GDS XDI-XDIwin-15/30J Quick Manual

Advertisement

Quick Links

XDI-XDIwin – 15/30J
FLAMMABLE SENSOR
Power Supply
15 to 30Vdc 24v nominal
Outputs
3 wire 4~20mA / 4 wire CANbus
Relays
Low alarm
SPCO
High alarm
SPCO
Fault alarm
SPCO
Inhibit option during servicing
Logging
Intervals - variable time
Roll over/stop
Storage - 2,880 readings
Requires
RS232 lead – see 8
PC or laptop (dedicated)
Hyperterminal (download from GDS website)
Set up procedure:
New sensors are supplied ready to connect to the system.
The following procedure is for full set up and where the sensor cell has
been replaced - only sections 5, 6, 7, 9 and 1 1 need to be carried out.
Voltage measurements are made wrt AG unless otherwise specified.
1.
Insert jumpers J20 and J6 position SO for 4-20mA source output.
2.
Turn sensor voltage potentiometer anti-clockwise (minimum
voltage).
3.
Connect sensor to J2 terminal W-white Y-yellow P-pink.
4.
Connect 24V + and 0V to JP10, short the 4~20mA terminal by
inserting test link at J9.
5.
Measure the sensor voltage at SV and adjust by turning sensor
volts pot for the correct reading.
(standard sensor CAT300 = 2Vdc.) DO NOT EXCEED THE
REQUIRED VOLTAGE OTHERWISE PERMANENT DAMAGE
WILL OCCUR. See sensor cell supply table.
6.
Rotate 20mA pot fully anti-clockwise (minimum span.)
7.
When in clean air the sensor bridge is zeroed by adjusting zero
pot until the dual colour LED D1 is off.
8.
Connect PC hyper terminal using Connect RS232 micro USB or
for earlier models Combi adapter (part no. 160-510) and lead
(part no. 160-515) at 4800 baud connected to J3. Ensure jumper
J29 is fitted before programming and initialise the sensor using (C)
calibration mode, then shift + ($) command from the keyboard.
9.
Using a digital mV meter measure across test pins TP8/9 and
adjust 4mA pot for 4mA (zero) = 4mV
10. Then press (Z) on the PC to zero the reading.
1 1. Apply a known test gas to the sensor (56% LEL = 2.5% vol
methane) for 1 minute at a flow rate of 1 litre to give a 13mA =
13mV across test pins TP8/9, adjust 20mA pot for correct mV
reading.
12. When using a PC press (S) to enter span mode and using (H) or (L)
adjust the reading to 56% LEL.
13. Press (space) to exit span and then (X) to exit the calibration mode.
0-5A @ 30Vdc
An example of continuous data output to the PC from a Flammable
sensor is shown below and is the format for all gas types.
O, H and L represent the Over Range High and Low alarms
respectively.
D indicates if a duplicate address is
detected
F indicates a fault present
I shows that this sensor has its alarms
inhibited
under the O H L the ^ ^ v represent the direction of the alarms. L
is falling and H and O are rising. A(*) under the letter(s) OHLDFI
represents a detected state so in this example the sensor would be in
high alarm and a fault present.
'Gas val 35.6' represents the value of the gas present at the sensor
head. Pressing (R) on the PC causes a reset to occur. Gas type with
address and serial number are then output to the PC together with
alarms and calibration date.
A full command list via PC is available by pressing the letter (P) which
will relist on the PC.
Command
Use
A = Set CAN address
Sets the CAN address
G = Select gas type
Select the gas type from a list
Z = Zero
Press when no gas on sensor to give zero
S = Span
Use when calibration gas applied,
H and L change reading
D = Enter calibration date
Enter the calibration date
Y = Toggle auto zero
Auto zero is ON or OFF, small drift is cleared
H = Set high alarm
Sets the high alarm threshold
L = Set low alarm
Sets the low alarm threshold
O = Set over range alarm
Sets the over range alarm threshold
P = List command
List these commands on screen
X = Exit calibration mode
Exit this PC mode
$ = Initialise this sensor
Use on new PCB to set gas type to Flam
U = Alarm direction
Sets rising or falling alarms
R = Range
Allows a change in maximum value
N = Decimal points
Toggles between 1 and 2 decimal places
E = Edit user gas text
Choose gas description
B = Toggle deadband
Deadband of 2.5% can be on or off
F = Toggle fault Input
External fault input contact can be disabled
# = Normally energised
Low /high alarm relays and fault relay can be
made normally energised
V= View gas log
From current log, display how many historical
readings to display, up to 2880
% = Clear gas log
Set all 2880 log readings to 0.00
I = Log interval log
Choose how many seconds between each
reading and whether the log will roll over or
stop at 2880 (60 second interval and 2880
readings = 48 hours)
14. Connect the sensor to a Combi alarm panel and ensure that it
reports in correctly.
Note:- Fit the end of line (EOL) link J1 if the sensor is to be installed
at the end of the sensor cable.
15. If front panel display board is fitted via connector J5 and U12
adjust contrast for LCD contrast.
16. Remove J9 test link for normal operation.
17. Insert link J12 to enable the bridge fault detection.
(4-20mA output falls to 2mA in fault).
18. Ensure J29 address link is removed (this is only used when
changing address from a Panel).
www.gds–technologies.co.uk
T E C H N O L O G I E S
Technical Sheet ref C893Sv. 1 4
198D1C
Flam %LEL
O H L D F I
^^v
-*--*-Gas val = 35.6

Advertisement

loading

Summary of Contents for GDS XDI-XDIwin-15/30J

  • Page 1 ‘Gas val 35.6’ represents the value of the gas present at the sensor PC or laptop (dedicated) head. Pressing (R) on the PC causes a reset to occur. Gas type with Hyperterminal (download from GDS website) address and serial number are then output to the PC together with Set up procedure: alarms and calibration date.
  • Page 2 This document is not contractual and the equipment specification may be modified at any time without prior notice. +24V O/Pt (eg. Infrared) CAN 1 or 2 sales@gds–technologies.co.uk +44 (0)1 13 286 0166 2-Wire Direct www.gds–technologies.co.uk 4~20mA Signal GDS TECHNOLOGIES LTD FUSION POINT ASH LANE GARFORTH LEEDS LS25 2GA 204M1C Sensor Control Unit...