Page 1
P r o c e s s C o n t r o l b y D e s i g n In stru men t Trai n in g Gu id e N920 Series Fl or i te I nte rna tional , I nc.
Page 2
Installation Instruction Connect input or output into in- strument port as shown Insert power plug into PWR jack as shown Plug the D9 part of the RS-232 connector into a computer serial port. Insert the plug on the other end of the cable into he PGM jack as shown When you unit is installed with the WAN modem option then...
Page 3
Quick Programming Instructions Press the CHAN button until reaching Input Port 1 (note: a 1 will be lo- cated in the upper right hand corner of the display). Pulse Output Sensors Press the PROG button until reaching the Pulse Constant screen followed by setting the number to correspond to the sensors number of pulses per quantity.
Page 7
900 Series Instrument Navigation & Structure D10140—021709...
Page 9
900 Series Instrument Programming Navigation D10140—021709...
Page 12
Network Address - System Program Function This screen is used to program the base address for serial communication programming and information reporting. Navigation Access this screen by pressing the CHAN key until reaching the "Sys" port - and then pressing the PROG key until reaching the desired screen.
Page 13
Report Start - System Program Function This screen is used to program the date and time that scheduled value reports for each input port having Comm Port appropriately set are to then be sent. It is comprised of a date field and a 24 hour clock time field.
Page 14
Reporting Frequency - System Program Function This screen is used to program the rate at which measurement information is send for each input port having its Comm Port set. It is comprised of a three character numeric field and a time field. Navigation Access this screen by pressing the CHAN key until reaching the "Sys"...
Page 15
Alarm and Report Phone Numbers - System Program Function These screens are used to program the phone numbers to remotely access computers and data collection equipment to report either one or more alarm conditions, or to send scheduled measurement information from input ports having their Comm Port appropriately set. Should an alarm condition occur without the alarm number programmed - the alarm will be sent to the report phone number to insure alarm information is reported.
Page 16
Answer Rings - System Program Function This screen is used to program the number of public switched telephone system rings after which the ringing line is answered by the instrument. The line will not be answered if set to zero. This function is often used for maintenance, diagnostic, and general remote access purposes.
Page 17
Log Records - System View Function This screen is used to view the number of data records that have been logged. This screen is also used to completely control the logging functions including start, stop, upload and zero records. Navigation Access this screen by pressing the CHAN key until reaching the "Sys"...
Page 18
Network Address - System View Function This screen is used to view the instruments programmed communication base address. Navigation Access this screen by pressing the CHAN key until reaching the "Sys" port - and then pressing the VIEW key until reaching the desired screen. Note the first character field blinks indicating readiness for programming.
Page 19
Date-Time - System View Function This screen is used to view the real time clocks date and time having a 24 hour clock time field. Navigation Access this screen by pressing the CHAN key until reaching the "Sys" port - and then pressing the VIEW key until reaching the desired screen.
Page 20
Next Report Date-Time - System View Function This screen is used to view the date and time that a next regularity scheduled value report is to be sent. Navigation Access this screen by pressing the CHAN key until reaching the "Sys" port - and then pressing the VIEW key until reaching the desired screen.
Page 21
Log Frequency - System Program Function This screen is used to program the rate at which measurement information is placed as records into the logging memory. It is comprised of a three character numeric field and a time field. Navigation Access this screen by pressing the CHAN key until reaching the "Sys"...
Page 23
Port Type - Input Program Function This screen is used to program an input (or output) port for the installed port module. The input Port Type may be programmed to service the selected input signal Type and Execution. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 24
Time Base - Input Program Function This screen is used to program the time base used for input signal rate and quantity measurements. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 25
Decimal Point - Input Program Function This screen is used to program the number of measurement value digits to the right of the decimal point. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 26
Measure Units - Input Program Function This screen is used to program a three character field defining units of measure representing the physical engineering measurement. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 27
Scale Factor - Input Program Function This screen is used to program a factor by which a measured input rate is multiplied to change its magnitude. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 28
Pulse Constant - Input Program Function This screen is used to program the factor by which measured pulse inputs are converted to an engineering value in the measure units indicated. This screen only available with "In Freq" input Port Type selected. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 29
Input Interpolation - Input Program Function The purpose of these screens in combination provides for linear interpolation of measured analog input values to be represented as a physical measurement meaning in engineering units. Navigation Access these screens by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 30
Rate Filter - Input Program Function This screen is used to program the factor which determines the amount of filtering to be applied to the rate measurement. The filtering range is from +0 to -20 dbHz representing the magnitude of noise and jitter suppression.
