American Standard S9V2B080D4VSAB Installer's Manual page 38

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, 2–stage condensing variable speed furnaces with variable speed draft inducer
Table of Contents

Advertisement

F F u u r r n n a a c c e e G G e e n n e e r r a a l l I I n n s s t t a a l l l l a a t t i i o o n n
Direct Vent Termination Clearances
A=
Clearance above grade, veranda, porch,
deck, or balcony
B=
Clearance to window or door that may be
opened
C=
Clearance to permanently closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
Clearance to inside corner
H=
Clearance to each side of center line
extended above meter/regulator
assembly
I=
Clearance to service regulator vent outlet
J=
Clearance to nonmechanical air supply
inlet to building or the combustion air
inlet to any other appliance
K=
Clearance to a mechanical air supply inlet
L=
Clearance above a paved sidewalk or
paved driveway located on public
property
M=
Clearance under veranda, porch, deck, or
balcony
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both
dwellings.
‡. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation
Instructions.
38
Canadian Installations
12 inches (30 cm)
6 inches (15 cm) for appliances ≤ 10,000
BTUH (3 kw), 12 inches (30 cm) for
appliances > 10,000 BTUH (3 kw) and ≤
100,000 BTUH (30 kw), 36 inches (91
cm) for appliances > 100,000 BTUH (30
kw)
*
*
*
*
*
3 feet (91 cm) with a height 15 feet (4.5
m) above the meter/regulator assembly
3 feet (91 cm)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm)
for appliances > 10,000 Btuh (3 kw) and
=/< 100,000 Btuh (30 kw), 36 inches (91
cm) for appliances > 100,000 Btuh (30
kw)
6 feet (1.83m)
7 feet (2.13 m)
12 inches (30 cm)
US Installations
12 inches (30 cm)
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm)
for appliances > 50,000 Btuh (15 kw)
*
*
*
*
*
*
*
6 inches (15 cm) for appliances =/<
10,000 Btuh (3 kw), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm)
for appliances > 100,000 Btuh (30 kw)
3 feet (91 cm) above if within 10 feet
(3m) horizontally
*
*
18-CE03D1-1F-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents