INNOVATIVE CIRCUIT TECHNOLOGY Distribution 2 Series Instruction Manual

Intelligent distribution panel with remote power control

Advertisement

Quick Links

Innovative Circuit
Technology Ltd.
Distribution Series 2
Intelligent Distribution Panel
with Remote Power Control
INSTRUCTION MANUAL
855-313-500
Model:
ICT180SE-12IRC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Distribution 2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for INNOVATIVE CIRCUIT TECHNOLOGY Distribution 2 Series

  • Page 1 Innovative Circuit Technology Ltd. Distribution Series 2 Intelligent Distribution Panel with Remote Power Control INSTRUCTION MANUAL 855-313-500 Model: ICT180SE-12IRC...
  • Page 2 Rev 0 2022 Copyright © 2022 Innovative Circuit Technology Ltd. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written consent of Innovative Circuit Technology Ltd.
  • Page 3: Table Of Contents

    User Setup .................... 22 Maintenance ..................22 MOBILE WEB APP ..................23 PASSWORD RESET ..................24 ROUTER CONFIGURATION ............... 25 TEXT MESSAGE ALARM NOTIFICATIONS ..........27 TROUBLESHOOTING ................. 27 PRODUCT SPECIFICATIONS............... 29 LIMITED WARRANTY ................31 Innovative Circuit Technology Ltd.
  • Page 4: Product Description

    DC outputs can be turned on and off remotely, allowing connected loads to be power-cycled through the Ethernet connection. FRONT PANEL Figure 1. 1. FUSE STATUS LEDs: Turns on when a fuse is blown or missing. 2. ATO/ATC FUSES: Location of the ATO/ATC fuses rated up to 25A. Innovative Circuit Technology Ltd.
  • Page 5: Installation

    Earth ground point. Otherwise, the four mounting screws and washers may be sufficient for earth ground connection. For non-rack set up, connect a ground cable from the ground stud on the back of the panel to a known Earth ground point. Innovative Circuit Technology Ltd.
  • Page 6 Alarm Input (1 - 5) and common (C) on the alarm input connector. The alarm input connector can be unplugged from the panel for easy installation. Refer to table 3 for the alarm input connector pin-out. FUSE STATUS Blown or missing Good Table 1: Fuse Status LED Innovative Circuit Technology Ltd.
  • Page 7 Table 2: Form “C” Alarm DESCRIPTION Common Alarm Input # 1 Common Alarm Input # 2 Common Alarm Input # 3 Common Alarm Input # 4 Common Alarm Input # 5 Table 3: Alarm Input Connector Pin-out Innovative Circuit Technology Ltd.
  • Page 8: Lcd/Select Button Operation

    (see Password Reset section). The backlight of the LCD turns off if the Output Select button is not pressed for 15 minutes. Press the Output Select button to turn the backlight back on. Innovative Circuit Technology Ltd.
  • Page 9 Line 4: Display the alarm input status. ALARM if the alarm input is triggered, READY if the alarm input is not triggered. Note: The alarm input screens are only displayed if the alarm input has enabled (see Alarm Setup section in the instruction manual). Innovative Circuit Technology Ltd.
  • Page 10: Web-Based Configuration Utility

    To log out, click on the Logout link on the top right of your browser window. The system will also automatically log off the user after 20 minutes of inactivity. Innovative Circuit Technology Ltd.
  • Page 11: Status & Control

    Disable All Outputs: Pressing this button will disable DC power to all outputs. Output On/Off Buttons: Pressing these buttons will enable or disable DC power to individual outputs. Innovative Circuit Technology Ltd.
  • Page 12: Alarm Status

    (Factory default). Note the Sequence Delay time will also be used as the Power Cycling time delay for each output that has the Power Cycling feature enabled on the Output Setup page. Innovative Circuit Technology Ltd.
  • Page 13 IP address continues to be unresponsive. Set Maximum Cycle Attempts to zero for no limit. Data Logging: Data Logging rate: Enable this feature to keep a running record the system voltage, system current, channel output currents, fuse status, and alarm Innovative Circuit Technology Ltd.
  • Page 14: Output Setup

    Sequence/Cycle Delay time whenever the output is disabled using the Output Off button on the Status & Control page. This feature is useful for remotely resetting power to hardware required for the network connectivity of the panel. Innovative Circuit Technology Ltd.
  • Page 15 Current alarm e-mail to the assigned address entered on the E-mail Setup page. Output Under-Current Alarm: Under-Current Threshold: Enter the under-current level. Output current below this level for at least 5s will trigger the Under-Current Alarm. Disable this alarm by setting the threshold to 0A. Innovative Circuit Technology Ltd.
  • Page 16: Network Setup

