Dpa1044 Digital Input & Output Expansion Module - Omega Engineering DPA1004 User Manual

Relay & i/o expansion modules
Table of Contents

Advertisement

DPA1004 & DPA1044 Expansion Modules
DPA1044 Digital Input & Output Expansion Module
CHANNELS
SYSTEM
DIGITAL INPUT
LOGIC HIGH
DIGITAL INPUT
LOGIC LOW
DIGITAL OUTPUT
LOGIC HIGH
DIGITAL OUTPUT
LOGIC LOW
SOURCE
CURRENT
SINK
CURRENT
+5 V
TERMINAL
WEIGHT
4 digital inputs & 4 digital outputs per module
Up to 2 modules for a total of 8 inputs & 8 outputs
Note: The jumper located between the RJ45 connectors
must be removed on the second module in order for the
system to recognize it as module #2.
3 to 5 VDC
0 to 1.25 VDC
3.1 to 3.3 VDC
0 to 0.4 VDC
10 mA maximum output current
1.5 mA minimum input current
To be used as pull-up for digital inputs only.
Connect normally open pushbuttons across +5 V & DI1-4.
DO NOT use +5 V terminal (pin 1) to
power external devices.
WARNING
2.2 oz (62 g)