Clevertronics L10 LIFELIGHT PRO LLIFE-PRO-SPOT Installation & Maintenance Instructions

Surface mount spotlight emergency

Advertisement

Quick Links

Clevertest and Clevertest Plus

The Clevertronics Clever-test units (LLIFE-PRO-SPOT-CT) can be programmed to perform 90 minute
discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a
5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a
test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until LED Test Switch
indicator flashes rapidly). Refer Clever-test Operation Guide for more information. Once the test has been
completed, maintenance personnel then view the Status Indicator of each fitting to determine a pass or
failure:
NORMAL – The luminaire is in a normal state charging and awaiting
SOLID GREEN (not flashing)
next discharge test.
SLOW YELLOW FLASH
Testing – The luminaire is currently performing a test.
(2s Yellow, 2s Off)
RECENTLY PASSED – The luminaire has previously tested and
VERY SLOW YELLOW & GREEN
passed. This indication remains for 5 days after the completion of the
(4s Yellow, 1s Green)
test and then changes to SOLID GREEN to indicate a normal state.
FAILED LAST TEST – The luminaire has previously tested and failed
FAST YELLOW & GREEN FLASH
to remain illuminated for the required duration. This indication will
(0.5s Yellow, 0.5s Green)
remain until the required maintenance work has been completed and
the luminaire passes a subsequent discharge test.

Zoneworks and DATA Monitored Options

LLIFE PROs with part numbers
LLIFE-PRO-SPOT-ZW, LLIFE-PRO-SPOT-DATA
Zoneworks communications modules (nodes).These fittings are monitored using either Powerline Carrier
Technology that utilises the power cable to provide data communication or a dedicated data cable to/from
data routers installed on a dedicated data trunk connected to a central Server (can also be connected via
Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and
collate test data from each Lifelight. Zoneworks LLIFEs can be commissioned by a single push of the test
switch, or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction
indication of the status of the Lifelight during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl.
DATA version)

DALI EM Option

LLIFE PROs with part number
LLIFE-PRO-SPOT-DALI
connection and integration to 3
rd
Party Lighting Control Systems.
LLIFE-PRO-SPOT-DALI, please confirm that the Lighting Control System has the capability to monitor
DALI Emergency Luminaires. The LLIFE-PRO-SPOT-DALI will be addressed and configured into the
control system by the Lighting Control System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
"IDENTIFY COMMAND"
Fitting goes into emergency mode for 10 seconds
A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network OR a 5/6way
"structured wiring system" lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
are fitted with
are fitted with DALI modules (nodes) that facilitate
Before installing the
L10
LIFELIGHT PRO
TM
Surface Mount Spotlight Emergency
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2017
NOTE: Standard product codes with this symbol
are enabled with Clevertest Plus capability. Please
refer to the operation guide supplied with the product for
details.
Models:
LLIFE-PRO-SPOT, LLIFE-PRO-SPOT-DATA, LLIFE-PRO-SPOT-DALI, LLIFE-PRO-SPOT-ZW,
LLIFE-PRO-SPOT-CT (Note: also applies to the four hour, -4HR, variants)
240V, 50Hz

Spare Parts:

1530230
Battery, 3.3 Volt 5000mAh Li-ion (Note: 2 battery packs used on the -4HR versions)
1100869
Lifelight Pro Head Assembly, Ld:280mm,Rnd,LT,Gen 2
LLIFE-PRO-CKIT
Lifelight Pro, Control Only, L10 Lithium

Important:

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before
installation, ensure that the electricity supply has been switched off and isolated. Installation must be
carried out in accordance with the relevant Australian and International Standards.
Victoria (Head Office & Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9248 3720
Fax: +61 8 9248 3725
New Zealand
Phone: +64 800 548 448
1942032
V1.1
3 March 2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the L10 LIFELIGHT PRO LLIFE-PRO-SPOT and is the answer not in the manual?

Questions and answers

Summary of Contents for Clevertronics L10 LIFELIGHT PRO LLIFE-PRO-SPOT

  • Page 1 Clevertest and Clevertest Plus The Clevertronics Clever-test units (LLIFE-PRO-SPOT-CT) can be programmed to perform 90 minute discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a 5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until LED Test Switch...
  • Page 2 IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. Warranty: For Product Warranty information and Terms and Conditions of Sales please refer to our website http://clevertronics.com.au/terms-conditions-sale-australia-nz/...

This manual is also suitable for:

L10 lifelight pro llife-pro-spot-dataL10 lifelight pro llife-pro-spot-daliL10 lifelight pro llife-pro-spot-zwL10 lifelight pro llife-pro-spot-ct

Table of Contents