Summary of Contents for EasyDrive Electric GT200-4T0007G
Page 1
Preface Thank you for using high performance general vector control inverter manufactured by Shenzhen EasyDrive Electric Co., Ltd. This series inverter is a general-purpose frequency converter based on flux vector algorithm control. It has a series of practical functions such as motor parameter...
Page 2
GT200 series general purpose inverter instruction manual Danger The frequency converter must be earthed reliably, If not, there is a potential risk of personal injury in the unit. Intended Readers The User Manual is intended for the following people to read: Inverter installation personnel, engineers and technicians (electrical engineers and electrical operators), and designers, etc.
GT200 series general purpose inverter instruction manual 1.2 Specifications Table 1-3 Product technical specifications Item Description Rated voltage/ three-phase,380V-440Vac;50Hz/60Hz Frequency Input Voltage:380v(-15%)~440v ( +10%) ;Voltage unbalance Allowed voltage range rate:﹤3%;Frequency:±5% Rated voltage(V) 380Vac~440Vac Frequency 0Hz~550Hz Output G type:150% rated current for 60s ;P type:120% rated Overload capacity current for 60s Control mode...
Page 6
GT200 series general purpose inverter instruction manual Item Description According to load condition, V/F curve can be Auto energy-saving optimized automatically to get the aim of energy-saving running running. Auto voltage when rhe voltage of network changes,the output voltage adjustment can be automatically kept constant Auto current During the operation, the current is automatically...
Page 7
GT200 series general purpose inverter instruction manual Item Description Indoor,not suffer from sun,dust,corrosive gas,oil Service location fog,steam and so on Altitude Less than 1000m (derating at higher than 1000m) Environment -10°C~+40°C (Derating use in 40°C~50°C) temperature Environment Humidity Less than 90%RH,no condensation Vibration Less than 5.9m/s2 Storage temperature -40℃~+60℃...
Page 10
GT200 series general purpose inverter instruction manual Mounting Model Refer Holes(Φ) GT200-4T2000G/ 4T2200P (Wall-mounting) 1158 1127 GT200-4T2200G/ 4T2500P (Wall-mounting) GT200-4T2500G/ 4T2800P (Wall-mounting) 1388 1357 GT200-4T2800G/ 4T3150P (Wall-mounting) Note: 1.Optional base for GT200-4T0300G/4T0370P~GT200-4T1850G/4T1600. 2.Need to match wall-mounted stand for wall-mounted design of GT200-4T2200G/4T2500P~GT200-4T2800G/4T3150P.
Page 11
GT200 series general purpose inverter instruction manual 1.5 Keyboard Size REV/FWD QUICK STOP RESET Hole size Diagram 1-1 Keyboard Size 1.6 Breaking Resistor Energy-consumption braking resistor is provided as shown in table 1-5,1-6 and the installation of braking resistor wire is provided as shown in 1-2. Inverter BRAKINGRESISTOR Diagram 1-2 Connection between inverter and braking unit...
Page 12
Utilization rate FC.01 is 10%) Table 1-5 Select table of braking resistor (380V) Applicable Resistor Resistor Power Model No. motor Power Resistance (Ω) (KW) ≥500 GT200-4T0007G/- 0.75 ≥300 GT200-4T0015G/- ≥200 GT200-4T0022G/- ≥200 GT200-4T0040G/4T0055P ≥80 GT200-4T0055G/4T0075P ≥50...
GT200 series general purpose inverter instruction manual Chapter2 Installation and Wiring of Inverter 2.1 Installation environment of inverter 2.1.1 Installation environment condition (1) The inverter shall be installed indoors of perfect ventilation,and the environment temperature shall be in the range of -10℃~40℃, in case that the temperature exceeds 40℃,the external air-blast cooling or derating shall be used.
Page 14
GT200 series general purpose inverter instruction manual Diagram2-1 Installation space condition Installation space(mm) Inverter type ≥50 ≥100 GT200-4T0007G~GT200-4T0370G/4T0450P ≥50 ≥200 GT200-4T0450G/4T0550P~GT200-4T2800G/4T3150P 2.1.3 Inverter Installation Method and Steps GT200 series according to different power levels, there are two kinds of plastic and sheet metal structure;Depending on the different installation application, GT210 series has two...
