Micro inverter packaged air-conditioners

Advertisement

Error code
Remote control:
None
1. Applicable model
All models
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note:
LED
Green
Red
Indoor Stays OFF Stays OFF
(Power supply to indoor control PCB)
Outdoor Stays OFF 2-time flash
5. Troubleshooting
Diagnosis
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
YES
Note(1) FDT, FD071-140, FDUM : F1, F2
Are fuses OK?
YES
Is DC5V
detected between �-�
of CNW1?
Note (2) � for GND
YES
Is JX1 open?
382
-
Content
Power supply system error
NO
Is
AC380/415V
for 3-phase unit detected
between 1, 2 and 3 on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
1 and 2 on the terminal
block of outdoor
unit?
YES
FDTC, FDF : F200, F201
(1)
FDEN, FDU200, 250 : Fuse between wires.
NO
Is the
check of resistance between
�-� of CNW0
OK?
YES
Is the
checked result
of resistance of FM,
etc OK?
YES
(2)
NO
NO
YES
-
'13 • PAC-T-198
Countermeasure
Defective outdoor control
NO
PCB (Noise filter)
Misconnection or breakage
of connecting wires
Defective indoor power
NO
PCB ➞ Replace.
Replace FM, etc.
NO
Replace fuse.
Defective indoor power
PCB ➞ Replace.
Open JX1.
Defective indoor control
PCB ➞ Replace.