Setting The Float Control Valve - Watts LFM110-10 Manual

Modulating float control valve

Advertisement

Valve Servicing Dimensions
A
FLOW
The following tables detail the recommended minimum valve servicing dimensions.
Globe
Size (in)
1 1/4
1 1/2
A (in)
16
16
B (in)
10
10
Angle
Size (in)
1 1/4
1 1/2
C (in)
16
16
D (in)
10
10

Setting the Float Control Valve

Step 1
Closing Speed –Turn the adjustment screw on the Closing Speed Control OUT, counterclockwise, 1½ to 2½ turns from full closed
position.
Step 2
To ensure proper operation, any trapped air will need to be bled off the valve cover during startup. The ACV includes a bleed valve, use
a flat head screwdriver to slowly open the valve (See Figure 1).
Step 3
Pressure the line, by opening the upstream isolation valve slowly.
Air is vented through the air bleed valve. Tighten the fitting when
liquid begins to vent (See Figure 1).
Step 4
Slowly open downstream isolation valve to establish flow through
the system.
IOM-ACV-110-10_6110-10 2115
B
FLOW
2
21/2
3
4
20
22
22
24
12
14
14
16
2
2 1/2
3
4
20
22
22
24
12
14
14
16
FLOW
6
8
10
32
34
38
24
26
28
6
8
10
32
34
38
24
26
28
Counterclockwise to OPEN
bleed valve
EDP#1917113
C
FLOW
12
14
16
20
44
48
52
30
34
40
12
14
16
44
48
52
30
34
40
Figure 1
Position Indicator
© 2021 Watts
D
24
56
56
48
48
3