Page 15
GT200 series general purpose inverter instruction manual Control cabinet installation plate Diagram2-5 Plastic structure embedded mounting 3、Sheet metal structure wall-mounted installation Control cabinet Installation plate Hole for hoist Fixed the four screws Diagram2-6 Sheet metal structure wall-mounted installation...
Page 16
GT200 series general purpose inverter instruction manual Hole for hoist Diagram2-7 Hoisting diagram of sheet metal structure 4、Sheet metal structure embedded mounting Embedded mounting bracket Embedded mounting bracket Diagram2-8 Sheet metal structure install schematic external bracket diagram Control cabinet Installation plate Fixed the four screws Diagram2-9 Sheet metal structure embedded mounting diagram...
Page 17
GT200 series general purpose inverter instruction manual 2.2 Disassembling and installation of inverter panel 2.2.1 Cover plate disassembly and installation of plastic enclosure inverter Disassemble Cover Plate Shown as diagram2-10,push out the hooks on the left and right sides of the cover from inside at 1 direction with tools, then lift the panel from direction 2 ...
Page 18
GT200 series general purpose inverter instruction manual Diagram2-12 Disassembly of cover Diagram2-13 Installation of cover 2.2.3 .Operation panel disassembly and installation Disassemble Cover Plate Pls refer to the diagram 2-10 to 2-13 Disassemble operation panel According to the diagram2-14,Press down on the groove 1 on both sides of the operation panel with your fingers,and then take out the operation panel body along the direction 2 ...
Page 19
U、V、W Braking resistor GT200-2S0007G (+)、BR connection GT200-2S0015G Motor grounding GT200-2S0022G Dc positive and negative bus (+)、(-) output,external braking unit GT200-4T0007G/- R、S、T 3-phase Ac 380v input GT200-4T0015G/- GT200-4T0022G/- U、V、W 3-phase Ac output GT200-4T0040G/ Braking resistor (+)、BR 4T0055P connection GT200-4T0055G/ Motor grounding...
Page 20
GT200 series general purpose inverter instruction manual Terminal Application model Terminal of main circuit Function description name R、S、T 3-phase Ac 380v input 3-phase Ac output U、V、W Braking resistor (+)、BR connection GT200-4T0185G/ 4T0220P Dc positive and negative bus GT200-4T0220G/ (+)、(-) output,external braking 4T0300P unit Motor grounding...
Page 21
GT200 series general purpose inverter instruction manual Terminal Application model Terminal of main circuit Function description name R、S、T 3-phase Ac 380v input GT200-4T0750G/ U、V、W 3-phase Ac 380v input 4T0900P GT200-4T0900G/ External connect DC P、(+) 4T1100P reactor GT200-4T1100G/ Dc positive and 4T1320P (+)、(-) negative bus...
Page 22
(2)Table2-3 The selection of main circuit cable diameter, protection circuit breaker QF or fuse as following Input/output Circuit breaker Fuse Control wire wire Model (mm ) (mm ) (A) (A) GT200-4T0007G GT200-2S0007G GT200-4T0015G GT200-2S0015G GT200-4T0022G GT200-2S0022G GT200-4T0040G GT200-4T0055G/4T0075P 25/40 25/32 GT200-4T0075G/4T0110P 40/63 32/38 6/10...
Page 23
GT200 series general purpose inverter instruction manual 2.4 Control circuit configuration and wiring 2.4.1 Layout of control circuit terminal as follows: +10V 485+ 485- +24V Diagram2-17 Diagram of control panel terminals arrangement 2.4.2 CN3 function description,shown as table 2-4 Terminal Terminal function Type Name...
Page 24
GT200 series general purpose inverter instruction manual Normal:RA-RB normally closed;RA-RC normally Rating of contact Programmable open; NO:5A 250VAC relay output Action:RA-RB normally NC:3A 250VAC terminal open;RA-RC normally Remark: By extend card closed (Detail refer to F6.34) Input voltage range:0~ Accept the input of analog Analog input 10V (input impedance:...
Page 25
GT200 series general purpose inverter instruction manual ) F6.00-6.04) Multi-function input terminal 5 Multi-function Programmable input terminal 1 multi-function switch Multi-function output terminals is referred input terminal 2 to introduction about input terminal function(Switch Multi-function ) input and output) on (Remark: By extend card input terminal 3 Chapter 6 terminals...
Page 26
GT200 series general purpose inverter instruction manual 0~10Vor 0~20mA Inverter input Select 0~20mA Select 0~10V ( ) Cable clip of case Grounding of shielded wire near terminal Diagram2-18 Wiring for analog input terminal 2.4.4 Inverter control circuit wiring Breaking resistor Breaker Contactor (+)...
Page 27
GT200 series general purpose inverter instruction manual Reactor ReactorBreaking resistor Breaker Contactor Motor (+) (-) GT200 Multi-function terminal 1 Multi-function terminal 2 Analog reference ground Multi-function terminal 3 Analog output 1 Multi-function terminal 4 Analog output 2 Multi-function terminal 5 Open collector output Multi-function terminal 6 Open collector output...
Page 28
GT200 series general purpose inverter instruction manual 2.4.5 Signal input terminal wiring Description for NPN and PNP model switch terminal ,shown as diagram 2-21 to diagram 2-24 DI10 +24V Internal Circuit The terminals of DI6-DI10 on the extend card Diagram2-21 Internal power supply NPN figure(OC) DI10 +24V External Circuit...
Page 29
GT200 series general purpose inverter instruction manual DI10 +24V Internal Circuit The terminals of DI6-DI10 on the extend card Diagram2-23Internal power supply PNP figure (OE) DI10 +24V External Circuit The terminals of DI6-DI10 on the extend card Diagram2-24 External power supply PNP figure(OE)
GT200 series general purpose inverter instruction manual Chapter 3 Frequency Inverter’s operation and instruction 3.1button function description The frequency converter operation panel is provided with 8 keys, each function definition of the key is shown in table3-1. Table 3-1 operation panel function table Keys Name Icon...
Page 31
GT200 series general purpose inverter instruction manual Project Function Explanation Display the current running state parameters and setting parameters. Digital Note: when the parameter exceeds four digits, only the first four digits display are displayed. Current digital display parameters corresponding to the physical Hz、...
GT200 series general purpose inverter instruction manual Chapter 4 Function Parameters 4.1 Symbol Description: ×—means that the parameter cannot be modified during the operation process ○—means that the parameter can be modified during the operation process ●—shows actually detected parameter which cannot be modified —shows manufacturer retention parameter which is forbidden to modify Parameter Parameter...
Page 33
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition LED units digit:first parameter display selection 0:Output frequency ( before compensation) 1: Output torque 2: Setting frequency frequency ( after 3:Output compensation) 4: Bus voltage 5: AI1 6: AI2...
Page 34
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition 0:Digital given 1, operation panel ▲ ▼ regulating 1:Digital given 2, terminal UP/DN regulating Frequency given ○ F1.02 2:Digital given 3, serial port channel selection given 3:AI1 given...
Page 35
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition 0:User setting V/F curve (confirmed by F1.18~F1.23 function code) 1:Reduced torque characteristic F1.17 V/F curve setting curve 1(2.0 hypo-power) × 2:Reduced torque characteristic curve 2(1.7 hypo-power) 3:Reduced torque characteristic curve 3(1.2 hypo-power)
Page 36
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition ○ F2.01 Start frequency 0.20~60.00Hz 0.01Hz 0.50Hz Start frequency ○ F2.02 0.0~10.0s 0.1s 0.0s retention time Start DC braking 0.0~100.0% frequency inverter ○...
Page 37
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition Deceleration time ○ F2.19 Jog operation ○ F2.20 0.10~50.00Hz 0.01Hz 5.00Hz frequency ○ F2.21 Jog interval time 0.0~100.0s 0.1s 0.0s Jog acceleration ○...
Page 38
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition F3.05 Rated voltage 1~480V × No-loading F3.06 0.1~999.9A 0.1mH × current I0 Stator resistance 0.000~50.000Ω 0.001Ω ○ F3.07 leakage inductive ○ F3.08 0.0~999.9mH 0.1mH reactanceX...
