XIM Technologies C3-X60 Series Installation Manual

Access control panel

Advertisement

Quick Links

Installation Guide for C3-X60 Series Access
Control Panel
Version: 1.0
Date: April, 2011
About This Manual
This manual is a guide to installation and connection of the C3-X60 series access
control panel. For software using direction of the product, please refer to the user
manual.

Advertisement

Table of Contents
loading

Summary of Contents for XIM Technologies C3-X60 Series

  • Page 1 Installation Guide for C3-X60 Series Access Control Panel Version: 1.0 Date: April, 2011 About This Manual This manual is a guide to installation and connection of the C3-X60 series access control panel. For software using direction of the product, please refer to the user manual.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents 1. Important Security Instructions ............1 1.1 Important Security Instructions ..........1 1.2 Installation Cautions ..............3 2. Introduction ..................5 2.1 System Function Parameters............5 2.2 Product Technical Parameters............6 2.3 Indicators Description..............6 3. Connection and Installation ..............8 3.1 Panel Box Installation..............8 3.2 Installation and Wiring ..............9 3.3 System Structure..............10 3.4 Connection Terminals ..............12...
  • Page 5: Important Security Instructions

    1. Important Security Instructions 1. Important Security Instructions 1.1 Important Security Instructions 1. Read, follow and keep instructions: Before operating the equipment, read and follow strictly all security and operation instructions. Please keep the instructions for reference. 2. Accessories: Please use the accessories recommended by the manufacturer or delivered with the product.
  • Page 6 Installation Guide for C3-X60 Series Control Panel  The equipment is wetted or exposed to bad weather (rain, snow, etc.).  If the equipment cannot work normally even though operated as instructed, please be sure to adjust only the control components specified in the operation instructions.
  • Page 7: Installation Cautions

    1. Important Security Instructions 1.2 Installation Cautions 1. All wires must run through casing pipes, for example PVC or galvanized pipes, to prevent failure caused by rodent damage. Although a control panel is designed with good antistatic, lightning-proof, and leakage-proof functions, ensure its chassis and the AC ground wire are connected properly and the AC ground wire is grounded physically.
  • Page 8 Installation Guide for C3-X60 Series Control Panel 11. The connection between a card reader and a control panel should not be longer than 100 meters. 12. The connection between a PC and a control panel should be shorter than 1200m for RS485 communications.
  • Page 9: Introduction

    2. Introduction 2. Introduction The access control management system is a new modernized security management system, which is an effective measure for security and protection management. It is mainly used to manage entrances and exits of important places, such as banks, hotels, equipment rooms, offices, smart communities, and factories.
  • Page 10: Product Technical Parameters

    Installation Guide for C3-X60 Series Control Panel 2.2 Product Technical Parameters Working power supply: Rated voltage 12V (±20%) DC; rated current ≤0.5A. Working environment: Temperature 0°C-55°C; humidity 10%-80%. Output load: Working voltage AC ≤ 30V, rated current ≤ 8A; DC ≤ 36V, rated current ≤...
  • Page 11 2. Introduction 4. PC RS485 indicator (yellow & green): Flash state indicates it is sending or receiving data through RS485 communication; 5. CARD indicator (yellow): Flash state indicates card is punched on reader. See the indicators in the following figure: Indicators in the C3-460...
  • Page 12: Connection And Installation

    3. Connection and Installation 3. Connection and Installation 3.1 Panel Box Installation Installation steps for the control panel: Appearance and Internal of the panel box:...
  • Page 13: Installation And Wiring

    3. Connection and Installation 3.2 Installation and Wiring Access Control Panel Wire Installation Notes: 1. Before connection, make sure the power supply is disconnected. Any operation with power connected will cause severe damage to the equipment. 2. The access control wires must be separated according to heavy and light current; the control panel wires, electronic lock wires, and exit button wires must run through their respective casing pipes.
  • Page 14: System Structure

    Installation Guide for C3-X60 Series Control Panel 3.3 System Structure C3-460 System Structure  Note: The diagram above takes the C3-460 for example. By contrast, only one-door two-way access is applicable to the C3-160 system; only two-door one-way or two-door two-way access is applicable to the C3-260 system.
  • Page 15 3. Connection and Installation The access control management system consists of two parts: Management workstation (PC) and control panel. They communicate via TCP/IP or RS485 networks. On a 485 bus, each management workstation can be connected with up to 63 C3 control panels (preferably fewer than 32). The communication wires should be kept away from high-voltage wires as far as possible, and should be neither routed in parallel with nor bundled with power wires.
  • Page 16: Connection Terminals

    Installation Guide for C3-X60 Series Control Panel 3.4 Connection Terminals C3-160 terminal connection diagram:...
  • Page 17 3. Connection and Installation C3-260 terminal connection diagram:...
  • Page 18 Installation Guide for C3-X60 Series Control Panel C3-460 terminal connection diagram:...
  • Page 19 3. Connection and Installation Descriptions of the terminals: 1. The auxiliary input may be connected to infrared body detectors, fire alarms, smoke detectors, etc. 2. The auxiliary output may be connected to alarms, cameras, door bells, etc. 3. All the terminals mentioned above are set through relevant access control software.
  • Page 20: Connection With External Accessories

