Special Applications; Section 4.0: Specific Applications; Section 4.1: Controlling Four Outputs From One Input - Fire-Lite Alarms FCPS-24F Installation And Operation Manual

Field charger/power supply
Table of Contents

Advertisement

C
F
HAPTER

Special Applications

4.0 Specific Applications
14
Page
Technical Manuals Online! - http://www.tech-man.com
:
OUR
4.1 Controlling Four Outputs from One Input
All four FCPS output circuits can be controlled from one control input, which in Figures
4-1a and 4-1b is illustrated as a control module. The control module can be powered
from the FCPS auxiliary 24 VDC power output (TB3 terminals 8 & 9) and supervised by
an EOL relay.
All four remote power supply outputs are shown as Notification Appliance Circuits.
Alternately, circuits 2 and/or 4 could be used as nonresettable power output circuits
which is accomplished by cutting resistors R175 for circuit 2 or R176 for circuit 4 (refer
to Figures 4-4 and 4-5).
The control module is shown to demonstrate the use of the power supply on a
multiplexed system. The control module could be replaced with any circuit capable of
polarity reversal. Note that Figure 4-1a shows Style Y configuration and Figure 4-1b
shows Style Z configuration.
Optional Style
Optional Style
Z Return
Z Return
Style Y
Style Y
*
*
CKT #1
CKT #2 CKT #3
Refer to Section 1.1 for current ratings.
Figure 4-1a: Control Module Application (Style Y)
Document # 50079 Rev. D
firealarmresources.com
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are not
required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
Style Y
*
*
CKT #4
Loop to Addressable
Control
Input #1
Control
Input #2
24 VDC NAC Power
Common
Specific
Application
Power
47 K ELR for Control Module
Part Number A2143-20 (F-ELR)
required in Canada
05/23/97
SLC
FACP
+
-
Control
Module
EOL Power
Supervision Relay
(A77-716B)