Page 39
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition Current loop F4.12 0.01~10.00 0.01 0.20 proportional gain Current loop F4.13 0.01~10.00 0.01 0.20 integral time Analog quantity terminal parameter F5 group LED units digit:...
Page 40
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition Curve 1 maximum given ○ F5.07 0.00~F1.06 50.00Hz corresponding frequency 0.0%~F5.10 (Specific value between Curve 2 ○ F5.08 minimum given value 2 and 0.1% 0.1% minimum given...
Page 41
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition 5: Acceleration and deceleration time terminal 2 Multifunction 6:External fault normally open input terminal input F6.01 7:External fault normally close Function input selection 8:External reset (STOP/RESET) input...
Page 42
GT200 series general purpose inverter instruction manual Parameter Parameter Mini Default Setting range code name munit value ition modes, stop according to the current stop mode) Multifunction 36:FWD terminal function input terminal 37:REV terminal function F6.06 38: Frequency inverter running Function prohibited selection...
Page 43
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit 0: Inverter running indication (RUN) 1:Frequency arrival signal (FAR) 2:Frequency level detection signal (FDT1) 3:Frequency level detection signal (FDT2) Bothway open 4:Overload detection signal (OL) collector F6.11 ×...
Page 44
GT200 series general purpose inverter instruction manual Parameter Parametr Mini Default Setting range code valu ition name munit 22:Setting frequency (0~ maximum) 23:Output current(0~2*Iei) 24:Output current(0~2*Iem) 25:Output torque(0~2*Tem) Relay output 26:Output voltage(0~1.2*Ve) function 27:Busbar voltage(0~800V) F6.13 × selection(TA/ 28:AI1(0~10V) TB/TC) 29:AI2(0~10V/0~20mA)...
Page 45
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Binary system setting 0:Breakover effective 1:Disconnect effective LED units digit: BIT0~BIT3:DI1~DI4 Terminal ○ LED tens digit: F6.23 positive and 0000 negative logic BIT0~BIT3:DI5~DI8 LED hundreds digit:...
Page 46
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit LED digit:AO1 output type selection 0:Voltage Analog output 1:Current ○ F6.29 voltage current LED ten digit:Expansion card AO2 type selection output type selection 0:Voltage 1:Current Common IO...
Page 47
GT200 series general purpose inverter instruction manual 0:Constant speed ineffective Over current 1:Constant speed effective F7.07 stall action × Note:Acceleration and deceleration selection is always effective Over current F7.08 0~100 × stall gain Kp Over current F7.09 stall integral 1~1000 ×...
Page 48
GT200 series general purpose inverter instruction manual 0:AI1; 1:AI2; 2:AI1+AI2; 3:AI1-AI2; Feedback 4:MIN(AI1,AI2); ○ F8.02 channel 5:MAX(AI1,AI2); selection 6:Pulse:(PG closed loop single\double is confirmed by terminal) 7:AI3(Expansion card) ; Given channel ○ F8.03 0.001~50.000s 0.001s 0.500s smoothing Feedback ○ F8.04 channel 0.001~50.000s 0.001s...
Page 49
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit 0.0~20.0% Deviation ○ (Corresponding closed loop given F8.15 0.1% 2.0% extremity value) 0:Direct action Closed loop 1:Reaction F8.16 regulating × Note:Relation between given speed characteristic and rotate speed Sleeping...
Page 50
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Multistage ○ F8.29 closed loop 0.00~10.00V 0.01V 0.00V given 10 Multistage ○ F8.30 closed loop 0.00~10.00V 0.01V 0.00V given 11 Multistage ○ F8.31 closed loop 0.00~10.00V...
Page 51
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Wakeing ○ F8.40 0.00V~10.00V 0.01V 0.00V threshold ○ F8.41 Sleeping time 0.1s~600.0s 0.1s 300.0s ○ F8.42 Waking time 0.1s~600.0s 0.1s 300.0s Limits acceleration 2.0%~100.0%(Relative to maximum ○...
Page 52
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Multistage F1.10(lower limit frequency)~ ○ F9.05 0.01Hz 40.00Hz frequency 5 F1.09(upper limit frequency) Multistage F1.10(lower limit frequency)~ ○ F9.06 0.01Hz 45.00Hz frequency 6 F1.09(upper limit frequency) Multistage F1.10(lower limit frequency)~...
Page 53
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 2(F9.02) 1:Determined by F1.02 function code 2: Multistage closed loop given 2(F8.21) 3:Determined by F8.01 function code LED tens digit: 0:Foreward ○ F9.10 Stage 2 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 54
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 3(F9.03) 1:Determined by F1.02 function code 2: Multistage closed loop given 3(F8.22) 3:Determined by F8.01 function code LED tens digit: 0:Foreward ○ F9.12 Stage 3 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 55
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 4(F9.04) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.23) 3:Determined by F8.01 function code LED tens digit: 0:Foreward ○ F9.14 Stage 4 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 56
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 4(F9.04) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.23) 3:Determined by F8.01 function code LED tens digit: 0:Foreward ○ 9.16 Stage 5 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 57
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Stage 6 ○ F9.19 0.0~5500 20.0 running time LED units digit: 0:Multistage frequency 4(F9.04) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.23) 3:Determined by F8.01 function code...
Page 58
GT200 series general purpose inverter instruction manual ○ F1.10(Lowest 0.01Hz 50.00Hz Multistage F9.28 frequency)~F1.09(Highest frequency14 frequency) ○ F1.10(Lowest 0.01Hz 50.00Hz Multistage F9.29 frequency)~F1.09(Highest frequency15 frequency) LED units digit: 0:Multistage frequency 4(F9.23) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.27) 3:Determined by F8.01 function code...
Page 59
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 4(F9.24) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.28) 3:Determined by F8.01 function code LED tens digit: 0:Foreward ○ F9.32 Stage 9setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 60
GT200 series general purpose inverter instruction manual Stage 10 ○ F9.35 0.0~6500.0s running time LED units digit: 0:Multistage frequency 4(F9.26) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.30) 3:Determined by F8.01 function code LED tens digit: 0:Foreward Stage 11 ○...
Page 61
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 4(F9.26) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.31) 3:Determined by F8.01 function code LED tens digit: 0:Foreward Stage 12 ○ F9.38 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 62
GT200 series general purpose inverter instruction manual Stage 13 ○ F9.41 0.0~5500 running time LED units digit: 0:Multistage frequency 4(F9.28) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.33) 3:Determined by F8.01 function code LED tens digit: 0:Foreward Stage 14 ○...
Page 63
GT200 series general purpose inverter instruction manual LED units digit: 0:Multistage frequency 4(F9.29) 1:Determined by F1.02 function code 2: Multistage closed loop given 4(F8.34) 3:Determined by F8.01 function code LED tens digit: 0:Foreward Stage 15 ○ F9.44 setting 1:Reversal 2: Determined by run command LED hundreds digit:...
Page 64
GT200 series general purpose inverter instruction manual 0~10,0 shows no automatic reset function Automatic FA.09 Note: Module protection and × reset times external device fault has no reset function. Automatic FA.10 reset interval 2.0~20.0s 0.1s 5.0s × time LED units digit:Action selection 0:Detecting all the time 1:...
Page 65
GT200 series general purpose inverter instruction manual LED units digit:Undervoltage fault indication action selection 0:No action 1:Action (regard undervoltage as fault) LED tens digit:Automatic reset interval fault indication action selection 0:No action 1:Action LED hundreds digit:Fault lock Protective function selection FA.14 action selection 0000...
Page 66
GT200 series general purpose inverter instruction manual LED units digit:communication abnormal action selection 0:Alarming and free halt 1:No alarming and continue to 2:No alarming and stop according to stop mode(Only in serial port control mode) 3:No alarming and stop according to stop mode(In all Protective control modes) FA.15...
Page 67
GT200 series general purpose inverter instruction manual LED units digit:Baud rate selection 0:1200BPS 1:2400BPS 2:4800BPS 3:9600BPS 4:19200BPS 5:38400BPS LED tens digit:data format 0:1-8-2-N format, RTU 1:1-8-1-E format, RTU Communicatio Fb.01 0003 × 2:1-8-1-O format, RTU n configuration 3:1-7-2-N format, ASCII 4:1-7-1-E format, ASCII 5:1-7-1-O format, ASCII 6:1-8-1-N format,RTU...
