    User Manual Applications: • Wastewater treatment, oil and gas refineries, drilling rigs, petrochemical facilities, food and beverage facilities, tunnels, outdoor wall and stanchion mounted general area lighting, and where flammable vapors, gases are present. • Applies to hazardous locations of Class I, Division 2 with explosive gas atmosphere. •...
  • Page 3 User Manual Canada: CSA C22.2 No. 137; CSA C22.2 No. 250.0; Certifications and compliances for marine locations: NEC: • Damp and wet locations; • Certification body:UL • Certification Mark:UL • Certificate No:E495071 Standard : US: UL 1598A; UL 1598; Warning: CUL for Hazloc: ⚫...
  • Page 4 User Manual Technical table: Input voltage: AC100V-277V; Frequency: 50/60Hz; Output voltage: 33V~42Vdc; CCT:3000K-6500K Power Model Power factor:0.97 Light Luminous LEDs Type Weights Size(mm) efficiency LEDs Chip ( ) flux (LM) (kg) L x W x H (Lm/W) Pmax ≤ ≥4400 CES-J40S 36PCS 3030...
  • Page 5 User Manual Figure 2 Figure 3 applies to CES-J200. L x W x H: 400mm x 400mm x 169(248)mm Figure 3 Mounting: The product can be mounted as shown in Figure 4 -6 below. U-Bracket Size, applies to CES-J40S: Page 5 /11...
  • Page 6: U Bracket Mounting

    User Manual Figure 4 U-Bracket Size, applies to CES-J100, CES-J200: Figure 5 U bracket mounting: 1. The mounting method of M10X60MM expansion bolt as shown on the right: Two M10X60MM expansion bolts can be installed in the wall mounting position, the distance between two bolts is 75-160MM Page 6 /11...
  • Page 7 User Manual 2. Make the mounting holes of U bracket through the expansion bolt heads, putting in the spring washer and screw on the nuts. Make fully tighten between and explosion bolts with the wall by the wrench. Expansion bolts must be able to withstand four times the weight of the light fixture.
  • Page 8: Tempered Glass

    User Manual Figure 6 Appearance and Cable gland connection chart : Triangle frame TEMPERED GLASS U bracket REFLECTOR Front view a) Connect the equipment’s using suitable cable gland and armored cable. Page 8 /11...
  • Page 9: Cable Gland

    User Manual COVER BODY CABLE GLAND POWER BOX Type A (With 1pc cable gland) Choose the accurate cable section and cable glands for the appropriate mounting type features. Do not use the equipment on the fittings that have a lower protection class. iii) Use the suitable cable series according to the equipment inlet diameter or cable diameter.
  • Page 10 User Manual - Do not remove the cover without cutting of the energy. - In the case that deformation occurs on the equipment due to misuse or improper mounting, do not remove the cover and the frame. - Make the product electrical cable connections as shown below. L=Live N=NEUTRAL Thread=NPT 3/4″...
  • Page 11 User Manual 2) Flame-proof surface Pay attention to protect the flameproof surface, do not damage or corrosion it, otherwise the safe operation can not be guaranteed. Please contact the manufacturing company as soon as possible. 3) Bolt Always check the tightening degree of all bolts, especially the bolts fixing the explosion-proof part and the rotating part must be in a tight state.