Thanks for purchasing XINJE XD series PLC and extension module. This manual will
introduce the electric features and using method of XD series extension ED module. Please
read this manual carefully before using the products, make sure the wiring operation is safe.
Features of analog extension module
XD-2AD2PT-V-ED
2 channels analog input: voltage input mode, 0~5V or 0~10V.
2 channels PT100 temperature input: temperature range -100~500℃, precision
0.1℃.
12-bit high precision analog input.
As the special function ED module of XD, XD series PLC can connect 1 XD-
2AD2PT-V-ED module.
Safety precautions
Control system design attentions
Dangerous!
 Make sure design the safety circuit, to ensure that the control system can still work
safety when the external power supply cut off or PLC broken.
 Make sure set emergency braking circuit, protection circuit, interlock circuit of forward-
reverse running in PLC external circuit and upper-lower limit switch to prevent from
machine damage.
 In order to make the equipment safe operation, please design external protection circuit
for important output signal.
 PLC CPU will close all the output when detecting the system error; the output will lose
control when the PLC circuit has problem. Please design suitable external control circuit
to ensure the device working normally.
 If the PLC relay or transistor unit is broken, the output cannot be ON or OFF.
 The PLC is designed for indoor environment, the lightning protection must be installed
in the power supply system to avoid PLC and other device damage.
Installation and wiring attentions
Dangerous!
 Do not use the PLC in the following environment: dust, soot, corrosive gases,
flammable gas, high temperature, condensation, vibration, impact, lightning, fire.
 Do not let the metal scrap and wire head drop into the ventilation hole of PLC, otherwise
it will cause fire or error operation.
 Do not cover the ventilation hole of PLC, otherwise it will cause fire, error operation.
 The I/O wiring must be fixed enough, otherwise the bad contactor will cause fault.
Attention!
 It can use external power supply for extension module DC24V power.
 Please use shield cable for high frequency I/O wiring to avoid interference.
Run and maintenance
Dangerous!
 Please connect all the cable include PLC, extension module and BD board after shutting
down the power supply.
 Please operate as the manual for online operation, forced output, RUN, STOP.
Attention!
 Please discard the product as industrial waste.
 Make sure cut off the power supply when installing or uninstalling the extension card.
Product information
Naming rule
XD– 2 AD 2 PT - V - ED
② ③ ④ ⑤
⑥ ⑦
Product series
XD: XD series extension module
Analog input channel: 2: 2 channels
Analog input
AD: analog input
Temperature input channel: 2: 2 channels
Temperature input
PT: PT100 temperature input
I/O type
V: voltage type for input
Module type
ED: left extension ED module
Basic parameters
XD series PLC can connect 1 extension ED module, the type is not limited.
Table 1: analog extension module XD-2AD2PT-V-ED general specifications
Item
Specifications
Using environment
No corrosive gas
Environment temperature
0℃~60℃
Storage temperature
-20~70℃
Environment humidity
5~95%RH
Storage humidity
5~95%RH
Installation
Fix with M3 screw or install on the rail DIN46277(width
35mm)
Dimension
100.0mm× 18.0mm× 90.0mm
Table 2: analog extension module XD-2AD2PT-V-ED I/O precision
的导轨上
Item
Analog voltage input (V)
Temperature input (PT)
Analog input
0~5, 0~10V
range
Temperature
-100~500℃
input range
Max input range
DC± 15V
Digital output
12-bit binary number
-1000~5000
range
(0~4095)
Resolution
1/4095(12Bit)
0.1℃
integrated
1%
± 0.8% of the full scale
precision
Transformation
2ms/1 channel
2ms/1 channel
speed
Power supply for
DC24V± 10%, 150mA
analog
Table 3: analog extension module XD-2AD2PT-V-ED AD transformation diagram
The relationship between analog input and transformed digital value
0~10V analog input
0~5V analog input
+4095
+4095
0
0
10V
analog
analog
PT100 input
Product appearance
Here listed I/O terminal configurations of XD series extension module XD-2AD2PT-V-ED.
Product structure
Each part name:
Name
PWR
The LED lights when the ED module has power supply
Indicator
COM
The LED lights when the ED module communication
light
port works well
ERR
The LED lights when the ED module has error
24V
ED module external power supply 24V +
0V
ED module external power supply 24V -
VI0
Channel 1 analog input
Wiring
VI1
Channel 2 analog input
terminal
CI0
VI0, VI1 ground
A0
Channel 1 PT100 input
A1
Channel 2 PT100 input
C0
PT1, PT2 ground
Product dimension and installation
Installation
Do not install the module in below environment:
 Direct sunlight
 Environment temperature out of range 0-50℃
 Environment humidity out of range 35%-85% RH
 Condensation as severe changes in temperature
5V
 Corrosive gas and flammable gas
 Dust, iron filing, salt, fume
 Vibration and impact
 Spray oil, water and medicine
 Strong magnetic field and strong electric field
XD series extension ED module can be installed in com3 port of XD series PLC.
Note: please cut off the power before operation!
Product dimension
XD series extension ED module dimension is shown as below:
Electric design reference
I/O address
XD series extension ED module will not occupy I/O unit, the transformed value is stored in
PLC register. The following is the PLC register corresponding to each channel.
Function
Channel
AD signal
0CH
ID30000
1CH
ID30001
Channel
PT signal
0CH
ID30002
1CH
ID30003
Working mode setting
(Unit: mm)
PWR
COM
ERR

Advertisement

loading
Need help?

Need help?

Do you have a question about the XD-2AD2PT-V-ED and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Xinje XD-2AD2PT-V-ED

  • Page 1 ① Product series XD: XD series extension module Thanks for purchasing XINJE XD series PLC and extension module. This manual will ② Analog input channel: 2: 2 channels introduce the electric features and using method of XD series extension ED module. Please ③...
  • Page 2 Please pay attention to below items when wiring: ① please use shield cable to avoid interference, and single point connect to ground for the shield layer. ② when XD-2AD2PT-V-ED connects external+24V power supply, please choose the power supply from PLC to avoid interference. ...