RSG CAPSULE PAK ECO Installation Manual

Refrigeration systems

Advertisement

Quick Links

CAPSULE PAK ECO™
REFRIGERATION
SYSTEMS
INSTALLATION
MANUAL
5/22 Rev. E 171551

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CAPSULE PAK ECO and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for RSG CAPSULE PAK ECO

  • Page 1 CAPSULE PAK ECO™ REFRIGERATION SYSTEMS INSTALLATION MANUAL 5/22 Rev. E 171551...
  • Page 2: Table Of Contents

    Table of Contents Refrigeration Systems-General Information Receiving Inspection Safety Information General Installation Instructions Set-Up and Installation Start Up and Operation Temperature Control Cooler Operation Freezer Operation Condensate Water Loading Product Locating and Mounting Condensing Units Maintenance Maintenance Analysis 5/22 Rev. E 171551...
  • Page 3: Refrigeration Systems-General Information

    Refrigeration Systems-General Information RECEIVING INSPECTION Congratulations on your purchase of a quality-built refrigeration system. When properly installed and maintained, this product will give many years of trouble-free service. It was shipped using trusted carriers with a history of careful handling, good customer service and prompt delivery. Even with all of these precautions, occasionally accidents may happen which result in shipping damage.
  • Page 4 This could lead to heat generation or fire. • The Capsule Pak ECO refrigeration system must be paired with a Master-Bilt or Norlake UL listed ignition protected walk-in.
  • Page 5: General Installation Instructions

    Once the Capsule Pak ECO has been lifted to the top of the walk-in, it will need to be positioned over the hole in the ceiling panel.
  • Page 6: Set-Up And Installation

    Capsule Pak ECO over the hole in the ceiling panel. Once the Capsule Pak ECO is located over the ceiling hole it should be secured in place by the four latches in the ceiling panel hole (see figure 3).
  • Page 7: Start Up And Operation

    The display will light up immediately but the unit may not start running for 1 minute. On a Low Temperature Capsule Pak ECO the evaporator fans will not run until the evaporator coil has pulled down to 40°F.
  • Page 8: Condensate Water

    General Installation Instructions CONDENSATE WATER Condensate water is collected in the drain pan under the evaporator coil and directed into a condensate evaporator pan in the condensing unit area. The condensate is then evaporated by the warm air off the condenser fan. LOADING PRODUCT Once the walk-in has been operating at the desired temperature for a sufficient period of time, product can be loaded into the refrigerated space.
  • Page 9: Maintenance

    Maintenance MAINTENANCE WARNING: When servicing any Capsule Pak ECO™ Refrigeration System or performing any maintenance procedure, always disconnect the main power supply. All service should be performed by factory authorized personnel. All component parts must be replaced with like components to minimize the risk of possible ignition due to incorrect parts or improper service.
  • Page 10: Maintenance Analysis

    Maintenance Analysis MALFUNCTION POSSIBLE CAUSE SOLUTION Compressor will not start - 1. Unplugged or power off Plug in service cord or turn power on no hum 2. Fuse blown or removed Replace fuse 3. Overload tripped Determine reasons and correct 4.
  • Page 11 5/22 Rev. E 171551...
  • Page 12 Thank you for purchasing Refrigerated Solutions Group equipment! Please visit the links below to complete your WARRANTY REGISTRATION. For Master-Bilt For Norlake Equipment Equipment master-bilt.com/register norlake.com/register Refrigerated Solutions Group 891 County Road U Hudson, WI 54016 800-955-5253 Norlake Foodservice Sales 800-477-5253 Norlake Scientific Sales 800-388-5253 Norlake Parts/Service 877-503-5253 Norlake Walk-In Installation...