Allarms - Gastrodomus TSD100 User Manual

Blast chillers
Table of Contents

Advertisement

Available languages

Available languages

Periodic Operations
-
Periodically clean the condenser using suitable tools ( vacuum cleaner or soft brushes)
-
Check that the electrical connections are not loose.
-
Check that the thermostat and the sensor are in proper working order.
-
Recommend that an agent or qualified technician clean the condenser.
-
Replace the power cable with qualified technical personnel
IX. ALLARMS
Message
rPf
EPF
NxF (X= numero inserito)
HA
LA
OFC
EA
CA
dA
CPA
Cause
Chamber probe fault
Evaporator probe failure
Insertion probe failure
Maximum temperature alarm
Minimum temperature alarm
The maximum cycle time has
been exceeded
External alarm
Serious external alarm
Door opening alarm
Compressor protection alarm
Outputs
Compressor Output According to
Con and Cof Parameters
Fans depend on FnC . Defrosting
ends on time
Unchanged outputs. The cycle
has a fixed time
outputs unchanged / not
changed
(manual reset)
outputs unchanged / not
changed
Outputs unchanged / not
modified.
When the blast chiller reaches
temperature, the cycle ends.
(it is reset manually)
outputs unchanged / not
changed
All controls off
According to "rrd" to control fans
and compressor
outputs unchanged / not
changed
24