Download Print this page

American Standard Foundation BAYHTFA305 Series Installation Instructions Manual page 7

Packaged rooftop units

Advertisement

Figure 7.
Install heater - side view
6. Secure heater with ½" sheet metal screws provided in
the ship-with packet, shooting through the pre-drilled
holes.
Figure 8.
Secure heater with screws
ACC-SVN207B-EN
7. Punch hole in rubber grommet in mid-panel behind
post prior to routing wires.
Note: Use wiring diagram provided to perform the
following steps.
8. Attach wires pre-routed in vestibule to heater.
Figure 9.
Attach wires
Harness connections between contactors
and heater elements assembly
9. Connect low voltage plug to the mating plug in the unit
control box.
10. Route and secure the power wire harness, one end to
the terminal block in the heater control panel and the
other end to the terminal block in the unit control box
or terminal block at single point box or TBUE, as
required.
Installation
7

Advertisement