Important Notes On Using The Device - Siemens SIMATIC NET S7-1200 Compact Operating Instructions

Compact switch module csm 1277
Hide thumbs Also See for SIMATIC NET S7-1200:
Table of Contents

Advertisement

Installation

4.1 Important notes on using the device

4.1
Important notes on using the device
Read the safety notices
Note the following safety notices. These relate to the entire working life of the device.
If a device is operated in an ambient temperature of more than 55 °C, the temperature of the
device enclosure may be higher than 70 °C. The device must therefore be installed so that it is
only accessible to service personnel or users that are aware of the reason for restricted access
and of the required safety measures at an ambient temperature higher than 55 to 70 °C.
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds
80 °C, special precautions must be taken. If the equipment is operated in an air ambient in
excess of 60 ℃, only use cables with admitted maximum operating temperature of at least 80
℃.
NOTICE
Improper mounting
Improper mounting may damage the device or impair its operation.
• Before mounting the device, always ensure that there is no visible damage to the device.
• Mount the device using suitable tools. Observe the information in the respective section
Safety notices on use in hazardous areas
General safety notices relating to protection against explosion
EXPLOSION HAZARD
Do not open the device when the supply voltage is turned on.
EXPLOSION HAZARD
Replacing components may impair suitability for Class 1, Division 2 or Zone 2.
22
WARNING
WARNING
about mounting.
WARNING
WARNING
Compact Switch Module CSM 1277
Compact Operating Instructions, 06/2022, A2B00079397-02

Advertisement

Table of Contents
loading

Table of Contents