American Standard UHMB080ACV3VB Series Installer's Manual page 37

Upflow/ horizontal and downflow/ horizontal, gas-fired, direct vent, variable speed inducer, modulating condensing communicating furnaces
Hide thumbs Also See for UHMB080ACV3VB Series:
Table of Contents

Advertisement

If the desired input rate cannot be achieved with a
change in manifold pressure, then the orifices must be
changed. See Table 16 for replacement orifice part num-
bers.
LP installations will require an orifice and gas valve
change. Order kit BAYLPKT220B or BAYLPSS220B.
IMPORTANT:
Reinstall the propane orifices to the same depth as the ori-
fices supplied with the equipment.
See Table 17 for help in selecting orifices if orifice
change is required. furnace input rate and temperature
rise should be checked again after changing orifices to
confirm the proper rate for the altitude. The vent length
table on page 19 shows the required vent lengths
for installations at various altitudes. An optional high
altitude kit is available for installations above 4000 feet
(Installations above 12,000 feet are not allowed). Use
Table 15A to select the appropriate high altitude kit for
your furnace model.
TABLE 16
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
PART
SIZE
NUMBER
44
ORF00501
45
ORF01427
46
ORF00909
47
ORF01429
48
ORF01099
49
ORF00503
50
ORF00493
51
ORF00494
Orifice 
Twist 
ALTITUDE ABOVE SEA LEVEL
Drill 
Size If 
and Orifice Required At Other Elevations
In-
stalled
At Sea
2000
3000
4000
5000
Level
42
42
43
43
43
43
44
44
44
45
44
45
45
45
46
45
46
47
47
47
46
47
47
47
48
47
48
48
49
49
48
49
49
49
50
49
50
50
50
51
50
51
51
51
51
51
51
52
52
52
52
52
53
53
53
53
54
54
54
54
54
54
55
55
55
55
55
55
55
56
56
56
56
57
57
57
58
59
59
60
58
59
60
60
61
From National Fuel Gas Code - Table F-4
DRILL
PART
SIZE
NUMBER
52
ORF00495
53
ORF00504
54
ORF00555
55
ORF00693
56
ORF01428
57
ORF00908
58
ORF01338
59
ORF01339
TABLE 17
6000
7000
8000
9000
44
44
45
46
45
46
47
47
47
47
48
48
48
48
49
49
48
49
49
50
49
50
50
51
50
50
51
51
51
51
52
52
52
52
52
53
52
53
53
53
53
53
54
54
54
54
55
55
55
55
56
56
56
56
56
56
57
58
59
59
60
61
62
63
62
62
63
63
GAS FLOW IN CUBIC FEET PER HOUR
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8
900
9
800
10
720
11
655
12
600
13
555
14
514
15
480
16
450
17
424
18
400
19
379
20
360
21
343
22
327
23
313
24
300
25
288
26
277
27
267
28
257
Note:
Natural gas input rate should be clocked at gas meter in high
heat when the gas valve is replaced or gas valve pressure
adjustments are made.
Table 19 lists the main burner orifices used with the furnace.
Table 19 ORIFICE SIZES
INPUT
RATING
BTUH
60,000
80,000
100,000
10000
120,000
Note:
47
48
The LP Conversion Kit used with the modulating furnace
50
is BAYLPSS220B or BAYLPKT220B.
50
51
52
52
52
53
54
54
55
56
57
60
63
64
18-CD30D1-20-EN
Installer's Guide
TABLE 18
2 CUBIC FOOT DIAL
29
248
50
144
30
240
51
141
31
232
52
138
32
225
53
136
33
218
54
133
34
212
55
131
35
206
56
129
36
200
57
126
37
195
58
124
38
189
59
122
39
185
60
120
40
180
62
116
41
176
64
112
42
172
66
109
43
167
68
106
44
164
70
103
45
160
72
100
46
157
74
97
47
153
76
95
48
150
78
92
49
147
80
90
MAIN BURNER ORIFICE
NUMBER
DRILL SIZE
OF
BURNERS
NAT. GAS
3
45
4
45
5
45
6
45
82
88
84
86
86
84
88
82
90
80
92
78
94
76
96
75
98
73
100
72
104
69
108
67
112
64
116
62
120
60
124
58
128
56
132
54
136
53
140
51
144
50
LP GAS