Download Print this page

Philips EasySense SNH210 MC Quick Installation Manual page 2

Outboard-mount for high bay

Advertisement

EasySense quick guide
Wiring requirements
EASYSENSE
SR
SR
(2) 18AWG wires, non-polarized
Overall length 60cm
Strip length 8mm
Wire to wire connection
SNH200 includes 18AWG wires, 60cm in length with 8mm strip length.
A wire to wire connection can be made with connectors or wirenuts
suitable for 18AWG solid wire.
The wire strip length in case of a wire to wire connection is connector
dependent.
Sensor Dimensions, mm [in]
PLt-17265QG 04/21 philips.com/lighting page 2 of 4
Connectors
DA-
SR-
SR+
DA+
GROUND
LINE
NEUTRAL
1
63 [ 2
]
2
1
1 .5 [
]
[ 1 /2"] Straight pipe thread
1 6
21
1 43.8 [ 5
]
32
3
1 8.5 [
]
4
3
60 [ 2
]
8
XITANIUM SR
NC
LED DRIVER
NFC ANTENNA
Note: Above depicts connecting wires from sensor to Xitanium SR
drivers that include connectors. For connection to Xitanium SR drivers
that include leads, use wirenuts suitable for 18AWG solid wire.
Wire to driver connection
A connection between the sensor and the driver should be made
according to local practices. The SR input wires of the EasySense for
High Bay are not polarized for fixtures using one driver and one sensor,
and therefore can be connected, without taking care of polarity, to the
SR output of the driver – SR+ and SR- terminals. It is recommended to
keep wire distance from sensor to driver less than 50 feet. Polarity must
be maintained when connecting multiple drivers to one sensor.
The wire strip length in case of sensor to driver connection is ~8mm.
Mounting in a Luminaire
EasySense for High Bay is intended to be mounted to a standard ½"
knockout available on the luminaire itself or a junction box. A nut
is included with the sensor for this purpose. An OEM can develop
custom brackets to attach to the top surface of the sensor in case the
sensor needs to be mounted to a curved/non-flat surface. Mounting
screws are provided with the sensor for this purpose. These screws are
matched to the thickness of the plastic sensor housing and are the only
screws approved for use. Also make sure that the view of the sensor is
not blocked anywhere by the luminaire or the bracket to avoid loss of
functionality.
SNS210 MC is commissioned using the Philips field app MC, available on
both Android and iOS smartphones.
LED+
LED+
LED-
LED-
RSET2
SGND

Advertisement

loading