Download Print this page

Wheelock 43T-G6-24 Installation Instructions

Advertisement

Quick Links

273 Branchport Ave.
Long Branch, N.J. 07740
(800) 631-2148
www.wheelockinc.com
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock's 43T Bell Series is UL Listed under Standard 464 for Audible Signal Appliances. The 43T Bell Series is also ULC
Listed under Standard CAN/ULC-S525-99 for Audible Signaling Appliances. The Bell's design features low power
consumption with a high sound output, and includes suppression to minimize the RFI generated by the contacts. The Bells are
available in either an AC model, for indoor or outdoor use in vibrating modes. Models are available with a 6" or 10" gong as
shown below. The various mounting options available for the Bell Series makes for a convenient and economical installation.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER
APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
WARNING: THE 43T HORN APPLIANCE IS A "FIRE ALARM DEVICE – DO NOT PAINT."
SPECIFICATIONS:
Model
Number
Type
43T-G6-24
43T-G6-115
AC
43T-G10-24
Vibrating
43T-G10-115
WARNING: FOR UL/ULC APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING
VOLTAGE LIMITS OF 16-33 VOLTS FOR 24V MODELS OR 96-132V FOR 115V MODELS. DO NOT APPLY 80%
AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE
CONNECTED TO THE SYSTEM'S PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE
POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO
WHICH THESE APPLIANCES ARE WIRED.
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN
EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
When calculating the total currents: Use Table 1 to determine the highest value of "RMS Current" for an individual bell (across
the expected operating voltage range of the bell), then multiply these values by the total number of bells; be sure to add the
currents for any other appliances, powered by the same source and include any required safety factors.
Copyright 2005 Wheelock, Inc. All rights reserved.
Thank you for using our products.
INSTALLATION INSTRUCTIONS
Table 1: Ratings Per UL/ULC
Gong
Rated
UL Voltage
Size
Voltage
(VRMS)
6"
24
6"
115
10"
24
10"
115
AC BELLS
. All warnings are printed in bold capital letters.
Maximum RMS
Range
Current
(VRMS)
16-33
0.666A
96-132
0.117A
16-33
0.666A
96-132
0.117A
OVERLOADING POWER SOURCES OR EXCEEDING FUSE
dBA at 10 Feet
ULC
UL 464
Anechoic
Reverberant
85
85
85
85
88
88
88
88
Mounting
Options
A,B,C,D
A,B,C,D
A,B,C,D
A,B,C,D
P10352 T
Sheet 1 of 3

Advertisement

loading

Summary of Contents for Wheelock 43T-G6-24

  • Page 1 Use this product according to this instruction manual. Please keep this instruction manual for future reference. GENERAL: Wheelock’s 43T Bell Series is UL Listed under Standard 464 for Audible Signal Appliances. The 43T Bell Series is also ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Appliances. The Bell's design features low power consumption with a high sound output, and includes suppression to minimize the RFI generated by the contacts.
  • Page 2 WIRING DIAGRAM: POS. TO NEXT SIGNAL OR PRECEDING SIGNAL OR FIRE ALARM CONTROL END OF LINE RESISTOR PANEL(FACP) (EOLR) Remove bell shell (Do not mix shells from other units.) Connect Wiring (Refer to Wiring Diagram.) Mount Bell To Backbox Using Screws Supplied With Unit. Reinstall Bell Shell (Note keyhole alignment.) MOUNTING OPTIONS: SEMI-FLUSH MOUNTING...
  • Page 3 (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty.

This manual is also suitable for:

43t-g6-11543t-g10-2443t-g10-115