49501860.3.0005 РЭ This operation manual contains information for using and operating Measuring Transducers Е855А, Е855В, Е855С, Е854А, Е854В, Е854С (further - transducers) and information on packing, transportation and storage. Read this manual before operation. 1 Description and operation 1.1 General Information Transducers are intended for a linear alternating-current converting (Е854А, Е854В, Е854С) and linear voltage converting (Е855А, Е855В, Е855С) to unified output signals of a direct current and can be applied to monitoring currents and voltages of electrical systems, in the equipment of technical di-...
49501860.3.0005 РЭ 1.2 Characteristics 1.2.1 Transducers convert input signal to direct current output signal according to table 1. Conversion function is linear. Table 1 Measurement range Output Load resistance range, Ω Type DC range, AC current, А AC voltage, V 0 –...
Page 5
49501860.3.0005 РЭ Table 2 Name of influencing magnitude Value of influencing Variation, % magnitude of the fiducial value - 30 to 50 °C ±0,4 on 10 °С of tempera- Ambient Air Temperature ture variation ±0,9 Relative Humidity to 95% at 35 °С ±0,5 Frequency 45 to 65 Hz...
49501860.3.0005 РЭ 1.3 Construction 1.3.1 General Form of the transducer can be seen in Annex A. 1.3.2 Transducer has the following parts: - Case; - Cover; - Component board; - Supply transformer; - Measuring transformer; - Latch. 1.3.3 The contacts, established on a cover, ensure strengthening a component board and reliable contact of conductors of a plated circuit to the leads.
49501860.3.0005 РЭ eedback flux Ф2 is formed by a current I2, which flows on secondary winding, being simulta- neously an output one. Unbalance signal is the voltage on a secondary winding. The СМТ output signal m oves on the circuit of selecting a module CSM and further on an input of the RMS-converter. DU consists of two log amplifiers (ОA1, ОA2) and exponentiating converter on the transistor VT1-4.
49501860.3.0005 РЭ 2 Uses to assignment 2.1 Operational constraints 2.1.1 The transducers are not intended for operation in requirements explosion-hazard and hos tile environment. 2.1 2 The transducers must not be effected by direct heat up to temperature more 50°С. The transducers should be placed on the premises without sharp temperature fluctuation and off the sources of strong electromagnetic field.
49501860.3.0005 РЭ When the rail is mounted on the vertical plane, its distortion from a horizontal position should not be more than 15°. .3.3.2 When mounting the transducer on the panel: fix a latch on the panel with the help of two screws according to figure B.2; pull the transducer over a latch against the stop.
49501860.3.0005 РЭ 3 Maintenance and repair 3.1 Safety 3.1.1 The qualified personnel should execute operations of maintenance. 3.1.2 The transducers correspond to ГОСТ Р 52319-2005 (IEC 61010-1:2001). Insulation class is primary. Pollution degree is 2. Overvoltage category III. 3.1.3 IT IS FORBIDDEN: TO C HANGE EXTERNAL CONNECTIONS, WHEN INPUT SIGNAL AND SUPPLY VOLTAGE ARE AVAILABLE IN THE TRANSDUCER.
49501860.3.0005 РЭ 3.4 Troubleshooting data 3.4.1 You can see the enumeration of possible defects and methods of their elimination in table 4. Table 4 Defect Probable reason Method of eliminat Intrinsic error exceeds an ac- The characteristics of circuit Make tuning with the h elp of ceptable value insignificantly...
49501860.3.0005 РЭ 4 Storage 4.1 Before introduction in operation the transducers should be stored in storehouses according to ГОСТ 12997-84. 4.2 Storage conditions for transducers in transport container: - Ambient Air Temperature ............5 to 50 °С; 5 °...