FEATURES The DP-PSUEN series of power supplies are designed to be used for fire alarm control and indicating equipment complying with EN54-2 and EN54-4. The power supply range consist of a 5 amp, 3 amp and 1.5 amp devices, providing a nominal 27V with two 12V lead acid batteries for standby operation without AC power.
RoHs: 2011/65/EU IEC61140: Protection against electric shock – Common aspects for installation and equipment: Class 1 EN54-4: 1997 + A1 + A2 Part 4: Power Supply Equipment 0359 DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE - 4 -...
The metal enclosures should be mounted on a solid, flat and dry surface using the three mounting points provided. The screws should have a minimum shank diameter of 5mm (No 11 gauge) and use suitable wall plugs where needed. DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE - 7 -...
When the jumper is fitted the PSU will use the internal on-board (Internal/external (Internal temperature sensor, the link must be put into the off position to use an temperature temperature external temperature sensor. sensing) sensing) DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE - 8 -...
Due to high instantaneous current that can flow under fault conditions, the DC output wire is recommended to be 1mm cross sectional area or greater for all DP-PSUEN series power supplies. The outputs are individually protected against short circuits. The outputs can be switched using the SW1 and SW2 output control inputs.
This is important to maintain a balance of charge between the two batteries. Two cable harnesses are provided for individual connection to the board, where they are connected in series. The remote temperature DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE...
8. Check the voltage outputs, they should be nominally between 26.5V and 28.5V depending on temperature. 9. There are no replaceable input, battery or output fuses. In the event of a fault the power supply board will have to be replaced. DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE - 11 -...
DISCLAIMER Although the contents of our product literature have been prepared with the greatest care, Technoswitch can accept no liability whatsoever for any direct or indirect damages of any kind that may arise due to either errors or omissions in them or amendments to products or other specifications following publication.
Page 14
Tyger Terraces II, Block 2B, DJ Wood Street, Bellville Business Park Cnr Mike Pienaar Blvd & Voortrekker Road, Bellville, 7530 DURBAN +27 (0)31 266 8843 Colchester Building, Essex Gardens 1 Nelson Road, Westville 3629 www.technoswitch.co.za DP-PSUEN Series Installation & Operation Manual Rev 11.1 220323.docx E&OE...