check that the connections have been carried out correctly and the corresponding seals have been used.
Page 135
Spare parts 6.4.1 SINGLE-PHASE humidifiers: Standard spare parts model KUESR* KUES1* KUES2* KUES3* Water circuit cylinder locking strap 18C499A006 18C499A006 18C499A006 18C499A006 supply tank + conductivity meter 13C119A003 13C119A003 13C119A003 13C119A003 fill solenoid valve kit KITVC00006 KITVC00006 KITVC00006 KITVC00012 drain solenoid valve kit 13C499A030 13C499A030 13C499A030...
Page 136
6.4.4 Spare parts for special applications The following spare parts are supplied separately from the standard humidifier, therefore they must be ordered separately. MODEL KUETR* KUET1* KUET2* KUET3* KUET4* KUET4* KUET4* (25kg/h) (35kg/h) (45kg/h≥400V) Sealed cylinders 200 to 230 VAC 3~, BL0TRA00H1 BL0T1A00H1 BL0T2A00H0...
Page 137
Troubleshooting For the alarms, see instruction sheet +050003755, which is an integral part of this manual. PROBLEM CAUSES SOLUTION 1. no electrical power supply; 1. check the protection device upstream of the humidifier and that the power supply is present; 2.
Page 138
7. OPERATING PRINCIPLE, CONTROL AND OTHER FUNCTIONS Operating principle In an electrode humidifier the production of humidity is obtained inside a cylinder (boiler) containing water that is heated to and then held at boiling temperature. The water that evaporates over time is automatically replaced with water from the mains supply. The heat required to boil the water is produced by passing an electrical current through the cylinder.
Page 139
8. TECHNICAL SPECIFICATIONS MODEL KUETR* KUESR* KUES1* KUET1* KUES2* KUET2* KUES3* KUET3* KUET4* steam flow-rate (kg/h) 1.5 to 3 1.5 to 3 1.5 to 3 1.5 to 3 5 to 8 10 to 15 25 to 45 22/30 connection (dia. mm) outlet pressure limits (Pa) 0 to 500 0 to 500...