  • Page 1 Expert Sensor Box 7211/7212 © 2015 Gude Analog- und Digitalsysteme GmbH Manual Ver. 2.2.0 valid from Firmware Ver. 1.0.1...
  • Page 2 Have your Gude devices always in view - and in control. With the free Gude Control App you can retrieve all relevant information from your GUDE products regardless of their current whereabouts. Check with your smartphone the important operating figures of your server and rack environment like sensor values (max/min), energy consumption as well as state of inputs and outputs with watchdog functions.
  • Page 3: Table Of Contents

    Expert Sensor Box 7211/7212 Table of content Table of contents Chapter 1 Device Description Security Advice Content of Delivery Description Installation Status LED Bootloader Mode Firmware-Update Technical Specifications Chapter 2 Configuration Configuration by Software Configuration via Webinterface 2.2.1 Configuration - IP Address 2.2.2...
  • Page 4: Chapter 1 Device Description

    · Please, never leave connected equipment unattended, that can cause damage. Content of Delivery The package includes: · expert sensor box 7211/7212 · CD-ROM and manual · Integrated P-o-E power supply (Model 7211-0 or 7212-0) · 500mA AC adaptor (Model 7211-1 or 7212-1)
  • Page 5: Installation

    Expert Sensor Box 7211/7212 Device Description Installation Connectors on the expert sensor box 7211/7212 1. Status LED 2. Bootloader Button 3. Ethernet Port (RJ45) 4. Connector for AC Adaptor (12V DC, 0,5A) The AC adaptor connnector is only built-in at the models 7211-1 and 7212-1.
  • Page 6 Expert Sensor Box 7211/7212 Device Description · Remove the power supply · Hold down the button (or the "Select" button for devices with 2 buttons). If the push button is reces- sed, use a pin or paper clip · Connect the operating voltage by Software: (only if "Enable FW to BL"...
  • Page 7: Firmware-Update

    Expert Sensor Box 7211/7212 Device Description Firmware-Update To perform a firmware update, the program GBL_Conf.exe and the latest firmware is needed. Enable the bootloader mode (see Chapter Bootloader Mode) Start GBL_Conf.exe Select the device for which a firmware update is to be performed Click "Program Device"...
  • Page 8: Configuration By Software

    To view and change the network settings, you can use the program GBL_Conf.exe. The program is available for free on our website www.gude.info and is also available on the accompanying CD-ROM. You can also use GBL_Conf.exe to install firmware updates and trigger a reset to factory defaults.
  • Page 9: Configuration - Ip Address

    Expert Sensor Box 7211/7212 Configuration Use the "Configuration" Tab to enter the configuration menu. 2.2.1 Configuration - IP Address Hostname: Here you can enter a name with up to 15 characters. This name will be used for registration on the DHCP server. Special characters and umlauts can cause problems in the network.
  • Page 10: Configuration - Ip Acl

    Expert Sensor Box 7211/7212 Configuration 2.2.2 Configuration - IP ACL Reply ICMP ping requests: If you enable this feature, the device responds to ICMP pings from the net- work. Enable IP filter: Enable or disable the IP filter here. The IP filter represents an access control for inco- ming IP packets.
  • Page 11: Configuration - Http

    Expert Sensor Box 7211/7212 Configuration 2.2.3 Configuration - HTTP HTTP port: Here can be set the port number of the internal HTTP. Possible values ? ? a re from 1 to 65534 (default: 80). If you do not use the default port, you must append the port number to the address with a colon to address the device from a web browser.
  • Page 12: Configuration - Sensors

    Expert Sensor Box 7211/7212 Configuration 2.2.4 Configuration - Sensors Choose sensor port: Selects a type of sensor to configure it. The first digit "1" indicates the number of the sensor port (only important for devices with more than one sensor port). This is followed by the sen- sor name (eg 7002 for the hybrid sensor), a letter for the sub-type sensor and the changeable sensor name.
  • Page 13: Configuration - Alarm Beeper

    Expert Sensor Box 7211/7212 Configuration 49.1 °C - is below the upper limit, but in the hysteresis range 49.0 °C - is below the upper limit, but in the hysteresis range 48.9 °C - a message is generated for underrunning the upper limit inclusive hysteresis range 2.2.5...
  • Page 14: Configuration - Syslog

    Expert Sensor Box 7211/7212 Configuration Community private: The community password for SNMP SET requests. MIB table: The download link to the text file with the MIB table for the device. Send SNMP traps: Activates the usage of SNMP traps. SNMP v1: SNMP traps are sent in SNMP v1 format.
  • Page 15: Configuration - E-Mail

    Expert Sensor Box 7211/7212 Configuration 2.2.8 Configuration - E-Mail Currently, only SMTP servers are supported, that are offering no authentication (open-relay) or unen- crypted authentication (PLAIN). An encrypted authentication to the SMTP server is not possible. An experienced user can learn whether the desired SMTP server understands the PLAIN authenticati- on, by sending the string "EHLO localhost"...
  • Page 16: Syslog

    · Exceeding of the max / min values ? ? o f attached sensors Support You will find the latest product software on our website at www.gude.info available for download. If you have further questions about installation or operation of the unit, please contact our support team. Fur- thermore, we present in our support wiki at www.gude.info/wiki FAQs and configuration examples.
  • Page 17: Declarations Of Conformity

    Technische Dokumentation zur Beurteilung von Elektro- und Elektronikgeräten hinsichtlich der Beschränkung gefährlicher Stoffe / Technical documentation for the assessment of electrical and electronic products w ith respect to the restriction of hazardous substan- Köln, 15.6.2015 Dr. Michael Gude, Geschäftsführer / General manager, CEO...