Century Comfort-Aire RSG1618S1P Service Manual page 11

Table of Contents

Advertisement

It is recommended that vertical suction risers not be up-
sized. Proper oil return to the compressor should be
maintained with suction gas velocity.
Filter Drier
The filter drier is very important for proper system operation
and reliability. If the drier is shipped loose, it must be
installed by the installer in the field. Unit warranty will be
void, if the drier is not installed.
Installation of Line Sets
DO NOT fasten liquid or suction lines in direct contact with
the floor or ceiling joist. Use an insulated or suspension
type of hanger. Keep both lines separate, and always
insulate the suction line. Liquid line runs (30 feet or more)
in an attic will require insulation. Route refrigeration line
sets to minimize length.
DO NOT let refrigerant lines come in direct contact with
foundation. When running refrigerant lines through the
foundation or wall, openings should allow for a sound
and vibration absorbing material to be placed or installed
between tubing and foundation. Any gap between
foundation or wall and refrigerant lines should be filled with
a vibration damping material.
If ANY refrigerant tubing is required to be buried by state
or local codes, provide a 6 inch vertical rise at service
valve.
Installation into an Existing R-22 System
If the unit will be installed in an existing system that uses
an indoor unit or line sets charged with R-22 refrigerant,
installer must perform the following procedures to convert
the system to an R-410A system.
Remove Existing Expansion Valve
1. On fully cased coils, remove the coil access and
plumbing panels.
2.
Remove any shipping clamps from the liquid line and
distributor assembly.
3.
Disconnect the equalizer line from the check expansion
valve equalizer line fitting on the vapor line.
4.
Remove the vapor line sensing bulb.
5.
Disconnect the liquid line from the check expansion
valve at the liquid line assembly.
6.
Disconnect the check expansion valve from the liquid
line orifice housing. Take care not to twist or damage
distributor tubes during this process.
7.
Remove and discard check expansion valve and the
two Teflon® rings (see Figure 6).
8.
Use a field-provided fitting to temporarily reconnect the
liquid line to the indoor unit's liquid line orifice housing.
508228-01
CAUTION
TWO-PIECE PATCH PLATE
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
Figure 6. Remove Existing Expansion Valve
Flushing Line Sets
If the unit will be installed in an existing system that uses
an indoor unit or line sets charged with R-22 refrigerant,
installer must perform the following flushing procedure.
NOTE: Existing system components (including line set
and indoor coil) must be an AHRI match with the unit in
order to fulfill unit warranty requirements.
Refrigerant must be reclaimed in accordance with
national and local codes.
Do NOT attempt to flush and re-use existing line sets
or indoor coil when the system contains contaminants
(i.e., compressor burn out).
"Clean refrigerant" is any refrigerant in a system that
has not had compressor burnout. If the system has
experienced burnout, it is recommended that the
existing line set and indoor coil be replaced.
In lieu of R-410A, an industry-standard flushing agent
may also be used.
Issue 2136
STUB END
LIQUID LINE
ORIFICE
EXPANSION
HOUSING
VALVE
®
TEFLON
RING
EQUALIZER
LINE
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
SENSING BULB
(uncased coil shown)
WARNING
CAUTION
NOTE
NOTE
®
TEFLON
RING
SENSING
LINE
LIQUID
LINE
Page 11 of 29

Advertisement

Table of Contents
loading

Table of Contents