  • Page 1 Stationary Battery Analyzer Model No.:CTE-4000 Instruction Manual 1 / 13...
  • Page 2: Chapter 1: Description

    Test Range CTE-4000 has an operating range of 300 - 3000 Siemens. Data Storage CTE-4000 can store 1000 groups of test results, and you can output the test results to your computer with the USB cable. Voltage Range: 1.8 -16.00 Volts DC...
  • Page 3: Chapter 2: Pre-Testing

    Parts of the analyzer CTE-4000 Screen USB Connector Menu Down Chapter 2: Pre-testing Before you test a site with the analyzer, you need to . Determine a reference value. Note: make sure the battery you are testing is 12V batteries.
  • Page 4 Options Lancol recommends that you create your own reference values for a group of batteries to get values specific to the group you are testing. For this reason, the following options are listed in the order you should take to obtain a reference value.
  • Page 5 Using the percentages of the reference value You can use the percentages of the reference value to help you determine the strength of the site. Table 6 lists ranges of reference value percentages, and the action you should take. % of the Reference value Battery condition Action...
  • Page 6: Chapter 3: Testing

    ● Enter into Menu functions 3.2 Tester Startup Tester automatically starts up after the clamps are correctly connected, and displays the Lancol startup interface (Default voltmeter is ON) refer to figure 1. Figure 1, Startup Interface with Voltmeter on At the middle bottom of the startup interface, it displays the voltmeter value, which can be used as DC voltmeter. DC Voltmeter test range is 1.80 - 16DCV, out of which will damage the tester.
  • Page 7 3.3 Testing Press or “HOLD” key of probe to get the quick test results. Note: This quick test does not need to set related parameters in the "MENU" function; if you press the "OK" test directly after power on, the parameters in the MENU will be used as the default value. (Test different batteries;...
  • Page 8 3.4.1 Click "OK" to confirm the parameter settings and enter the following interface: 3.4.2 Continue to press "OK" to set the battery reference value Press the up and down key to adjust the value of the standard values, press "OK" to confirm the standard value input and return to the boot main interface.
  • Page 9 3.4.4 Select alert value settings and press OK to enter: Press " " and "OK" left and right choice, the key to adjust the value, press "OK" to confirm. 3.4.5 Select low voltage setting and press OK to enter: 12V voltage default low voltage reminder for 12.60V, you can press up and down keys to adjust the reminder voltage value.
  • Page 10 3.5.1 Set and view the confirmation parameter is correct, press " " back to boot interface. Press "OK" for battery test, the test result interface is as follows: 3.6 Select View Test Results and press " OK" Press the up and down key to select the time and serial number you want to view, press "OK" to go to view the test results.
  • Page 11 3.7 Select Output test results press "OK" to confirm Select the "output test data" Press "OK" button, the product packaging box to connect the data cable computer and tester data export interface, and install data export software, its installation steps are as follows: Please download the software and installation instructions: https://boxpro.cn/boxpro/p/T19WYZ8MS...
  • Page 12 The up and down keys select to delete "last set of data" or "all data" and press "OK" to confirm. Note: Select "all Data deletion" will delete all tested data, save data zero. 4.Product Specifications Model:CTE-4000 Suitable deep cycle batteries:12V Conductance range: 30-3000 S (Siemens) Conductance accuracy: ±3%...
  • Page 13: Warranty

    When the equipment needs to be repaired, please confirm the product problem in advance and then send it to Lancol Company with a description of the problem. If the equipment is within the scope of warranty, Lancol will repair it for free; if the equipment is out of warranty, Langer will charge repairs and add return freight.