Page 31
Low Rate Limit Function This screen is used to program the rate value below which an alarm is detected. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen. Note the first numeric field blinks indicating readiness for programming.
Page 32
Hi Rate Limit - Input Program Function This screen is used to program the rate value above which an alarm is detected. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 33
Rate Limit Delay - Input Program Function This screen is used to program the time period over which a rate alarm must have been detected and continuously persisted prior to the alarm condition is declared to be a qualified alarm. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 34
Qty 1 Lim - Input Program Function This screen is used to program the quantity amount above which a quantity 1 alarm condition is declared. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 35
Qty 2 Lim - Input Program Function This screen is used to program the quantity amount above which a quantity 2 alarm condition is declared. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 36
Time Limit - Input Program Function This screen is used to program the service time amount above which a service time alarm condition is declared. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 37
Communication Port - Input Program Function This screen is used to program which of the available communication ports from which to send report information when the reporting capability is enabled. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 38
Log Type Function This screen is used to program the measured rate or accumulated quantity for an input port what is to be placed in a date-time stamped log record. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 39
900 Series Instrument Viewing Navigation D10140—021709...
Page 40
Quantity 1 - Input View Function This screen is used to independently view and zero the accumulated port quantity 1 when the port time base is set for seconds, minutes, hours or days. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the VIEW key until reaching this screen.
Page 41
Quantity 2 - Input View Function This screen is used to independently view and zero the accumulated port quantity 2 when the port time base is set for seconds, minutes, hours or days. The output port link number and arrow are displayed blinking when the linked output is performing a control function that requires using quantity 2 to perform the control process.
Page 42
Rate/Value - Input View Function This screen is used to view the present process rate when the port time base is set for seconds, minutes, hours or days, or scalar value when the time base is set for scalar. The output port link number and arrow are displayed blinking when the linked output is performing a control function that requires using the measured rate to perform the control process.
Page 43
Process Offset - Input View Function This screen is used to view the present process rate-value offset or tare value. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the VIEW key until reaching this screen. Zero Process Offset Press the ZERO key while viewing this screen to cause the present offset value to be zero.
Page 44
Process Input - Input View Function This screen is used to view input signal measurement values for install diagnostic purposes, and is also used to perform zero and full-scale calibrations for the port. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the VIEW key until reaching this screen.
Page 45
Service Time - Input View Function This screen is used to view the present accumulated input port service time. This value is often used for such purposes as maintenance scheduling as a Hobbs Hour-Meter would be used. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the VIEW key until reaching this screen.
Page 47
Port Type - Output Program Function This screen is used to program an output (or input) port for the installed port module. The output Port Type may be programmed to service the selected output signal Type and Link. Navigation Access this screen by using the CHAN key until reaching the desired port number, and then by using the PROG key until reaching this screen.
Page 48
Control Type - Output Program Function This screen is used to program a desired output control function. A linked input port programmed in the outputs Port Type provides process measurement information required for the output port to perform its selected function. Navigation Access this screen by using the CHAN key until reaching the desired output port number, and then by using the PROG key until reaching this screen.
Page 49
Control Amount - Output Program Function This screen is used to program a desired output value or rate used by the output port to accomplish the requirements of its selected Control Type. The Control Amount units and time base are the same as the input port, which had been programmed as the input link in this outputs Port Type.
Page 50
PID Response - Output Program Function This screen is used to program the factor which determines the bandwidth - time response - applied to the PID output. The response range is from +0 to -20 dbHz which represents the response magnitude.
Page 51
Output Interpolation - Output Program Function The purpose of these screens in combination provides for linear interpolation of a physical measurement in engineering units to be represented by an analog output signal type. The programmed High/Low Values additionally serve respectively as the highest or lowest analog output values that are allowed to be output.
Page 52
Control Type - Output View Function This screen is used to view the present Control Type. Navigation Access this screen by using the CHAN key until reaching the desired output port number, and then by using the VIEW key until reaching this screen. Control Types Monitor o Analog output Port Type - converts and outputs its linked input port measurement as an...
Page 53
Process Output - Output View Function This screen is used to view the output signal value for install diagnostic purposes. Navigation Access this screen by using the CHAN key until reaching the desired output port number, and then by using the VIEW key until reaching this screen. Diagnostic The screen value indicates the value presently being output from the port.
Page 54
900 Series Instrument Optional Configuration D10140—021709...