    Installation Guide for C3-X60 Series Control Panel 3.5 Connection with External Accessories 1. Door sensor A door sensor is used to detect the open/closed status of a door. With a door sensor switch, an access control panel can detect illegal opening of a door, and will trigger an alarm.
  • Page 21: Connection With Readers

    3. Connection and Installation Connections between C3-460 and external accessories  Note: The diagram above takes C3-460 for example. By contrast, C3-160 provides one auxiliary input interface; C3-260 provides two, and C3-460 provides four. 3.6 Connection with Readers The control panel supports inBIO biometric verification reader and Wiegand reader.
  • Page 22 Installation Guide for C3-X60 Series Control Panel In use of inBIO reader, all operations including storage, verification, etc. execute in control panel. No need to re-register the fingerprints for reader changing. Realize the real biometric reader connection. 1. Connected with inBIO readers C3-160 can connect two inBIO readers in the one-door two-way mode.
  • Page 23: Relay Output Connection

    3. Connection and Installation types of readers. If your card reader does not use the voltage of DC 12V, an external power supply is needed. A reader should be installed at a height of about 1.4 meter above the ground and at a distance of 30-50mm away from a door frame. Connection between C3-460 and Readers 3.7 Relay Output Connection C3-160 has two relays (by default, one used as a control lock and the other used as...
  • Page 24 Installation Guide for C3-X60 Series Control Panel an auxiliary output); C3-260 has four relays (by default, two used as control locks and the other two used as auxiliary outputs); C3-460 has eight relays (by default, four used as control locks and the other four used as auxiliary outputs).
  • Page 25 3. Connection and Installation 1. Wet mode: External power supply for NO Lock 2. Wet mode: External power supply for NC Lock...
  • Page 26 Installation Guide for C3-X60 Series Control Panel 3. Dry mode: External power supply for NO Lock 4. Dry mode: External power supply for NC Lock...
  • Page 27 3. Connection and Installation 5. Dry mode: NO Lock under the binary value control. 6. Dry mode: NC Lock under the binary value control.
  • Page 28: System Power Supply Structure

    Installation Guide for C3-X60 Series Control Panel 3.8 System Power Supply Structure An access control operator panel is powered by +12V DC. Generally, to reduce...
  • Page 29 3. Connection and Installation power interference between control panels, each control panel should be powered separately. When high reliability is required, control panels and electronic locks should be powered respectively. To prevent power failure of a control panel from making the whole system unable to work normally, the access control management system is usually required to have one UPS at least, and access control locks are powered externally to guarantee the access control management system can still work normally during power failure.
  • Page 30: System Networking

    4. System Networking 4. System Networking 4.1 System Wiring and Wires Requirements 1. RS485 communication wires are made of internationally accepted shielded twisted pairs, which provide effective protection and shield of interference. 2. The power supply is 12V DC converted from 220V. 3.
  • Page 31: Tcp/Ip Network Communication

    4. System Networking  Shielding measures and shielding connection: If the electromagnetic interference in the wring environment is found strong in the survey before construction, it is necessary to consider shielding protection for data cables when designing a construction scheme. Overall shielding protection is required if there is a large radioactive interference source or wiring has to be parallel with a large-current power supply on the construction site.
  • Page 32: Rs485 Network Communication

    Installation Guide for C3-X60 Series Control Panel TCP/IP Communication System Networking 4.3 RS485 Network Communication RS485 communication wires are made of internationally accepted RVSP wires (shielded twisted pairs), which prove effective to prevent and shield interference. RS485 communication wires should be connected by means of bus cascade instead of in a star form, to achieve a better shielding effect by reducing signal reflection during communications.
  • Page 33: Dip Switch Settings

    4. System Networking For this access control operator panel, putting place 8 of the DIP switch to the ON position is equivalent to parallel connection of one 120ohm resistance between the 485+ and 485- lines. As shown in the figure below, put number 8 of the DIP switches of the first and last control panels to ON position.
  • Page 34 Installation Guide for C3-X60 Series Control Panel For example, to set a device number 39=1+2+4+32, which corresponds to the binary code 111001, put number 1, 2, 3, and 6 to ON position, as illustrated below. 485 address setting table: Switch Setting Place Address Address No.
  • Page 35 4. System Networking...
  • Page 36 Installation Guide for C3-X60 Series Control Panel 2. Restoring factory setting The silk-screened 7 (number 7) of the DIP switch is the switch for restoration of system settings. The switch is set to OFF by default. When it is moved upwards and downwards for three times within 10 seconds and finally returned to OFF position, the factory settings will be restored after the access control panel is restarted.