Thank you for your purchase of the Larson Electronics EPSW-TS-RTD-6P-R1.
\
WARNING:
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
CRITICAL SAFETY INSTRUCTIONS:
INSTALLATION SHOULD ONLY BE CONDUCTED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NEC AND ANY
RELEVANT LOCAL BUILDING CODES.
RISK OF FIRE OR ELECTRIC SHOCK. FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF FIXTURE'S ELECTRICAL
SYSTEMS. IF NOT QUALIFIED, CONTACT A QUALIFIED ELECTRICIAN.
BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.
MAKE SURE THE SUPPLY VOLTAGE IS THE SAME AS THE FIXTURE'S RATED VOLTAGE.
TO PREVENT WIRING DAMAGE OR ABRASION, DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR SHARP
OBJECTS. SUITABLE FOR DAMP LOCATIONS.
WARNING
TO AVOID THE RISK OF FIRE, EXPLOSION OR ELECTRIC SHOCK, THIS PRODUCT SHOULD BE INSTALLED,
INSPECTED AND MAINTAINED BY A QUALIFIED ELECTRICIAN ONLY, IN ACCORDANCE WITH ALL
APPLICABLE ELECTRICAL CODES.
TO AVOID ELECTRIC SHOCK:
BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.
PRODUCT MUST BE CONNECTED TO A WIRING SYSTEM WITH AN EQUIPMENT-GROUNDING
CONDUCTOR.
TO AVOID EXPLOSION:
MAKE SURE THE SUPPLY VOLTAGE IS WITHIN THE VOLTAGE RATING.
ENSURE THE MARKED T RATING IS LESS THAN THE IGNITION TEMPERATURE OF THE HAZARDOUS
ATMOSPHERE.
DO NOT OPERATE IN AMBIENT TEMPERATURES ABOVE THOSE INDICATED ON THE PRODUCT
NAMEPLATE.
DO NOT OPERATE IF THE LENS, CORD, SEALS, HOUSING, RECEPTACLES, ETC. IS CRACKED OR
DAMAGED. IF SO, DISCONTINUE USE AND CONTACT MANUFACTURER FOR REPLACEMENT PARTS.
ALL FASTENERS SHOULD BE PROPERLY SEATED.
The EPSW-TS-RTD-6P-R1 from Larson Electronics is an Explosion Proof RTD Temperature Transmitter for Class I, II
and III rated locations. This low voltage unit contains a 6" stem/probe and features an LCD display. Protected by a NEMA
4X rated 316 stainless steel housing, the transmitter offers seven pre-programmed temperature ranges.
WIRING
Standard pigtail(flying leads) wiring
We strongly encourage a licensed electrician install this product
where weatherproofing may be required. Universal voltage driver permits operation at 10V - 35V DC.
Warning: Check product label for correct input voltage!
Attach supply line wires to the appropriate light fixture wires as shown
in the diagram 
Secure each pair of wires according to the diagram. Utilize a junction box or
similar
device
and
take
connections if installed in a location where water may come in contact with the
unit. Ensure the unit is properly grounded and that wiring is done according to
all local and national electrical/building codes.
Larson Electronics, LLC
Explosion Proof RTD Temperature Transmitter
Class I, II, III - 6" Probe - ATEX/IECEx - N4X
Instruction Manual
precautionary
steps
Phone: (800) 369-6671
, in all locations especially in outdoor areas
for
weatherproofing
all
Fax: (903) 498-3364
EPSW-TS-RTD-6P-R1
www.larsonelectronics.com
1 of 5

Advertisement

loading

Summary of Contents for Larson Electronics EPSW-TS-RTD-6P-R1

  • Page 1 ALL FASTENERS SHOULD BE PROPERLY SEATED. The EPSW-TS-RTD-6P-R1 from Larson Electronics is an Explosion Proof RTD Temperature Transmitter for Class I, II and III rated locations. This low voltage unit contains a 6" stem/probe and features an LCD display. Protected by a NEMA 4X rated 316 stainless steel housing, the transmitter offers seven pre-programmed temperature ranges.
  • Page 2: Installation

    DC. This variable voltage allows greater versatility without affecting light output. Ensure deutsch connectors are properly connected (If applicable) HUBS The EPSW-TS-RTD-6P-R1 contains one 1/2" male NPT hub for process connections and one 1/2" female NPT hub for conduit connections. INSTALLATION 1.
  • Page 3: Equipment Required

    Upon detecting an open RTD, the unit may be set to force the output to read 3.5 mA or 21mA based upon the setting of DIP SWITCH 6. SWITCH 6 “OFF”, output forced to 3.5 mA SWITCH 6 “ON”, output forced to 21 mA Larson Electronics, LLC 3 of 5 Phone: (800) 369-6671 Fax: (903) 498-3364...
  • Page 4: Electrical Connections

    10 kA. If the power source is rated for a prospective short circuit current of less than 10 kA, the end user or installer must mark the equipment with the prospective short circuit current rating of the power supply it is used in conjunction with. Larson Electronics, LLC 4 of 5 Phone: (800) 369-6671 Fax: (903) 498-3364 www.larsonelectronics.com...
  • Page 5: Maintenance

    Inspect for good working condition prior to storage and before re-use. REPLACEMENT PARTS The EPSW-TS-RTD-6P-R1 is designed to provide years of reliable performance. Should the need for replacement parts arise, please contact Larson Electronics. THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS.