Specifications (cont'd)
Response Times:
Operate
Sampling: 2 seconds
Delay-on-Make: (sampling delay) + (1.5 seconds to 5 minute delay)
adjustable in one (1) minute increments
Release
Under Voltage: 1.5 seconds (approx.)
Over Voltage: 1.5 seconds (approx.)
Frequency Shift: 1.5 seconds (approx.)
Unbalance: 2.0 seconds (approx.)
Phase Loss/Shift: 1.0 seconds (approx.)
(Total loss of operating voltage on phase A or C will result in a
release time of approximately 80 milliseconds.)
Operating Conditions:
0 °C to 55 °C (32 °F to 131 °F)
Storage Conditions:
- 45 °C to 85 °C (-49 °F to 185 ° F)
Mounting Holes:
Diameter: 3 mm (0.125")
Depth: 7 mm (0.25")
Power Required: 7 VA typical