Download Print this page

Helios KWL-FB Installation And Operating Instructions page 2

Advertisement

Available languages

Available languages

INSTALLATION AND OPERATING INSTRUCTIONS NO. 91794
Control panel KWL-FB (for KWL EC 200/300/500)
CONTROL PANEL
Start button
1 1
Press this button to switch the KWL EC
200/300/500 Pro on and off. If the LED lights
up, the unit is switched on.
Carbon dioxide control
2 2
Press this button to switch the carbon dioxide
control on and off. If the LED lights up, the
control is switched on.
Humidity control
3 3
Press this button to switch the humidity con-
trol on and off. If the LED lights up, the control
is switched on.
4 4
Summer/Winter function
Press this button to switch from summer to
winter operation. The winter operation is ac-
tivated when the LED lights up and the me-
chanical bypass is deactivated.
CONTROL PANEL MOUNTING, REMOVAL, WIRING
The control panel is wired directly from the KWL EC 200/300/500 Pro terminal box. The control panel can also be wired in
series with a CO
-sensor or another control panel.
2
ADDRESSES OF CONTROL PANELS
If two or more control panels are connected to the system, the addresses of the control panels have to be changed.
Example: 3 control panels
- Connect the first control panel to the unit and change its address to 3.
- Connect the second control panel to the unit and change its address to 2.
- Connect the third control panel to the unit and check to see if its address is 1.
If control panels have the same address, they go to bus fault state. In this case, remove the second control panel
and change the address of the second control panel. Such a situation can occur in connection with the later in-
stallation of an additional control panel.
Scrolling upwards
5 5
with this button you can scroll upwards in the
display.
Scrolling downwards
6 6
With this button you can scroll downwards in
the display.
7 7
Positive button
With this button you can increase values.
Negative button
8 8
With this button you can decrease values.
Fireplace or booster switch
The fireplace / booster switch is activated in this display by simulta-
neously pressing down the + and – buttons (>2 sec.).
Main menu
Fan speed
Supply air temperature
Postheating active
"without function"
Control panel inside
(fig. no guarantee)
2
The fan speed can be changed in this display
with the + and – button.
Maintenance reminder alert
Fireplace / booster switch on
Clock timer is on
Wiring
1 2 3 4 5
+ - A B M
Cable:
JY(ST)Y
2x2x0,6 mm
ATTENTION:
Faulty coupling of the (+) wire
damage the cotrol panel.
1 = orange 1 = +
2 = white 1
3 = orange 2 = A
4 = white 2
5 = metal
Keyboard
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
Main menu
2
2
+ 0,5 mm
= –
= B
= signal ground

Advertisement

loading