    The following ports may be changed within a range of 1 to 65565, if required. HTTP Port: This port is used for HTTP traffic between the panel and your browser. The default HTTP port is 80, and if you change this the new HTTP Innovative Circuit Technology Ltd.
  • Page 17 SNMP. No other settings can be configured through SNMP. • Full Device Control: Allow SNMP clients to set all device settings through SNMP. MIB files for full SNMP device control can be downloaded from the ICT Website: Innovative Circuit Technology Ltd.
  • Page 18 Trap Community: Assign the community string/password that will be sent with all SNMPv1 traps. Some trap receivers are able to filter based on Trap Community. Trap User Name: Assign the user name for SNMPv3 traps. Innovative Circuit Technology Ltd.
  • Page 19: E-Mail Setup

    Use commas to separate multiple addresses. This field can also be used to send a text message notification to a phone; see the Text Message Alarm Notifications section for further information. Innovative Circuit Technology Ltd.
  • Page 20: Alarm Setup

    Under-Voltage Recovery: If the system voltage rises above the value in this field, the system under-voltage alarm will clear. The value in this field must be at least 0.50V higher than the Under-Voltage Threshold. Innovative Circuit Technology Ltd.
  • Page 21 Send E-mail: Check this box to have an email notification sent when one of the enabled alarm inputs is triggered, stating which input was affected. Note Innovative Circuit Technology Ltd.
  • Page 22: User Setup

    Reset Distribution Panel: Clicking the Reset button will restart the panel. Channel output states will be restored according to the Output State after Panel Reset setting for each output on the Output Setup page. All other setting are maintained during the reset. Innovative Circuit Technology Ltd.
  • Page 23: Mobile Web App

    Status & Control screen: For improved security you should normally use a secure HTTPS connection when assessing the panel over the Internet with the Mobile Web App, or use a Virtual Private Network (VPN) connection. Innovative Circuit Technology Ltd.
  • Page 24: Password Reset

    20 seconds until Resetting is shown on the LCD. Release the button Press and release the output select button once to view the Network Status screen on the LCD. The new IP address of the panel will be displayed. Innovative Circuit Technology Ltd.
  • Page 25: Router Configuration

    (such as a panel, or web server) already using port 80. Configure HTTPS forwarding by repeating steps 2a to 2e with the HTTPS port number that the panel is using. The default HTTPS port number is 443. Innovative Circuit Technology Ltd.
  • Page 26 HTTP port number the panel is using. (e.g. http://209.123.10.33:8000 for a router address 209.123.10.33, port 8000) Figure 9: Panel Access With Router Address Innovative Circuit Technology Ltd.
  • Page 27: Text Message Alarm Notifications

    Ensure the network card settings on your computer are configured for accessing the IP address of the panel. To access a panel with the default IP address of 192.168.0.180 the typical network settings for your computer are: IP Address: 192.168.0.100 Innovative Circuit Technology Ltd.
  • Page 28 If your SMTP server requires SSL encryption, ensure the SMTP Server requires SSL checkbox is ticked. Otherwise leave blank. • If your SMTP server requires authentication, ensure that the SMTP User Name and SMTP Password fields are correctly entered. Innovative Circuit Technology Ltd.
  • Page 29: Product Specifications

    SNMP v1/v2c/v3 supported Network Security: Password protection, SSL encryption for HTTPS and SMTP (TLS 1.2) Input Connector: Heavy Duty Insulated M10 Stud 75in-lbs Max Output Connector: Barrier Terminal Block M4 Screws 8 – 20AWG Wire Range 12in-lbs Max Innovative Circuit Technology Ltd.
  • Page 30 Euro Terminal Block M2 Screws 16 – 28AWG Wire Range 1in-lbs Max Operating Temperature: -20°C to +60°C Weight: 8.0lbs (3.6kg) Warranty: 2 years Dimensions: 19.0” x 9.3” x 1.7” 483mm x 236mm x 44mm Figure 10: Mechanical Dimensions Innovative Circuit Technology Ltd.
  • Page 31: Limited Warranty

    ICT LIMITED WARRANTY The warranty period on ICT products is two (2) years from date of purchase from an authorized ICT reseller or OEM with valid proof of purchase, or from date of shipment from the ICT manufacturing facility. The warranty period for a repaired product or part is ninety (90) days or the remainder of the unexpired term of the new product warranty period, whichever is greater.
  • Page 32 ICT and Purchaser with respect to the subject matter herein and supersedes all prior verbal or written communications, representations, understandings or agreements relating to this subject. INNOVATIVE CIRCUIT TECHNOLOGY LTD. 26921 Gloucester Way Langley, British Columbia, Canada V4W 3Y3 T 604.856.6303 F 604.856.6365...