Honeywell R4560 Instruction Sheet page 3

Automatic ignition controller

Advertisement

SPECIFICATIONS
Model
R4560:
220 ... 240 V, 50 Hz.
Suffix M: For power burners.
Manual reset according to
DIN 4788 part 3.
Warm air heaters according
to DIN 4794 part 3
Lock--out on false flame.
Lock--out on no air.
Dimensions
See fig. 5
Ambient temperature
E
--20 ... 60
C
Relative humidity
E
90% max. at 40
C (non condensing)
Supply voltage
Line voltage, 220 V (--15%) ... 240 V
p
(+10%), 50 Hz (
2 Hz)
Power consumption
10 VA maximum.
SYSTEM OPERATION
Automatic ignition controller for po-
wer burners (see fig. 3 and 4)
When thermostat calls for heat, fan is
energized if air proven switch is in the
no air position.
When sufficient air flow is proven by the
air proving switch, a prepurge period
(T
) elapses before the optional built--in
p
spark igniter or the external ignition
transformer and the pilot gas valve (V
is energized in case of intermittent pilot
ignition or both gas valves (V
are energized in case of direct burner
Control behaviour during loss of air flow and flame signal
Prepurge time
Loss of air flow
0,5 s < T
< 1 s
lost
Flame lost
Note: Air flow loss < 0,5 second is not considered as air flow loss
EN1R--9102 9402R1--NE
Electrical rating
Valve output:
Fan:
Alarm output:
Ignition transformer: 1 A cos ϕ =0.4
Timing (depending on O.S. number)
Prepurge time (T
Safety time (T
Flame sensing
Flame sensing is based on the
rectification principle.
Minimum flame current: 1 µA
Response time "ON"
(at 2 µA flame current): < 200 ms
Response time "OFF": < 1 s
Ignition
:
Integral electronic spark generator
with 2,8 x 0,8 mm spade terminal for
extended wiring (terminal/cable 11,
in fig. 1 and 2).
Spark voltage:
Repetition rate:
Max. cable length: 100 cm
ignition.
The ignition spark ignites the gas and
the resulting flame is detected by the
flame rod.
Ignition is switched off immediately
after flame is established.
If flame is not established within the
safety time (T
controller locks out.
)
If air flow is not proven by the air
1
proving switch, the automatic ignition
and V
)
controller will lockout after T
1
2
Air flow loss during:
Safety time
(T
(T
p )
s
Restart
Lockout
--
Restart
1 A cos ϕ =0.6
1 A cos ϕ =0.6
1 A cos ϕ =0.6
): 10, 20 or 30 s
p
):
3 or 5 s
s
12 kV at 40 pF
load
50 Hz
), the automatic ignition
s
T
.
p +
s
Normal run
)
Lockout
Restart
:
An external (more powerful) ignition
transformer (S720) can be wired in
the system.
Recommended flame sensor
Q354 Flame sensor
Recommended spark igniter
Q375 Spark igniter
Fusing
Automatic ignition controller should be
externally fused to prevent damage to
automatic ignition controller, wiring or
periferals.
External fuse: 16 A slow max.
Enclosure
IP 40
Accessories (to be ordered separa-
tely)
High voltage ignition cable with length
of 50 cm.
order number:............ 45.900.411--001
Subbase
ordernumber:............. Q632A 1124
If flame is lost during normal run, the
automatic ignition controller repeats the
start sequence.
Lockout reset
The auto ignition controller will be reset
by depressing the reset button.
Press the button completely down.
If a first reset is not succesful wait at
least 15 seconds before making
another attempt.