Installation; Positioning - Warmco XR Series Instruction Manual

Premix unit air heater
Table of Contents

Advertisement

4 Installation

4.1 Positioning

Check that the support is solid enough.
The heater is designed as free hanging. The heater
should be able to blow the warm air free from any ducting
or obstacles. Also the air intake should be free.
Keep sufficient distance between the heater and any
obstruction , in connection with safety and access for
service and maintenance. See the drawings in this
chapter. Pay particular attention to any flammable
materials. Please take into account the possibility to
open the door of the heater for the necessary service
and maintenance work . Make sure the air flow to and
from the heater is unhindered. Any obstacles should be
a minimum of 5 metres away from the front of the
heater.
The heater can be installed horizontally or on an angle
of maximum 45 degrees downwards.
When the heater is installed other than horizontal,
Always re-adjust the CO2 setting from the gas valve.
The heaters type 10 and 20 are provided with 2 off
M10 threaded sockets as fixing points (see the
dimension diagram).
The types 30 and 40 have in the middle a M10 socket and also 4 sockets on the top corners
of the heater
The types 50 and 60 have on the top and bottom 4 M10 sockets. (see drawings)
Use preferably the Winterwarm suspension kits.
Make sure that after fitting, there is no mechanical tension on any connecting gas or electric
supplies.
If the heater is installed with the air stream vertical downwards the maximum suspension
height is 8 meters. Otherwise the warm air will not reach the floor.
Attention:
See the application-restrictions in this manual (Chapter 2) for further installation restrictions.
Instructions condensing Air heaters type XR version XR-GB-4001-a
10 t/m 30 min. 500 mm
40 t/m 60 min 660 mm