MODEL
TYPE
RATINGS ②
40% (low) heat Input BTUH
40% (low) heat Capacity BTUH (ICS) ③
100% (high) heat Input BTUH
100% (high) heat Capacity BTUH (ICS) ③
Temp. rise (Min.-Max.) °F.
AFUE
BLOWER DRIVE
Diameter - Width (In.)
No. Used
Speeds (No.)
CFM vs. in. w.g.
Motor HP
R.P.M.
Volts / Ph / Hz
FLA ⑦
COMBUSTION FAN - Type
Drive - No. Speeds
Motor HP - RPM
Volts / Ph / Hz
FLA
FILTER — Furnished?
Type Recommended
Hi Vel. (No.-Size-Thk.)
VENT Size Min. (in.)
HEAT EXCHANGER
Type
-Fired
-Unfired
Gauge (Fired)
ORIFICES — Main
Nat. Gas. Qty. — Drill Size
L.P. Gas Qty. — Drill Size ⑤
GAS VALVE
PILOT SAFETY DEVICE
Type
BURNERS — Type
Number
POWER CONN. — V / Ph / Hz ④
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs)
① Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.
② For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.
For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
③ Based on U.S. government standard tests.
④ The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
⑤ Furnace ships in natural gas configuration. The LP conversions kit used with the modulating furnace is BAYLPSS220B or BAYLPKT220B.
⑥ EnergyStar
⑦ Check motor nameplate for actual FLA
NOTE:
This furnace can be configured for Communicating or
24 VAC modes. Using fully Communicating or 24 VAC
modes, the furnace can support single or multi stage
heat pump, AC, or heating only applications. Com-
bined with a communicating Comfort Control only,
the furnace will support a single stage 24 VAC cooling
outdoor unit only.

ENERGY EFFICIENT OPERATION

Furnace is certified to leak 2% or less of nominal air
conditioning CFM delivered when pressurized to .5" water
column with all inlets, outlets, and drains sealed.
UHM-DHM-SF-1V-EN
PRODUCT SPECIFICATIONS
*DHMB060BCV3VB
*DHMB080ACV3VB
Downflow / Horizontal
Downflow / Horizontal
24,000
23,000
60,000
57,000
30 - 60
95.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
See Fan Performance Table
1/2
Variable
115/1/60
6.4
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
1.0
Yes
High Velocity
2 - 14x20 - 1 in.
2 Round
Aluminized Steel - Type I
Aluminized Steel - Type I
20
3 — 45
3 — 56
Modulating
Hot Surface Igniter
Multiport Inshot
3
115/1/60
9.2
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
41-3/4 x 19-1/2 x 30-1/2
160/ 146
*DHMC100ACV4VB
Downflow / Horizontal
32,000
32,000
80,000
76,000
35 - 65
96.0
DIRECT
10 x 8
1
Variable
See Fan Performance Table
1/2
Variable
115/1/60
6.4
Centrifugal
Centrifugal
Direct - Variable
Direct - Variable
1/50 - 5000
1/50 - 5000
115/3/60
1.0
Yes
High Velocity
High Velocity
2 - 16x20 - 1 in.
2 - 14x20 - 1 in.
2 Round
2.5 Round
Aluminized Steel - Type I
20
4 — 45
4 — 56
Modulating
Modulating
Hot Surface Igniter
Hot Surface Igniter
Multiport Inshot
Multiport Inshot
4
115/1/60
9.2
15
1/2
H x W x D
H x W x D
41-3/4 x 23 x 30-1/2
168 / 158
NOTE:
CONTINUOUS fan mode during COOLING operation
may not be appropriate in humid climates. If the in-
door air exceeds 60% relative humidity or simply feels
uncomfortably humid, it is recommended that the fan
only be used in the AUTO mode.
A communicating comfort control will disable a con-
tinuous fan call if the relative humidity exceeds the set
point. See the Troubleshooting Information section of
the Communicating Comfort Control Installer's Guide
for details.
Service Facts
*DHMD120BCV5VB
Downflow / Horizontal
40,000
48,000
39,000
47,000
100,000
120,000
96,000
114,000
35 - 65
40 - 70
96.0
95.0
DIRECT
DIRECT
10 x 10
10 x 10
1
1
Variable
Variable
See Fan Performance Table
3/4
1
Variable
Variable
115/1/60
115/1/60
8.0
10.0
Centrifugal
Direct - Variable
1/50 - 5000
115/3/60
115/3/60
1.0
1.0
Yes
Yes
High Velocity
2 - 16x20 - 1 in.
3 Round
Aluminized Steel - Type I
20
20
6 — 45
5 — 45
6 — 56
5 — 56
Modulating
Hot Surface Igniter
Multiport Inshot
6
5
115/1/60
115/1/60
13.7
11.2
15
15
1/2
1/2
H x W x D
41-3/4 x 26-1/2 x 30-1/2
206 / 196
185 / 175
3