Page 1
All manuals and user guides at all-guides.com Pro Series DC Power Supply INSTRUCTION MANUAL 855-343-001 Models: ICT690-12S/ICT690-12SB ICT690-24S/ICT690-24SB ICT690-48S/ICT690-48SB ICT1190-12S/ICT1190-12SB ICT1190-24S/ICT1190-24SB ICT1190-48S/ICT1190-48SB “DC Power Solutions…not just components”...
Page 2
All manuals and user guides at all-guides.com WARNING Risk of serious personal injury or damage to equipment and property! Always observe the following: Install and operate unit in a Restricted Access location, such as an enclosed equipment rack Operate the supply from a grounded 3-pin 120Vac or 230Vac outlet (50 or 60Hz) with a branch circuit breaker rated 20A or less Always observe the following for applications requiring a back up battery:...
All manuals and user guides at all-guides.com Table of Contents INTRODUCTION ................... 4 CHECK and CONFIGURE UNIT ..............4 INSTALLATION ..................... 6 OPERATION ....................7 Status Indicators and Alarms ..............9 PRODUCT SPECIFICATIONS ............... 10 LIMITED WARRANTY ................. 12 Innovative Circuit Technology Ltd.
Floating Form-C alarm contact output supports remote monitoring of unit operation Model Output Max Output Continuous Voltage (V) Current (A) Current (A) ICT690-12S(B) 13.8 ICT690-24S(B) 27.6 ICT690-48S(B) 55.2 12.5 12.5 ICT1190-12S(B) 13.8 ICT1190-24S(B) 27.6 ICT1190-48S(B) 55.2 CHECK and CONFIGURE UNIT Perform a quick physical check of the unit as it is being taken out of the box to ensure it has not been damaged during shipping.
Page 5
All manuals and user guides at all-guides.com WARNING Risk of serious personal injury or damage to equipment and property! Always observe the following! If a battery is used ensure the nominal battery voltage is correct for the model of power supply, and that the battery positive is connected to the BAT positive (+) terminal and the battery negative is connected to the NEG (-) terminal.
All manuals and user guides at all-guides.com Set the max charge current to be supplied to the battery by setting SW 3, and SW 4 on the back panel according to the following chart: (note that actual current flow to the battery may be less than the setting, and is determined by the battery state of charge and temperature) Charge Charge...
All manuals and user guides at all-guides.com Connect the supply NEG bus bar to the load negative input terminal (using a supplied bus bar bolt/washer/nut set for the bus bar connection) Connect a ground bonding wire from the chassis ground stud to the rack ...
Page 8
All manuals and user guides at all-guides.com digital voltmeter. If a battery is connected install the external fuse and close the disconnect switch. On units with the battery back-up option connected switch off the ac power, and use a hand held digital voltmeter to verify that the battery voltage is provided to the output load terminal.
All manuals and user guides at all-guides.com Status Indicators and Alarms The 2 LEDs on the front panel and the Form-C alarm contacts on the back indicate the status of the power supply: Alarm or Trigger Condition LOAD BATT Green Notification Output FAULT...
All manuals and user guides at all-guides.com PRODUCT SPECIFICATIONS AC Input (IEC C 14 connector): 110 to 254Vac 50/60Hz Input Power Factor: 0.99 typ (120Vac input) Peak Efficiency (typical): Output V Line Regulation: +/- 0.1% Output V Load Regulation: +/- 1% Model: 100A 12.5A...
Page 11
All manuals and user guides at all-guides.com Alarm, on/off Connector: 5 pin removable plug, cage clamp type 16 –24 AWG Operating Temperature Range: -30C to +60°C Storage Temperature Range: -40 to +70°C Humidity: (Operating) 10 – 90% (non-condensing) (Storage) 5 – 95% (non-condensing) Cooling: Temperature controlled Regulatory Compliance:...
All manuals and user guides at all-guides.com LIMITED WARRANTY ICT Ltd. warrants to the original consumer purchaser that this product shall be in good working order, free from defects in materials and workmanship, for a period of three (3) years from the date of purchase. Should failure occur during the above stated time period, then ICT will, at its option, repair or replace this product at no additional charge except as set forth below.
Need help?
Do you have a question about the ICT690-24S and is the answer not in the manual?
Questions and answers