(6) Hardware specifications
Model
DOP-110CG
Panel type
10.4" TFT LCD (65535 colors)
Resolution
800 x 600 pixels
Display
Backlight
LED back light (half-life under room temperature 25°C > 20,000 hours)
Display range
211.2 mm * 158.4 mm
Brightness
300 cd / m² (Typ.)
CPU
ARM Cortex-A8 (800 MHz)
Flash ROM
256 Mbytes
RAM
256 Mbytes
Touchscreen
4-wire resistive touchscreen > 1,000,000 operated
Buzzer
Multi-tone frequency (2 - 4 kHz) / 80 dB
Network interface
USB
1 USB Slave Ver 2.0; 1 USB Host Ver 2.0
SD
COM1
RS-232 (supports flow control)
Serial
communication
COM2
RS-232 (supports flow control) / RS-485
port
COM3
RS-422 / RS-485
Auxiliary function key
Calendar
Cooling method
Natural cooling
CE (use shielding network cable and magnetic ring with the filter of
Approvals
300 ohm / 100 MHz)
Panel waterproof level
IP65 / NEMA4 (indoor use only)
DC +24V (-15% to +15%) (use an isolated power supply)
Operation voltage
*2
Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation)
Leakage current
500 V
for 1 minute (between DC24V terminal and FG terminal)
AC
Power consumption
*3
8 W (Max.)
3V lithium battery CR2032 × 1
Backup battery
About 3 years or more at 25°C (77°F)
Backup battery life
(subject to operation temperature and condition)
Operation temperature
0°C to 50°C (32°F to 122°F)
Storage temperature
-20°C to +60°C (-4°F to 140°F)
10% to 90% RH [0°C to 40°C (32°F to 104°F)],
Operating environment
10% to 55% RH [41°C to 50°C (105.8°F to 122°F)], pollution degree: 2
Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with amplitude
Vibration resistance
3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G
Conforms to IEC60068-2-27: 11 ms, 15 G Peak, in X, Y, Z directions each
Shock resistance
Dimensions
299 x 224 x 46.8
(W) x (H) x (D) mm
Mounting dimensions
285.2 x 210.2
(W) x (H) mm
Weight
Approx.1735 g
Note:
1. The half-life of the backlight is defined as the maximum luminance being reduced by 50% when the
maximum drive current is supplied to the HMI. The life of LED backlight shown here is estimated at the
room temperature of 25°C (77°F) with ambient humidity.
2. The withstand voltage of the isolated power circuit is 1500V peak for 1 minute.
3. The HMI power consumption is the power consumed when the HMI is not connecting with other
peripheral devices. To ensure normal operation of the HMI, the recommended capacity of the power
supply is 1.5 to 2 times of the specified power consumption.
4. Isolated power supply is recommended.
5. For the programming software DOPSoft of DOP-100 series and its user manual, you can download
them at http://www.delta.com.tw/ia.
6. DOP-100 series can be used with other industrial automation equipment. Read through this sheet
carefully and install the product according to the instructions to avoid danger.
*1
N/A
N/A
*2
*2
*2
N/A
Built-in
*3
for 6 times