INSTALLATION AND OPERATION MANUAL, DIRECT STEAM KETTLES MOUNTED ON GAS
BOILER CABINET BASE, GMT-6, GMT-10, GMT-6-6, GMT-10-6, GMT-10-10

3.0 OPERATION INSTRUCTIONS

WARNING: Do not force the gas control knob. Use only your hand
to turn the gas control knob. Never use any tool. If the gas control
knob will not operate by hand the gas control should be replaced by
a qualified service technician.
WARNING: Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly or repair may
damage the gas control.
WARNING: In the event of main burner ignition failure, a 5 minute
purge period must be observed prior to re-establishing ignition
source.
CAUTION: If you smell gas during the lighting procedure,
immediately shut off the gas supply until the leak has been
corrected.
For CSD-1 equipped boilers, see section 4.0 Operation Instructions for CSD-1 Equipped Boiler.
BOILER CONTROLS (Inside Cabinet)
Main Power Switch
Pilot Light
Boiler Pressure Gauge
Water Level Sight Glass
PART NUMBER 10072R1
- ON fills the boiler tank and turns the boiler controls on. You
should allow 20 minutes to fill the tank and generate steam.
-
OFF shuts off the boiler controls and opens the automatic
blowdown valve (if so equipped), emptying the boiler tank and
releasing water and steam to the drain. This should be done at
least once daily to remove sediment, lime or scale.
-
Indicates main power is ON.
-
Should read 9 - 11 psi during operation, 0 psi during shutdown.
-
Observe level of water in the boiler and water quality. Murkiness
in the water indicates inadequate water quality; the owner must
supply proper water to the boiler. See page 4 Water Quality
Statement.