NI-9230 Getting Started Overview This document explains how to connect to the NI-9230. In this document, the NI-9230 with screw terminal and the NI-9230 with BNC are referred to inclusively as the NI-9230. Note Before you begin, read the NI-9230 Safety, Environmental, and Regulatory Information document on ni.com/manuals...
Safety Guidelines for Hazardous Locations The NI-9230 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4 Gc and Ex nA IIC T4 Gc hazardous locations;...
II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9230 in Gas Group IIC hazardous locations, you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Furthermore, any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory rules. Notice To ensure the specified EMC performance, operate this product only with shielded cables and accessories.
Note You must use 2-wire ferrules to create a secure connection when connecting more than one wire to a single terminal on the NI-9230 with screw terminal. Each channel has a terminal to which you can connect a signal source. The AI+ terminal of the connector provides the DC excitation, when enabled, and the positive input signal connection.
You can connect ground-referenced or floating signal sources to the NI-9230. If you make a ground-referenced connection between the signal source and the NI-9230, make sure the voltage on the AI+ and the AI- connections are in the channel-to-earth safety voltage range to ensure proper operation of the NI-9230.