Download Print this page

CENTRAL Omega C-1A Manual

Orifice adjustable pendent automatic sprinkler

Advertisement

Quick Links

Omega C-1A
Quick Response Commercial
Automatic Sprinkler
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Omega Model C-1A Quick
Response Commercial Pendent
Automatic Sprinkler is a low profile,
aesthetically pleasing, ceiling mounted
sprinkler that offers a high degree of
protection for human life. It operates
five to six times faster than a standard
sprinkler and features a spray pattern
that has been shown to be effective in
the control or extinguishment of fire.
The Model C-1A incorporates a
significant cost saving feature; a
special escutcheon assembly that pro-
vides for
7
/
"
of field adjust-
(22.2 mm)
8
ment resulting in an easily accom-
plished, tight fit against the ceiling.
The Model C-1A carries a Listing*
by Underwriters Laboratories for use
as a Quick Response Commercial
Sprinkler that qualifies for installation
in accordance with current NFPA 13
and NFPA 13R Standards.
The Model C-1A is available in three
standard finishes. Its mating escutch-
eon plate is available in three stan-
dard finishes with additional special
finishes available.
Operation: A fusible alloy pellet is
compressed by a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat collect-
ing fins and conducted to the alloy
pellet. At the rated temperature, the
*For specific listing requirements, see the appropriate
information contained in this brochure.
alloy melts, causing the ball plunger to
drop, freeing balls from the retaining
groove. This movement allows
system water pressure to force the
orifice sealing mechanism and deflec-
tor assembly open. Water is then
discharged in a designed flow pattern.
Technical
Data
Model: C-1A
Style:
Pendent (adjustable)
Escutcheon:
Wrench: Omega Adjustable Model A
Sprinkler Wrench
3
Orifice Size:
/
"
or
(9.5 mm)
8
3
K-Factor:
/
" = 2.7
(38.6 Metric)
8
1
/
" = 5.6
(80.1 Metric)
2
Thread Size:
1
/
"
N.P.T.
(15 mm)
2
Temperature Rating: 145°F/63°C
160°F/71°C
200°F/93°C
3
Approvals:
/
"
- U.L. only
(10 mm)
8
1
/
"
- U.L., ULC,
(15 mm)
2
MEA (46-92-E Vol. III)
Maximum Working Pressure:
175 psi / 12.1 bar
Factory Hydro Test: 100% at
500 psi / 34.5 bar
Standard Finishes:
Sprinkler: chrome plated, brass
plated, white painted
Escutcheon: chrome plated, brass
plated, white painted
Adjustable Range Below Ceiling:
3
/
"
to 1
1
/
"
(9.5 mm)
8
4
C-1A
3
/
"
8
(9.5 mm) & (12.7 mm)
Orifice
Adjustable
Pendent
Automatic
Sprinkler
Highest Allowable Ambient Temp:.
1
/
"
100°F/38°C for 145°F rating
(12.7 mm)
2
100°F/38°C for 160°F rating
150°F/66°C for 200°F rating
Length: 2
7
Width:
1
1
Weight: 3.2 oz.
(31.8 mm)
1-98
1
/
"
&
2
/
"
(61.9 mm)
16
/
"
(31.8 mm)
4
(91 grams)
No.1-10.0

Advertisement

loading

Summary of Contents for CENTRAL Omega C-1A

  • Page 1 C-1A 1-98 Omega C-1A Quick Response Commercial Automatic Sprinkler Manufactured by: Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 alloy melts, causing the ball plunger to " " Product & drop, freeing balls from the retaining groove. This movement allows...
  • Page 2 Installation Diagram Omega C-1A Commercial Quick Response Pipe Drop 1" x 1/2" (25 mm x 15 mm) 2" (50.8 mm) NPT Reducing Coupling Dia. Max. 1 3/4" (44.5 mm) Dia. Min. Note: Use this flange for field installation. DO NOT HOLD by deflector.
  • Page 3 Design Requirements — Quick Response Commercial Applications associated fittings have been wire In Quick Response Commercial applications, the Omega C-1A sprinklers are brushed to remove any flux. Residual intended for standard area coverages and standard flow and pressure require- flux can cause corrosion and in ments as specified in current NFPA 13 and NFPA 13R Standards.
  • Page 4 U.S. and Canada, and interna- to secure permission from all Authori- ties Having Jurisdiction , and notify all tionally, through a network of Central Sprinkler distribution centers. You personnel who may be affected during may write directly to Central Sprinkler system shutdown.