Page 68
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit Automatic 0:No action ○ FC.03 energy saving 1:Action running Slip 0:No enabled ○ FC.04 compensation 1:Enabled enabled Slip ○ FC.05 compensation 0.1~20.0ms 0.1ms 1.0ms filtering time...
Page 69
GT200 series general purpose inverter instruction manual Parametr Parameter Mini Default Setting range code valu ition name munit 0.000~65.535(km) (power down 0.001 0.000 ○ FC.15 Actual length storage) (km) (km) Length ○ FC.16 multiplying 0.001~30.000 0.001 1.000 power Length ○ FC.17 correction 0.001~1.000...
Page 70
GT200 series general purpose inverter instruction manual LED units digit: Frequency channel selection when keyboard is started or stopped 0:No binding 1:Keyboard ▲ ▼ given 2:Terminal UP/DN given 3:Serial port given 4:AI1 analog given 5:AI2 analog given 6:Terminal pulse given 7:Reserved 8:Expansion card AI3 analog given...
Page 71
GT200 series general purpose inverter instruction manual 0:No action; 1:Keyboard ▲ ▼ given (given by FC.27 directly); 2:Terminal UP/DN given (given by FC.27 directly); 3:Serial port given (given by FC.27 directly); 4:AI1; 5:AI2; 6:PULSE; Auxiliary given 7:-AI1; ○ FC.25 channel 8:-AI2;...
Page 72
GT200 series general purpose inverter instruction manual LED units digit: STOP/RESET key function selection 0:Ineffective in non-panel control mode 1:Stop according to stop mode in non-panel mode 2:E015 free halt in non-panel mode LED tens digit:M-FUNC key function selection Operation 0:Ineffective panel key 1:Effective in halt status...
Page 73
GT200 series general purpose inverter instruction manual Digit:Frequency source selection 0:The main frequency source 1:Primary and secondary operation results (the results are determined by the tens digit) 2:The main frequency source switching with the auxiliary frequency source 3:The main frequency source switching with Primary and secondary operation results Frequency...
Page 74
GT200 series general purpose inverter instruction manual Fan start-stop ○ Fd.09 temperature 0~100℃ threshold Monitoring parameter U0 group Output frequency U0.00 (before compensation) U0.01 Output torque Setting U0.02 frequency Output frequency U0.03 (after compensation) U0.04 Bus voltage U0.05 U0.06 Analog closed U0.07 loop feedback Analog closed...
Page 75
GT200 series general purpose inverter instruction manual External count U0.16 value U0.17 Terminal status U0.18 Actual length U0.19 Setting length U0.20 Reserved Inverter rated U0.21 capacity Inverter rated U0.22 voltage Inverter rated U0.23 current U0.24 Reserved IGBT U0.25 temperature First failure U0.26 type Second failure...
Page 76
GT200 series general purpose inverter instruction manual Bus voltage 0~999V U0.33 during second failure Output current 0.00~99.99A 0.01A 0.00A U0.34 during second failure Output frequency 0.00Hz~550.00Hz 0.01Hz 0.00Hz U0.35 during second failure IGBT temperature U0.36 0.0~100.0℃ 0℃ during second failure Accumulated U0.37 running time...
Page 77
GT200 series general purpose inverter instruction manual The fault code table Fault code Fault type Fault code Fault type Frequency inverter Accelerating E001 E016 485 communication fault running of the current Frequency inverter decelerating Fault of current detection E002 E017 running of the current circuit Frequency inverter constant...
GT200 series general purpose inverter instruction manual Chapter 5 Fault Countermeasures and Abnormality Handling 5.1 Fault Phenomena and Countermeasures When the inverter is abnormal, LED digit tube will display corresponding fault codes and its contents, the inverter will stop outputting, when a fault occurs, if the motor is rotating, it will park freely, till it stops rotating.
