Piping Insulation - LG LSN HSV4 Series Installation Manual

Standard wall-mounted indoor unit
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
Connecting the Indoor Unit Piping to the Field-Installed Piping
1. Center align the indoor unit piping (refrigerant and drain) and the
field-installed piping, then hand tighten the flare nut.
2. Tighten the flare nut with a torque wrench.
3. Attach the drain tube piping to the
indoor unit drain hose as shown.
Note:
If the drain hose is routed inside a room,
add insulation to prevent condensation
from forming.
Refrigerant Piping System Insulation
All refrigerant piping including Y-branch connections, field-provided isolation ball valves, service valves, and elbows must be completely
insulated using closed cell pipe insulation (up to the indoor unit piping connections). To prevent heat loss/heat gain through the refrigerant
piping, all refrigerant piping including liquid lines and vapor lines must be insulated separately. Insulation must be a minimum 1/2" thick, and
thickness may need to be increased based on ambient conditions and local codes. Insulation for field-installed refrigerant piping must have
a minimum heat resistance of 248°F. Table 25 lists minimum wall thickness requirements for Ethylene Propylene Diene Methylene (EPDM)
insulation.
Note:
Follow locals codes when selecting EPDM insulation wall thickness. Thickness in Table 25 is based on heat conductivity of 0.61 Btu/in/h/ft2/°F.
Classification
ø1/4 inches
Liquid pipe
ø3/8 inches
≥ø1/2 inches
ø3/8 inches
ø1/2 inches
Vapor pipe
ø5/8 inches
ø3/4 inches
1. Air-conditioned, Typical location
• When piping passes through an indoor area where the indoor unit operates, such as an apartment, classroom, office, mall, hospital, etc.
2. Air-conditioned, Special location
• When the location is air conditioned, but has severe temp/humidity difference due to high ceilings, such as a church, auditorium, theater, etc.
• When the location is air conditioned, but internal temperature/humidity are high, such as a bathroom, swimming pool, locker room, etc.
3. Non-air conditioned, Typical location
• When piping passes through an indoor area where the indoor unit does not operate, such as a hallway, dormitory, or school, etc.
4. Non-air conditioned, Special location (when both conditions listed below are present)
• When piping passes through an indoor area where the indoor unit does not operate
• When the humidity is high and there is no air flow in the location where the piping is installed
Figure 43: Extending the Drain Hose.
Drain extension
Narrow tape
Adhesive
Table 25: Insulation Guidelines for Typical and Special Circumstances.
Air-conditioned location
1. Typical location
1/2 inches
1/2 inches
1/2 inches
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
PIPING CONNECTIONS
Figure 42: Indoor Unit to Field-Installed Piping Connection.
Indoor unit piping
Indoor unit
drain hose
Torque
wrench
2. Special location
3. Typical location
1/2 inches
1/2 inches
1/2 inches
1/2 inches
3/4 inches
3/4 inches

Piping Insulation

Flare nut
Field-installed
piping
Spanner
Flare nut
Field-installed
piping
Non-air conditioned location
4. Special location
1/2 inches
1/2 inches
1 inch
35

Advertisement

Table of Contents
loading

Table of Contents