Page 1
DC I/O Conversion Module FA-TB32XY User's Manual Thank you for purchasing FA Goods product. Before using, please read this User’s Manual and the relevant manuals carefully to ensure correct use. SAFETY PRECAUTIONS (Always read these precautions prior to use.) Before using this product, please read this User’s Manual and the relevant manuals carefully and pay...
Page 2
[Design Precautions] WARNING Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller, this product. Failure to do so may result in an accident due to an incorrect output or malfunction. (1) Configure external safety circuits, such as an emergency stop circuit, protection circuit, and protective interlock circuit for forward/reverse operation or upper/lower limit positioning.
Page 3
[Wiring Precautions] WARNING Shut off the external power supply for the system in all phases before installation and wiring. After wiring, attach the included terminal cover to the module before turning it on for operation. Failure to do so may result in electric shock. [Wiring Precautions] CAUTION Use applicable solderless terminals and tighten them within the specified torque range.
Page 4
[Startup and Maintenance Precautions] WARNING Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction. Shut off the external power supply for the system in all phases before cleaning the module or retightening the terminal screws, connector screws, or module fixing screws.
1.INTRODUCTION This User’s Manual describes the specifications and so on between connectors and the terminal block conversion modules used in combination with Mitsubishi Electric Corporation DC I/O modules. 2.GENERAL SPECIFICATIONS Item Specifications Operating Surrounding air 0 to 55°C temperature Storage ambient -25 to 75°C temperature Operating ambient...
3.PERFORMANCE SPECIFICATIONS Model name FA-TB32XY Item Number of I/O points 32 points, X0 to X1F / Y0 to Y1F I/O device numbers Rated voltage 24VDC (CLASS 2) Maximum usage voltage 28.8VDC (CLASS 2) (* 4) Maximum usage current Signal: 1A, Common: 2A M3 screw, Number of terminals:34P, 7.62mm pitch,...
Page 7
At positive common FA-CBLFMV LX41C4 LX42C4 MELSEC-L Series At negative common FA-CBLFMVE connector type LY41NT1P FA-CBLFMV LY42NT1P A1SX41 (Note 2) FA-TB32XY A1SX41-S1 A1SX41-S2 FA-CBLFMV A1SX42 (Note 2) A1SX42-S1 A1SX42-S2 A1SX71 At positive common FA-CBLFMV (Note 1),(Note 2) At negative common FA-CBLFMVE...
5.EXTERNAL DIMENSIONS [Unit: mm] Cable connection connector Module Module mounting hole mounting hole Simple lock DIN rail (120°) Terminal block 6.INSTALLATION METHOD Insert the connector to the back, and then fully install the connector to the programmable controller module using the mounting screws.
7.EXTERNAL CONNECTION EXAMPLE (1) When the positive common input module connection. Connection example 1 line system switch input (2) When the negative common input module connection. Connection example 1 line system switch input...
Page 10
(3) When the sink output module connection. Connection example 1 line system load (4) When the source output module connection. Connection example 1 line system load...
Page 11
8.APPLICABLE CRIMPING TERMINALS ● Size of crimping terminal [Unit:mm] Size of crimping terminal MIN 5.0 MAX 6.3 ● Terminal trapezoid [Unit:mm]...
FOR YOUR SAFETY This product has been manufactured as a general-purpose product for general industry applications, etc. The product is not intended for use in devices or systems used under conditions in which human life could be greatly affected. ...