Page 79
GT200 series general purpose inverter instruction manual Fault Fault Type Possible Fault Reasons Countermeasures Code Input voltage abnormal Check input power supply The inverter Properly lengthen the accelerating Accelerating time is set too short accelerating time E004 running When instant stop occurs, Set start method F2.00 as the overvoltage implement restart on all rotating...
Page 80
GT200 series general purpose inverter instruction manual Fault Fault Type Possible Fault Reasons Countermeasures Code Ambient temperature is too high. Reduce ambient temperature. Control panel wiring or inserts are Check and connect again. loose. Current waveform abnormal Check wiring. caused by reasons such as output phase fault etc.
Page 81
GT200 series general purpose inverter instruction manual Fault Fault Type Possible Fault Reasons Countermeasures Code Control panel wiring or inserts are Check and connect again. loose. Auxiliary power supply is Current Seek for services E017 detection damaged. circuit fault Hall devices are damaged. Seek for services Amplification circuit is abnormal.
Page 82
GT200 series general purpose inverter instruction manual 5.2 Operation Abnormalities and Countermeasures The following abnormalities may occur during the usage, refer to Table 5-2 countermeasures to deal with: Table 5-2 Operation Abnormalities and Countermeasures Phenome Occurrence Possible Reasons Countermeasures Conditions Power on of the Operation panel locking function inverter after complete...
Page 83
GT200 series general purpose inverter instruction manual Phenome Occurrence Possible Reasons Countermeasures Conditions indicator turns Upper computer or remote Check communication off. control box disconnects from the line and Fb.04, Fb.03 inverter communication. and FA.15 settings. Check power supply Power supply is interrupted. situation.
Page 84
GT200 series general purpose inverter instruction manual Phenome Occurrence Possible Reasons Countermeasures Conditions Free parking function terminal is Check the free parking valid. terminal. Check the inverter to Inverter forbid the running forbid the running terminal is valid. terminal. Check external External shutdown function shutdown function terminal is valid.
GT200 series general purpose inverter instruction manual Chapter 6 Maintenance 6.1 Maintenance In case of change of service environment for inverter, such as temperature, humidity, smog and aging of inverter internal parts, the inverter fault may occur. Therefore, the inverter must be examined daily and given the regular maintenance in period of storing and using.
Page 86
GT200 series general purpose inverter instruction manual Table 6-2 Changing time of inverter parts Part name Standard changing time 2~3 years Electrolytic capacitor 4~5 years 5~8 years Fuse 10 years Applicable condition for changing time of aforementioned inverter parts (1) Environment temperature:Annual average is 30℃. (2) Load factor: Less than 80% (3) Running time: Less than 12 hours every day...
Page 87
GT200 series general purpose inverter instruction manual Annex Communication Protocol Networking Method Master is Master is PC Master is PLC 485 conversion 485 conversion module module RS485 RS485 GT210 GT210 M200 ED3100 GT210 Single master Single master multiple slaves multiple slaves Inverter Networking Diagram Interfacing method RS485: Asynchronous, half duplex Default: 8-N-2, 9600bps.See group FB description...
Page 88
GT200 series general purpose inverter instruction manual ASCII mode Modbus data frame Slave Function Check Data Start:“0x3A” End:“0xD,0xA” address code Modbus adopts the “Big Endian” coding method, which sends high bit bytes first, and then low bit bytes. RTU method: Under RTU method, idle time between frames could select function code setting or observe inner conventions of Modbus.
Page 89
GT200 series general purpose inverter instruction manual Frame Function Register Write Frame Address Head Code Address Content Check Character F A 0 8 CR LF ASCII 30 31 36 30 30 30 32 30 46 41 30 34 38 0D 0A The inverter, via function code, could set different response delays to adapt to detailed application needs of various master station, for RTU mode, actual response delay is not less than an interval of 3.5 characters, for ASCII mode, actual response delay is not less than 1ms.
Page 90
GT200 series general purpose inverter instruction manual These two parts form the application protocol data unit of Modbus, and the application protocol data unit in the following refers to these two parts. Description on frame format in the following takes RTU mode as an example, and ASCII mode application layer protocol data unit’s length needs to be doubled.
