High Voltage - Maytag Amana VSZ14 Installation & Service Reference

Condensing unit
Table of Contents

Advertisement

5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
1
2
If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.
• If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.
If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as nec-
essary then repeat evacuation.
Electrical Connections
WARNING

HIGH VOLTAGE!

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death due to electric shock.
Wiring must conform with NEC or CEC and all
local codes. Undersized wires could cause
poor equipment performance, equipment damage
or fire.
WARNING
To avoid the risk of fire or equipment damage, use
copper conductors.
NOTICE
Units with reciprocating or rotary compressors and
non-bleed TXV's require a Hard Start Kit.
LEAK(S)
PRESENT
CONDENSIBLES OR SMALL
LEAK PRESENT
NO LEAKS
NO CONDENSIBLES
3
4
5
6
7
8
9
MINUTES
The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion. Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length.
Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit. Refer to the installa-
tion instructions supplied with the indoor furnace/air handler for
specific wiring connections and indoor unit configuration. Like-
wise, consult the instructions packaged with the thermostat
for mounting and location information.
Overcurrent Protection
The following overcurrent protection devices are approved for
use.
10
Time delay fuses
HACR type circuit breakers
These devices have sufficient time delay to permit the motor-
compressor to start and accelerate its load.
Three Phase Compressor Rotation
CAUTION
Use care when handling scroll compressors. Dome temp-
eratures could be hot.
Three phase compressors are power phase dependent and
can rotate in either direction.
Verify proper rotation for three phase compressors by ensuring
the suction pressure drops and discharge pressure rises when
the compressor is energized. NOTE: When operated in re-
verse, a three phase scroll compressors is noisier and its cur-
rent draw substantially reduced compared to marked values.
To correct, disconnect power and switch any two leads at the
unit contactor and re-observe.
High Voltage Connections
Route power supply and ground wires through the high voltage
port and terminate in accordance with the wiring diagram pro-
vided inside the control panel cover.
Low Voltage Connections
The indoor transformer must supply 24 volt AC low voltage
power to the outdoor section for the control wiring. Cooling
only units require 25VA minimum and heat pump units require
40VA minimum. Low voltage wiring for two-stage units de-
pends on the thermostat used and the number of control wires
between the indoor unit and the condensing unit. Route con-
trol wires through the low voltage port and terminate in accor-
dance with the wiring diagram provided inside the control panel
cover.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amana vsz140241Amana vsz140301

Table of Contents