1. Important Safety Warning SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries Please comply with all warnings and operating instructions in this manual strictly. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1.
1-4. Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output ...
Page 5
When changing batteries, install the same number and same type of batteries or battery packs. Battery Case Manufacture Type Flame Rating Rating HITACHI CHEMICAL GP 1272 12 V, 7.2 Ah ENERGY TECHNOLOGY CO GP 1272 F2 12 V, 7.2 Ah LTD (MH14533) GP 1272 FR 12 V, 7.2 Ah...
Page 6
CO LTD (MH28539) RT1290 12 V, 9.0 Ah Please replace the fuse only with the same type and amperage in order to avoid fire hazards. Do not dismantle the UPS system. NOTE: This equipment has been tested and found to comply with the limits for a ...
2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1. Rear panel view DTK-UPS1000R+/DTK-UPS1500R+ DTK-UPS2000R+ DTK-UPS3000R+ 1. Programmable outlets: connect to non-critical loads. 2.
2-2. Operating principle The operating principle of the UPS is shown as below Output Input Dynamic Bypass The UPS is composed of EMI/RFI Rectifier Inverter EMI/RFI filters, rect Filters /PFC inverter, battery charg converter, battery, dynam DC-to-DC Converter UPS output. Battery Battery Charger...
Tower Installation with battery pack Step 1 Step 2 2-4. Setup the UPS Before installing the UPS, please read below to select proper location to install UPS. 1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration, dust, humidity, high temperature, flammable liquids, gases, corrosive and conductive contaminants.
Page 10
3. Remove the cover of the external battery connector by using a screwdriver. 4. Plug the battery cable into the external battery connector of the UPS and the battery pack(s). Note: If you have multiple battery packs available, connect them serially. An example is shown in the diagram below (connecting the second battery connector of the first battery pack to the first battery connector of the second battery pack).
Page 11
Step 2: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. The power cord is attached to the UPS. The input plug is a NEMA 5-15P for DTK-UPS1000R+/ DTK-UPS1500R+models, NEMA 5-20P for DTK-UPS2000R+ model and NEMA L5-30P for DTK-UPS3000R+ model.
Step 6: Disable and enable EPO function This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin 1 and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To activate EPO function, remove two screws on EPO port and metal plate will be removed.
Page 13
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. Step 1 Step 2 Step 3 Remove front panel. Disconnect battery wires. Pull out the battery box by removing two screws on the front panel. Step 4 Step 5 Step 6 Remove the top cover of After replacing the Re-connect the battery wires.
2-6. Battery Kit Assembly NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. 2-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart.
Page 15
4-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells. below chart.
3. Operations 3-1. Button operation Button Function Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the alarm ON/Mute system.
Page 17
Function Display Backup time information Indicates the estimated backup time. H: hours, M: minute, S: second. Configuration and fault information Indicates the configuration items, and the configuration items are listed in details in section 3-5. Indicates the warning and fault codes, and the codes are listed in details in section 3-7 and 3-8.
3-3. Audible Alarm Battery Mode Sounding every 5 seconds Low Battery Sounding every 2 seconds Overload Sounding every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds 3-4. LCD display wordings index Abbreviation Display content Meaning Enable Disable Escape High loss Low loss Active open...
3-5. UPS Setting There are three parameters to set up the UPS. Parameter 1 Parameter 1: It’s for program alternatives. Parameter 2 Refer to below table. Parameter 2 is the setting options or values for each program. 01: Output voltage setting ...
Page 20
05: ECO voltage range setting Interface Setting Parameter 2: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. The setting range in parameter 3 is from +3V to +12V of the nominal voltage.
Page 21
49HZ. (Default: 47.0Hz) For 60Hz output frequency models: 55-59Hz: setting the frequency low loss point from 55Hz to 59Hz. (Default: 57.0Hz) 09: Programmable outlets enable/disable Interface Setting Parameter 2: Enable or disable programmable outlets. ENA: Programmable outlets enable DIS: Programmable outlets disable (Default) 10: Programmable outlets setting ...
Page 22
13: Maximum charger current setting Interface Setting Parameter 2: Set up the charger maximum current. 1/2/4/6/8: setting the charger maximum current 1/2/4/6/8 in Ampere. (Default: 2A) Note: Please set the appropriate charger current based on battery capacity used. The recommended charging current is 0.1C~0.3C of battery capacity as following table for reference.
18: Display setting for autonomy time Interface Setting Parameter 2: Set up the display setting for autonomy time EAT: If EAT is selected, it will display the remaining autonomy time. (Default) RAT: If RAT is selected, it will show accumulated autonomy time so far.
3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail Battery voltage too high Bus over Battery voltage too low Bus under Charger output short Inverter soft start fail Over temperature Inverter voltage high Overload Inverter voltage Low Charger failure...
4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the mains is normal. connected well.
Symptom Possible cause Remedy Fault code is shown as 14 on LCD The UPS shut down Check output wiring and if display and alarm is continuously automatically because connected devices are in sounding. short circuit occurs on the short circuit status. UPS output.
Page 29
Battery Pack Specification Model DTK-UXB1000R+ DTK-UXB1500R+ DTK-UXB2000R+ DTK-UXB3000R+ Used with UPS Models DTK-UPS1000R+ DTK-UPS1500R+ DTK-UPS2000R+ DTK-UPS3000R+ Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Battery Numbers Dimensions (DxWxH) mm 380 x 438 x 88 480 x 438 x 88 600 x 438 x 88 Net Weight(kgs) 17.1...