Page 91
GT200 series general purpose inverter instruction manual Application Layer Protocol Data Length(Bytes) Value or Range Data Unit Function Code 0x06 Register Address 0x0000~0xFFFF Register Content 0x0000~0xFFFF Response format is as follows: Application Layer Protocol Data Length(Bytes) Value or Range Data Unit Function Code 0x06 Register Address...
Page 92
GT200 series general purpose inverter instruction manual Re-initialize communication: Make no-response mode failure. 0xFF00 0xFF00 “New frame “New frame Set frame end of ASCII mode, and this end” and “00” end” and “00” “new frame end” will replace the old 0x0003 occupy high and occupy high...
Page 93
GT200 series general purpose inverter instruction manual register address in the following. If operation request fails, abnormal response is shown in the above. When storing multiple register parameters continuously, the inverter starts storing from the register at the lowest address, till the one at the highest address, and the storage may success completely or return from the address failing first.
Page 94
GT200 series general purpose inverter instruction manual Sub Function Function Data (Request) Data (Response) Significance Code Function code group The upper limit of Read the upper limit number and group 0x0000 function code of function code index occupy high and parameter.
Page 95
GT200 series general purpose inverter instruction manual Featured Parameter Value Significance (BIT) Modify step length to 1 BIT5~BIT4 Others Reserved Able to be modified. Unable to be modified during running BIT7~BIT6 Factory set, and users cannot modify. Actual parameter, unable to be modified. 0000B No unit 0001B...
Page 96
GT200 series general purpose inverter instruction manual Frequency proportion 0x3208 setting Virtual terminal control 0x3209 setting 0x320A Set accelerating time 1 0x320B Set decelerating time 1 Inverter’s State Parameter Index Register Parameter Name Address 0x3300 Operation state character 1 0x3301 Actual operation value of the current main setting 0x3302 Slave model...
Page 97
GT200 series general purpose inverter instruction manual 0x331A 0x331B Set length 0x331C Set accelerating time 1 0x331D Set decelerating time 1 Running command given channels: 0: Panel control 0x331E 1: Terminal control 2: Serial port control 0x331F Inverter state character 2 Frequency given channels: 0: Digit given 1, keyboard ▲...
Page 98
GT200 series general purpose inverter instruction manual Jog reversal BIT5 Jog reversal invalid Allow accelerating and decelerating BIT6 Reserved Prohibit accelerating and decelerating Upper computer Control word distributed by the control valid current upper computer valid. BIT7 Upper computer Control word distributed by the control invalid current upper computer invalid.
Page 99
GT200 series general purpose inverter instruction manual 0: Indicates the inverter is normal; Non-0: Indicates there’s a fault, and for the significance of specific fault code, please refer 00~ BIT15~8 Fault code to the user manual for 0xFF inverter of related type. For example, the fault code of motor overload E014 is 0x0E, while...
Page 100
GT200 series general purpose inverter instruction manual 3. Internal parameters of the inverter F3.09, F0.03 and F0.04 cannot be modified via communication settings, and communication cannot modify F0.04, but user password could be verified via writing F0.04. 4. When multiple multifunction input terminal functions are set the same, it will cause function disorders, and it is required to avoid such situation when users modify multifunctional terminal function via MODBUS protocol.
Page 102
GT200 series general purpose inverter instruction manual If CRC checksum of each sending byte is calculated online, it will take a long time, but could save program space occupied by tables.CRC codes to be calculated on line are as follows: unsigned int crc_check(unsigned char *data,unsigned char length) int i;...
Page 103
GT200 series general purpose inverter instruction manual Register Register Address Function Code Checksum Address Content 0x05 0x06 0x3200 0x00D0 0x876A 0x05 0x06 0x3200 0x00D0 0x876A 5#inverter Jog stops: Register Register Address Function Code Checksum Address Content 0x05 0x06 0x3200 0x00C0 0x86A6 0x05 0x06...
Page 104
GT200 series general purpose inverter instruction manual Register Function Register Register Address Number or Checksum Code Address Content Read bytes 0x05 0x03 0x3306 0x0001 None 0x6ACB 0x045 0x03 None 0x02 0x12C 0x49C9 Read 5#inverter’s decelerating time (which is F0.11), and inverter response decelerating time is 6.0S.