Optional plate Technical specifications µ General α The ND800PA valve controller is suitable for rotary and slid- ing stem valves. Actuator connection In accordance with VDI/VDE 3845 standard (S1) or as an option compatibility with other NE-series (S2). To replace an existing NE/NP positioner,...
Page 4
Enclosure Electrical connections Material: Anodized aluminium alloy Input signal: Profibus PA Protection class: IP65, NEMA 4 and 4X according to IEC 61158-2 Mechanical position Approvals indicator: on cover Temp. ≤ +75 °C (+67 °F): Pneumatics ports: 1/4 NPT Cenelec EEx ia IIC T5/T6 (pending), Electrical connection: Screw terminals internals for 2.5 mm Temp.
Damage to the equipment and personal injury may result. If the ND800PA is supplied with valve and actuator the tubes are mounted and the ND800PA adjusted in accordance with the customer’s specificatons. If the controller is ordered separately, the CAUTION: mounting parts for the assembly must be ordered at the same time.
Mounting on EC and EJ actuators (S4) See Sections 11.6-11.9 Mount the O-rings (38) into the air connections in the bottom of the controller. Place the valve controller on top of the actuator so that the yellow mark is located in the position shown in Fig. 5. Painted See also Fig.
Spring rate (bar/psi) CAUTION: B1JK 3/43 Do not exceed the permitted supply pressure B1JSTD 4.2/61 of the ND800PA! B1JV 5.5/80 3/43 Table 1 provides the recommended tube sizes in accordance with 4.3/62 actuator sizes. Tube sizes are the minimum values allowed. For 5.6/81...
Page 8
DOUBLE-ACTING ACTUATOR 1. Self closing. Default setting: PFA = CLO ROT = cC ( lose valve to lockwise) A0 = % (acc. to valve type) cLo = 2 % NOTE: EC05 actuator requires a coupling plate 2. Self opening. Setting: PFA = OPE ROT = cC ( lose valve to lockwise) A0 = % (acc.
Chapter 6. The ND800PA stays in the selected operation mode during the Now the ND800PA will work with basic settings including 2 ± 0.5 % g and d settings. signal cutoff margins to secure full closing of the valve.
Table 3. Dead angle as percentage Control valve related settings The basic factory settings of the ND800PA assume a positioner fail Valve series action to be closing the valve and a clockwise closing direction for the position sensor. The setpoint cut-off CLOSE is set to 2 ± 0.5 %...
MAINTENANCE shown on the display. Setpoint cut-off CLOSE (cLo) The maintenance requirements of the ND800PA valve controller When cLo appears on the display, press the r key and the depend on the service conditions, for instance, the quality of instrument current default value as a percentage (%) appears on the air.
Spool valve Circuit board pack Before removing the spool valve (4) the prestage (3) must be taken Disassembly off. (See Section 5.1) Loosen the M8 screw (66) and turn the position indica- tor (65) outwards from the feedback shaft. Disassembly Unplug all wire connectors from the circuit board (5) and Unscrew the M4 screws (99, 4 pcs.) and remove the spool the signal wires from the terminal block (35).
PDM communication. See the instruc- Tighten the M3 screws. tions in the ND800PA User’s guide. Install a 0,1 mm (0.004 in) thick gauge strip between the sensor and the spiral. Press the sensor against the spiral, without using unnecessary force, and tighten the screws (116) evenly.
Table 4 lists the error messages shown on the LCD display and their by the PDM. The error message is displayed until the cause of error explanations. is eliminated and the ND800PA unit is cold-started, i.e. the fieldbus is momentarily disconnected. Cold-start can also be done using PDM.
Section 4.3 and Fig. 7 the actuator did not move or was stuck during calibration ND800PA/actuator mounting is incorrect, see Figs. 4, 5, 15 and Sections 10.2-10.6 spool valve sticks prestage is defective PDM trouble shooting is explained in the ND800PA User’s Guide.
10.1.1 General description (gold plated contacts) Protection class IP67 ND800 can be equipped with limit switches. ND800PA/K00B has 2 microswitches. Resistive load: 100 mA: 30 V DC/125 V AC (06) Limit switches are used for electrical position indication of the valves Switch accuracy: <...
10.2 Installing ND800PA/K06B on a valve 10.5 Removal of the limit switch ND800PA/K06B controller for accessing the valve controller Before the protective cover (46) can be removed the limit switch The limit switch can be installed on an existing valve controller.
11.10 Mounting parts for D/R linear actuators LEVER ARM IN MID-STROKE POSITION DISTANCE FROM THE CENTER OF FEEDBACK ARM TO THE CENTER OF ACTUATING PIN 3.57 2.87 2.50 1.00" UP TO 5.00" 1.61 STROKE @ 70° ROTATE 1.07 0.80 35° 0.71 3.50 60°...
11.12 Connections 11.12.1 Connection diagram for ND800PA/K06B LIMIT SWITCH (.../K06B) A = Open (LS2) VALVE CONTROLLER (ND800) K = Closed (LS1) ND84../X./K06BX only PG13,5 ND84../../K06B With limit switch OMRON D2VW-01 micro switches Connection diagram shows limit switch when actuator is in intermediate position.
11.12.2 Device gland receptacles +Voltage, brown - Voltage, blue Shield, black ND84.../...P1 = male type WEIDMÜLLER 945565, PG13.5/M12 +Voltage, brown - Voltage, blue Shield, grey ND84.../...P2 = male minifast type TURCK RSFV48/13.5...
CONTROL DRAWINGS 13.1 FMRC control drawing for ND84_/MU (ND84_/NU) HAZARDOUS (CLASSIFIED) LOCATION NONHAZARDOUS LOCATION Class I, Divisions 1 and 2, Groups A, B, C, D Class I, Zone 0, AEX ia, Group IIC T5/T6 T5: Ta = -40...65 C T6: Ta = -40...50 C FMRC approved associated apparatus with applicable division and group or zone and group...
Page 32
Control Drawing for Installations according to the FISCO Model: This concept may only be applied if all devices at the fieldbus line are approved and specified for the FISCO model, also the barrier of Segment coupler must be specified for the FISCO model. HAZARDOUS (CLASSIFIED) LOCATION NONHAZARDOUS LOCATION Class I, Division 1 and 2, Groups A, B, C, D...
13.2 CSA control drawing for ND84_/XU (ND84_/ZU) HAZARDOUS (CLASSIFIED) LOCATION NONHAZARDOUS LOCATION Class I, Divisions 1 and 2, Groups A, B, C, D Class I, Zone 0, AEX ia, Group IIC T5/T6 T5: Ta = -40...65 C T6: Ta = -40...50 C CSA approved associated apparatus with applicable division and group or zone and group approval e.g.:...
Page 34
Control Drawing for Installations according to the FISCO Model: This concept may only be applied if all devices at the fieldbus line are approved and specified for the FISCO model, also the barrier of Segment coupler must be specified for the FISCO model. HAZARDOUS (CLASSIFIED) LOCATION NONHAZARDOUS LOCATION Class I, Divisions 1 and 2, Groups A, B, C, D...