Specifications

Blanket
Conduit
Required
Size
860–1-1/2
1/2
860–1-1/2
3/4
860–1-1/2
1
860–1-1/2
1-1/4
860–1-1/2
1-1/2
860–3
2
860–3
2-1/2
860–3
3
860–4
3–1/2
860–4
4
1
This is the maximum length which can be treated in one trial to form a bend approximately five times the conduit size.
2
Actual times may vary based on ambient temperature, wind conditions, if outside, and line voltage. (See recommended
extension cord on previous page.)
3
Schedule 20 heating times are slightly faster.
4
Type EB and DB duct heating times are approximately 2/3 of Schedule 40. Do not heat longer than necessary or
marking may occur.
Voltage:
The 860-1-1/2, 860-3 and 860-4 require 120 volts AC.
Greenlee Textron / Subsidiary of Textron Inc.
Voltage
Power
Required
Required
120 VAC
200 Watts
120 VAC
200 Watts
120 VAC
200 Watts
120 VAC
200 Watts
120 VAC
200 Watts
120 VAC
800 Watts
120 VAC
800 Watts
120 VAC
800 Watts
120 VAC
1300 Watts
120 VAC
1300 Watts
860 PVC Heating Blankets
Approximate Warm-up Time
1
Max-Bend
Angle
Sch. 40
90
3-4
90
4-5
90
5-6
45
6-7
45
6-7
90
7-8
60
8-10
60
10-12
60
8-10
30
8-10
7
4455 Boeing Dr. • Rockford, IL 61109-2988 USA • 815/397-7070
Minutes (70 F Ambient)
2
4
Sch. 80
EB, DB
4-5
5-6
6-7
7-8
7-8
4-5
7-8
4-1/2–5
11-13
12-14
8-12
12-14
6-10
12-14
6-10
3