INSTALLATION MANUAL
DOWNFLOW SINGLE AND TWO STAGE ELECTRIC FURNACE WITH:
FACTORY INSTALLED ELECTRIC HEAT, OR
NO HEAT MODELS WITH FIELD INSTALLED ELECTRIC HEAT KITS
MODELS: WE30 SERIES
SECTION I: GENERAL
The following list includes important facts and information
regarding the electric furnace and its inclusions.
1. Furnace is rated at 240 volts AC at 60 Hertz
2. Furnace is the same size for all models
3. Four-wire thermostat operation for heating and cooling
4. A/C ready furnaces equipped with blower for A/C or
Heat Pump operation
5. Holding Strap furnished with furnace
6. This furnace is designed for downflow application
7. This furnace must not be operated without furnace door
installed
NOTE: This furnace and its components listed on the
A/C and Heat Pump equipment sticker were listed in
combination as a system by ETL for the United States.
Hamilton Home Products
LIST OF SECTIONS
1
3
4
5
7
8
LIST OF FIGURES
2
4
4
5
5
5
6
22 - Typical Two Stage Heat Pump/Heating/Cooling T'stat, Furnace 16
6
6
7
7
8
11
11
13
LIST OF TABLES
2
2
2
4
5
9
10
Blower Speed Tap Description
Tap 5 - High Speed - Cooling or Heat Pump Operation
Tap 4 - Med-High Speed - Cooling or Heat Pump Operation
Tap 3 - Medium Speed - Cooling or Heating Operation
Tap 2 - Med-Low Speed - Heating Operation
Tap 1 - Low Speed - Constant Circulation Operation Only.
Tap 1 air circulation is around 200 CFM. This is not enough
air flow for heating, cooling or heat pump operation. If Tap 1
is used for cooling the evaporator will freeze up. If Tap 1 is
used for heating with electric heat the limits will open in a
very short time frame.
DO NOT USE SPEED TAP 1 FOR HEATING OR
COOLING!
SAVE THIS MANUAL FOR FUTURE
REFERENCE
Canal Winchester, OH 43110
8
12
13
16
17
18
14
14
14
14
15
15
17
17
18
19
20
21
22
10
12
12
13
15
15
16
61MH0037A
Need help?
Do you have a question about the WE30B Series and is the answer not in the manual?
Questions and answers