PREVENTIVE MAINTENANCE AND CALIBRATION ..........15 TECHNICAL SPECIFICATION ................... 16 9.1. Technical parameters ....................16 9.1.1. Common parameters ....................16 H5021 – CO 9.1.2. regulator ....................16 H5024 – CO 9.1.3. regulator ....................16 H6020 – temperature, relative humidity and CO 9.1.4.
Page 3
Models marked HxxxxZ are non-standard versions of the devices. Description is not included in this manual. Copyright: COMET System, Ltd. It is prohibited to copy and edit this instruction manual and make any changes at all without explicit agreement of COMET System, Ltd. All rights reserved.
Measured temperature and relative humidity are recomputed to following humidity expression: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy. Type Temperature Humidity Computed value ✓ H5021 ✓ H5024 ✓ ✓ ✓ ✓ H6020 The device is equipped with two relay outputs for alarming or controlling of external devices.
5. Description of device function and setting 5.1. Device setting from the manufacturer Value assigned to Relay1 and Relay2: none Password for setting through keys: 0000 LCD display: value shown at first LCD line: temperature / CO - by device type value shown at second LCD line: relative humidity / dew point temp.
value. This fact adds a noise of typ. ±30 ppm which has to be considered in terms of accuracy. From the principle of measurement, the measured value of CO concentration depends on the value of air pressure - altitude at the installation site. For this reason, it is suitable for accurate measurement to set the altitude of the installation site by TSensor software.
Low limit „Lo“ – the relay closes when measured value falls below preset „low limit” for longer time than preset „delay time“. Relay goes open when measured value exceeds „low limit“ value plus the „hysteresis” value. See example. Low limit „Lo“ Delay [s] Hysteresis 5.5.
5.5.2. Setting with using regulator keys If „Actual regulator preset” is displayed, it is possible to enter into edit mode and edit displayed value by pressing „SET“ key. You can edit selected value if right password is entered. During value editing there is range check executed and edited value is still compared with limits for corresponding value (range).
Page 11
Acoustic alarm deactivation activated acoustic alarm is possible to acoustic alarm is still activated for all time and deactivate by pressing „ESC“ key it is impossible to deactivate it Relay response for error Regulator continuously checks its state during operation. In case error of assigned value measurement is found then output relay: stays unchanged (in previous status) Relay1 switch OFF...
Page 12
measurement mode selection This item provides to choice if measured value is displayed and read in “SLOW” or “FAST” mode. “FAST” mode provides last measured value without averaging; this means that no software filter is used for calculating the output value. “SLOW” mode provides value averaged from last 11 measured values.
Page 13
don’t show value on LCD show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not. There is shown the name of computed value on the top LCD line – see “Computed value selection“ below.
5.6. Restore to „Factory default“ – measurement part This item provides regulator restoring to factory setting. Press „SET“ key, select „YES“ and confirm it by pressing of „SET“ key. It reset regulator parameters to following values: Value assigned to relay 1 and relay 2: none Password for setting through keys (PASS): 0000 display:...
Error 3 - there is a reading „Err3“ on LCD display upper line. Error of internal A/D converter appeared (converter does not respond, probably damage of A/D converter). At this state device does not measure temperature and relative humidity. This error does not affect CO concentration measurement.
Relays contact is not designed for direct control of line voltage! (relay contact parameters: max 220Vdc, 125Vac, 2A, 60 W, 62.5 VA) EMC: EN 61326-1, EN 55011 9.1.2. H5021 – CO regulator Concentration of CO ± (100 ppm + 5 % of measuring value) at 25°C (77°F) and 1013 hPa...
9.1.4. H6020 – temperature, relative humidity and CO regulator Temperature: ± 0,4 °C (±0,7 °F) Accuracy: -30 to +60 °C (-22 to 140 °F) Range: 0,1 °C (0,2 °F) Resolution: Relative humidity: ± 2,5 %RH from 5 to 95 %RH at 23 °C (73,4 °F) Accuracy: Range: 0 to 100 %RH...
9.1.6. Value computed from measured relative humidity and temperature Dew point temperature -60 to +80 °C (-76 to 176 °F) Range: ±1,5°C (±2,7°F) at ambient temperature T<25°C (77°F) and relative Accuracy: humidity RH >30%, for more details see graphs below Absolute humidity Range: 0 to 400 g/m...
9.2. Operating conditions Operating temperature range: -30 to +80 °C (-22 to 176 °F) electronics H5021: -30 to +60 °C (-22 to 140 °F) electronics H5024, H6020: -30 to +80 °C (-22 to +176 °F) measuring end of stem H6020: -40 to +60 °C (-40 to +140 °F)
-40 to +60 °C (-40 to 140 °F) temperature: relative humidity: 5 to 95 % RH (no condensation) 700 až 1100 hPa atmospheric pressure: Dimensions:see dimensional drawings Weight: approximately: H5021/1m probe 420 g H5021/2m probe 450 g H5021/4m probe 510 g H5024 330 g...
Page 21
10. Appendix A Connection of external power relay Coil data chart of external power relay: nominal voltage : max. 50V nominal power: max. 60VA current: max. 2A 11. Appendix B Wiring diagram of relay contacts for devices with serial number lower than 16981000.